Carrier Understanding Alarm Codes for Air Conditioners

Models: 19XRV

1 40
Download 40 pages 42.18 Kb
Page 16
Image 16

Table 5 — ICVC Alarm Codes (cont)

CHILLER PROTECTIVE LIMIT FAULTS (cont)

ICVC FAULT

PRIMARY

SECONDARY

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

STATE

MESSAGE

MESSAGE

 

 

220

PROTECTIVE LIMIT

GROUND FAULT

220Ground Fault Trip;

Check for condensation on motor terminals.

 

 

 

Check Motor and Current

Check motor power leads for phase to phase or

 

 

 

Sensors.

phase to ground shorts. Disconnect motor from

 

 

 

 

VFD and megger motor.

 

 

 

 

Call Carrier Service.

221

PROTECTIVE LIMIT

UNUSED

221UNUSED

 

222

PROTECTIVE LIMIT

LINE FREQUENCY TRIP

222Line Frequency —

If operating from a generator, check generator

 

 

 

[VALUE] exceeded limit of

size and speed.

 

 

 

[LIMIT]; Check Power Supply.

Check utility power supply.

223

LOSS OF

WITH VFD GATEWAY

223Loss of SIO Comm with

Check VFD communication wiring and

 

COMMUNICATION

MODULE

VFD Gateway: Check VFG

connectors on VFD Gateway and DPI board.

 

 

 

Module and Power.

Check for compatibility between ICVC and

 

 

 

 

Gateway software.

224

PROTECTIVE LIMIT

VFD COMMUNICATIONS

224Loss of DPI Comm with

Check VFD communication wiring and

 

 

FAULT

VFD Gateway: Check VFG to

connectors.

 

 

 

VFD Comm.

Check status lights on DPI Communications

 

 

 

 

Interface Board.

 

 

 

 

Call Carrier Service.

225

PROTECTIVE LIMIT

MOTOR CURRENT

225Motor Current Imbal-

Check Motor Current % Imbalance in

 

 

IMBALANCE

ance: Check VFD Fault

VFD_CONF screen.

 

 

 

History for Values.

 

226

PROTECTIVE LIMIT

LINE PHASE REVERSAL

226Line Phase Reversal:

Reverse connections of any two line conductors

 

 

 

Check Line Phases.

to circuit breaker.

227

PROTECTIVE LIMIT

OIL PRESS SENSOR

227Oil Pressure Delta P

Check transducer wiring and accuracy.

 

 

FAULT

[VALUE] (Pump Off): Check

Check power supply to pump.

 

 

 

Pump/Transducers.

Check pump operation.

 

 

 

 

Check transducer calibration.

228

PROTECTIVE LIMIT

LOW OIL PRESSURE

228Low Operating Oil

Check transducer wiring and accuracy.

 

 

 

Pressure [VALUE]: Check Oil

Check power supply to pump.

 

 

 

Pump and Filter.

Check pump operation.

 

 

 

 

Check oil level.

 

 

 

 

Check for partially closed service valves.

 

 

 

 

Check oil filters.

 

 

 

 

Check for foaming oil at start-up.

 

 

 

 

Check transducer calibration.

229

PROTECTIVE LIMIT

LOW CHILLED WATER

229Low Chilled Water Flow;

Perform pump control test.

 

 

FLOW

Check Switch/Delta P Config

Check optional transducer calibration and

 

 

 

& Calibration.

wiring.

 

 

 

 

Check Evaporator Refrigerant Temperature

 

 

 

 

sensor.

 

 

 

 

Check chilled water valves.

 

 

 

 

Check for evaporator saturation temperature

 

 

 

 

< 34 F if not in Pumpdown Lockout mode. Place

 

 

 

 

unit in Pumpdown mode before removing

 

 

 

 

charge.

230

PROTECTIVE LIMIT

LOW CONDENSER

230Low Condenser Water

Perform pump control test.

