Table 4 — ICVC Alert Codes (cont)

CHILLER ALERTS

ICVC FAULT

PRIMARY

SECONDARY

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

STATE

MESSAGE

MESSAGE

 

 

140

SENSOR ALERT

LEAVING COND WATER

140Sensor Fault: Check

Check sensor resistance or voltage drop.

 

 

TEMP

Leaving Cond Water Sensor.

Check for proper wiring.

141

SENSOR ALERT

ENTERING COND WATER

141Sensor Fault: Check

Check sensor resistance or voltage drop.

 

 

TEMP

Entering Cond Water Sensor.

Check for proper wiring.

142

LOW OIL

CHECK OIL FILTER

142Low Oil Pressure Alert.

Check for partially or closed shut-off valves.

 

PRESSURE ALERT

 

Check Oil Filter.

Check oil filter.

 

 

 

 

Check oil pump and power supply.

 

 

 

 

Check oil level.

 

 

 

 

Check for foaming oil at start-up.

 

 

 

 

Check transducer wiring and accuracy.

143

AUTORESTART

LINE CURRENT

143Line Current Imbal-

Power loss has been detected in any phase.

 

PENDING

IMBALANCE

ance: Check VFD Fault His-

Chiller automatically restarting.

 

 

 

tory for Values.

 

144

AUTORESTART

LINE VOLTAGE

144Single Cycle Line

A drop in line voltage has been detected within

 

PENDING

DROP OUT

Voltage Dropout.

2 voltage cycles.

 

 

 

 

Chiller automatically restarting if Auto Restart is

 

 

 

 

enabled in OPTIONS screen.

145

AUTORESTART

HIGH LINE VOLTAGE

145High Percent Line

Check phase to phase and phase to ground line

 

PENDING

 

Voltage [VALUE].

power.

146

AUTORESTART

LOW LINE VOLTAGE

146Low Percent Line

Check phase to phase and phase to ground line

 

PENDING

 

Voltage [VALUE].

power.

147

AUTORESTART

VFD MODULE RESET

147->VFD Module Power-On

VFD Module has detected a hardware fault due

 

PENDING

 

Reset When Running.

to electrical noise, power loss or software and

 

 

 

 

has reset. Chiller automatically restarting.

 

 

 

 

Check for power loss and sources of electro-

 

 

 

 

magnetic interference.

148

AUTORESTART

POWER LOSS

148Control Power-Loss

Check 24 vac control power supply to ICVC.

 

PENDING

 

When Running.

 

149

SENSOR ALERT

HIGH DISCHARGE TEMP

149Comp Discharge Temp

Check sensor resistance or voltage drop.

 

 

 

[VALUE] Exceeded Limit of

Check for proper wiring.

 

 

 

[LIMIT]*.

Check for proper inlet guide vane and optional

 

 

 

 

diffuser actuator operation.

 

 

 

 

Check for proper condenser flow and

 

 

 

 

temperature.

 

 

 

 

Check for high lift or low load.

 

 

 

 

Check for fouled tubes or noncondensables in

 

 

 

 

the chiller.

150

SENSOR ALERT

HIGH BEARING

150Comp Thrust Brg Temp

Check sensor resistance or voltage drop.

 

 

TEMPERATURE

[VALUE] exceeded limit of

Check for proper wiring.

 

 

 

[LIMIT]*.

Check for partially closed service valves.

 

 

 

 

Check oil cooler TXV.

 

 

 

 

Check oil level and oil temperature.

151

CONDENSER

PUMP RELAY

151High Condenser Pres-

Check sensor wiring and accuracy.

 

PRESSURE ALERT

ENERGIZED

sure [VALUE]: Pump Ener-

Check condenser flow and water temperature.

 

 

 

gized to Reduce Pressure.

Check for fouled tubes.

 

 

 

 

This alarm is not caused by the High Pressure

 

 

 

 

Switch.

152

RECYCLE ALERT

EXCESSIVE RECYCLE

152Excessive recycle

Chiller load is too low to keep compressor on

 

 

STARTS

starts.

line and there has been more than 5 starts in

 

 

 

 

4 hours.

 

 

 

 

Increase chiller load, adjust hot gas bypass,

 

 

 

 

increase RECYCLE RESTART DELTA T from

 

 

 

 

SETUP1 Screen.

153

no message:

no message; ALERT only

153Lead/Lag Disabled-

Illegal chiller address configuration in Lead/Lag

 

ALERT

 

Config: Duplicate Chiller

screen. Both chillers require a different address.

 

only

 

Address.

 

154

POTENTIAL

COND PRESS/TEMP

154Condenser freeze up

The condenser pressure transducer is reading a

 

FREEZE-UP

TOO LOW

prevention.

pressure that could freeze the condenser tubes.

 

 

 

 

Check for condenser refrigerant leaks.

 

 

 

 

Check fluid temperature.

 

 

 

 

Check sensor wiring and accuracy.

 

 

 

 

Place the chiller in PUMPDOWN mode if the

 

 

 

 

vessel is evacuated.

155

OPTION SENSOR

REMOTE RESET

155Sensor Fault/Option

Check sensor resistance or voltage drop.

 

FAULT

SENSOR

Disabled: Remote Reset

Check for proper wiring to CCM connector J4.

 

 

 

Sensor.

 

156

OPTION SENSOR

AUTO CHILLED WATER

156Sensor Fault/Option

Check sensor resistance or voltage drop.

 

FAULT

RESET

Disabled: Auto Chilled Water

Check for proper wiring to CCM connector J5.

 

 

 

Reset.

 

157

OPTION SENSOR

AUTO DEMAND LIMIT

157Sensor Fault/Option

Check sensor resistance or voltage drop.

 

FAULT

INPUT

Disabled: Auto Demand Limit

Check for proper wiring to CCM connector J5.

 

 

 

Input.

 

158

SENSOR ALERT

SPARE TEMPERATURE

158Spare Temperature 1

Check sensor resistance or voltage drop.

 

 

#1

[VALUE] exceeded limit of

Check for proper wiring to CCM connector J4.

 

 

 

[LIMIT]*.

Check Spare Temp #1 Limit in SETUP1 screen.

*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

13

Page 13
Image 13
Carrier 19XRV Primary Secondary Primary Cause Additional CAUSE/REMEDY, Sensor Alert, Low Oil, Pressure Alert, Autorestart

19XRV specifications

The Carrier 19XRV is a cutting-edge rooftop chiller designed to provide reliable and efficient cooling solutions for a wide range of applications, including commercial buildings and industrial facilities. This advanced system integrates the latest technologies and innovative features to ensure optimal performance, energy efficiency, and ease of use.

One of the most prominent features of the 19XRV is its advanced inverter-driven compressor technology. This allows the chiller to adjust its capacity seamlessly based on the building's cooling demand. By varying the speed of the compressor, the 19XRV maximizes energy efficiency and minimizes operational costs, especially during partial load conditions. This capability not only enhances comfort but also contributes to reduced energy consumption, making it a sustainable choice for environmentally conscious users.

In addition to the inverter technology, the 19XRV incorporates a microchannel coil design. This design optimizes heat exchange efficiency and reduces the refrigerant charge, which is an essential factor in lowering greenhouse gas emissions. The microchannel coils also allow for more compact dimensions, making installation easier and maximizing rooftop space usage.

Another significant aspect of the Carrier 19XRV is its robust controls system. Equipped with Carrier’s advanced ComfortLink™ controls, this chiller offers precise monitoring and control over its operation. Users can easily integrate the chiller into building management systems for real-time data access and efficiency analytics. This connectivity ensures that operators can make informed decisions to optimize performance continuously.

The 19XRV also includes features aimed at enhancing reliability and durability. Its structural design incorporates corrosion-resistant materials, allowing the unit to withstand harsh environmental conditions. This reliability translates to lower maintenance requirements and extended equipment lifespan, providing excellent value over time.

Moreover, the chiller is designed for quiet operation, making it suitable for applications where low noise levels are essential. Sound-dampening measures ensure that the 19XRV can be utilized in urban environments or near sensitive areas without causing disturbances.

In conclusion, the Carrier 19XRV is a state-of-the-art rooftop chiller that combines efficiency, technology, and durability. Its inverter-driven compressor, microchannel coil design, advanced controls, and robust construction make it an ideal choice for those looking to maintain comfort while minimizing energy usage and environmental impact. Whether for commercial or industrial applications, the 19XRV stands out as a reliable and innovative cooling solution for the modern age.