 

 

WATER FLOW

Flow; Check Switch/Delta P

Check optional transducer calibration and

 

 

 

Config & Calibration.

wiring.

 

 

 

 

Check condenser water valves.

 

 

 

 

Check for COND PRESS OVERRIDE + 5 psig.

231

PROTECTIVE LIMIT

HIGH DISCHARGE TEMP

231Comp Discharge Temp

Check for closed compressor discharge isola-

 

 

 

[VALUE] Exceeded Limit of

tion valve.

 

 

 

[LIMIT]*.

Check if chiller was operating in surge.

 

 

 

 

Check sensor resistance or voltage drop.

 

 

 

 

Check for proper wiring.

 

 

 

 

Check for proper condenser flow and

 

 

 

 

temperature.

 

 

 

 

Check compressor discharge isolation valve.

 

 

 

 

Check for proper inlet guide vane and optional

 

 

 

 

diffuser actuator operation.

232

PROTECTIVE LIMIT

LOW REFRIGERANT

232Evaporator Refrig Temp

Check for proper refrigerant charge.

 

 

TEMP

[VALUE] exceeded limit of

Check float valve operation.

 

 

 

[LIMIT]*.

Check for closed condenser liquid line isolation

 

 

 

 

valve. If problem occurs at high load, check for

 

 

 

 

low condenser pressure which causes inade-

 

 

 

 

quate flasc orifice differential pressure.

 

 

 

 

Check for proper water flow and temperature.

 

 

 

 

Confirm that condenser water enters bottom row

 

 

 

 

of condenser tubes first.

 

 

 

 

Check Evaporator Refrigerant Temperature

 

 

 

 

sensor.

 

 

 

 

Check for division plate gasket bypass.

 

 

 

 

Check for fouled tubes.

*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

16

Page 16
Image 16
Carrier 19XRV specifications Protective Limit

19XRV specifications

The Carrier 19XRV is a cutting-edge rooftop chiller designed to provide reliable and efficient cooling solutions for a wide range of applications, including commercial buildings and industrial facilities. This advanced system integrates the latest technologies and innovative features to ensure optimal performance, energy efficiency, and ease of use.

One of the most prominent features of the 19XRV is its advanced inverter-driven compressor technology. This allows the chiller to adjust its capacity seamlessly based on the building's cooling demand. By varying the speed of the compressor, the 19XRV maximizes energy efficiency and minimizes operational costs, especially during partial load conditions. This capability not only enhances comfort but also contributes to reduced energy consumption, making it a sustainable choice for environmentally conscious users.

In addition to the inverter technology, the 19XRV incorporates a microchannel coil design. This design optimizes heat exchange efficiency and reduces the refrigerant charge, which is an essential factor in lowering greenhouse gas emissions. The microchannel coils also allow for more compact dimensions, making installation easier and maximizing rooftop space usage.

Another significant aspect of the Carrier 19XRV is its robust controls system. Equipped with Carrier’s advanced ComfortLink™ controls, this chiller offers precise monitoring and control over its operation. Users can easily integrate the chiller into building management systems for real-time data access and efficiency analytics. This connectivity ensures that operators can make informed decisions to optimize performance continuously.

The 19XRV also includes features aimed at enhancing reliability and durability. Its structural design incorporates corrosion-resistant materials, allowing the unit to withstand harsh environmental conditions. This reliability translates to lower maintenance requirements and extended equipment lifespan, providing excellent value over time.

Moreover, the chiller is designed for quiet operation, making it suitable for applications where low noise levels are essential. Sound-dampening measures ensure that the 19XRV can be utilized in urban environments or near sensitive areas without causing disturbances.

In conclusion, the Carrier 19XRV is a state-of-the-art rooftop chiller that combines efficiency, technology, and durability. Its inverter-driven compressor, microchannel coil design, advanced controls, and robust construction make it an ideal choice for those looking to maintain comfort while minimizing energy usage and environmental impact. Whether for commercial or industrial applications, the 19XRV stands out as a reliable and innovative cooling solution for the modern age.