Table 4 — ICVC Alert Codes

PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is necessary.

ICVC FAULT

PRIMARY

SECONDARY

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

STATE

MESSAGE

MESSAGE

 

 

100

PRESTART

STARTS LIMIT

100Excessive compressor starts

Depress the RESET softkey if additional start

 

ALERT

EXCEEDED

(8 in 12 hours).

is required. Reassess start-up requirements.

101

PRESTART

HIGH BEARING

101Comp Thrust Brg Temp [VALUE]

Check oil heater for proper operation.

 

ALERT

TEMPERATURE

exceeded limit of [LIMIT]*.

Check for low oil level, partially closed oil sup-

 

 

 

 

ply valves, clogged oil filters.

 

 

 

 

Check the sensor wiring and accuracy.

 

 

 

 

Check Comp Thrust Brg Alert setting in

 

 

 

 

SETUP1 screen.

102

PRESTART

HIGH MOTOR

102Comp Motor Winding Temp

Check motor sensors for wiring and accuracy.

 

ALERT

TEMPERATURE

[VALUE] exceeded limit of [LIMIT]*.

Check motor cooling line for proper operation,

 

 

 

 

or restrictions.

 

 

 

 

Check for excessive starts within a short time

 

 

 

 

span.

 

 

 

 

Check Comp Motor Temperature Override

 

 

 

 

setting in SETUP1 screen.

103

PRESTART

HIGH

103Comp Discharge Temp [VALUE]

Allow discharge sensor to cool.

 

ALERT

DISCHARGE

exceeded limit of [LIMIT]*.

Check sensor wiring and accuracy.

 

 

TEMP

 

Check for excessive starts.

 

 

 

 

Check Comp Discharge Alert setting in

 

 

 

 

SETUP1 screen.

104

PRESTART

LOW

104Evaporator Refrig Temp [VALUE]

Check transducer wiring and accuracy.

 

ALERT

REFRIGERANT

exceeded limit of [LIMIT]*.

Check for low chilled fluid supply

 

 

TEMP

 

temperatures.

 

 

 

 

Check refrigerant charge.

 

 

 

 

Check Refrig Override Delta T in SETUP1

 

 

 

 

screen.

105

PRESTART

LOW OIL

105Oil Sump Temp [VALUE]

Check oil heater contactor/relay and power.

 

ALERT

TEMPERATURE

exceeded limit of [LIMIT]*.

Check oil level and oil pump operation.

106

PRESTART

HIGH

106Condenser Pressure [VALUE]

Check transducer wiring and accuracy.

 

ALERT

CONDENSER

exceeded limit of [LIMIT]*.

Check for high condenser water

 

 

PRESSURE

 

temperatures.

 

 

 

 

Check high condenser pressure switch wiring.

107

PRESTART

LOW LINE

107Percent Line Voltage [VALUE]

Check voltage supply.

 

ALERT

VOLTAGE

exceeded limit of [LIMIT]*.

Check voltage transformers and switch gear.

 

 

 

 

Consult power utility if voltage is low.

108

PRESTART

HIGH LINE

108Percent Line Voltage [VALUE]

Check voltage supply.

 

ALERT

VOLTAGE

exceeded limit of [LIMIT]*.

Check power transformers.

 

 

 

 

Consult power utility if voltage is high.

109

PRESTART

GUIDE VANE

109Actual Guide Vane Pos

Press STOP button on ICVC and perform

 

ALERT

CALIBRATION

Calibration Required Before Startup.

Guide Vane Calibration in Controls Test

 

 

 

 

screen.

 

 

 

 

Check guide vane actuator feedback

 

 

 

 

potentiometer.

110

PRESTART

HIGH

110Rectifier Temperature [VALUE]

Check that VFD refrigerant isolation valves

 

ALERT

RECTIFIER

exceeded limit of [LIMIT]*.

are open.

 

 

TEMP

 

Check VFD refrigerant cooling solenoid and

 

 

 

 

refrigerant strainer.

 

 

 

 

Check for proper VFD cooling fan operation

 

 

 

 

and blockage.

111

PRESTART

HIGH

111Inverter Temperature [VALUE]

Check that VFD refrigerant isolation valves

 

ALERT

INVERTER

exceeded limit of [LIMIT]*.

are open.

 

 

TEMP

 

Check VFD refrigerant cooling solenoid and

 

 

 

 

refrigerant strainer.

 

 

 

 

Check for proper VFD cooling fan operation

 

 

 

 

and blockage.

*[LIMIT] is shown on the ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

11

Page 11
Image 11
Carrier 19XRV specifications Icvc Alert Codes, Message, Prestart

19XRV specifications

The Carrier 19XRV is a cutting-edge rooftop chiller designed to provide reliable and efficient cooling solutions for a wide range of applications, including commercial buildings and industrial facilities. This advanced system integrates the latest technologies and innovative features to ensure optimal performance, energy efficiency, and ease of use.

One of the most prominent features of the 19XRV is its advanced inverter-driven compressor technology. This allows the chiller to adjust its capacity seamlessly based on the building's cooling demand. By varying the speed of the compressor, the 19XRV maximizes energy efficiency and minimizes operational costs, especially during partial load conditions. This capability not only enhances comfort but also contributes to reduced energy consumption, making it a sustainable choice for environmentally conscious users.

In addition to the inverter technology, the 19XRV incorporates a microchannel coil design. This design optimizes heat exchange efficiency and reduces the refrigerant charge, which is an essential factor in lowering greenhouse gas emissions. The microchannel coils also allow for more compact dimensions, making installation easier and maximizing rooftop space usage.

Another significant aspect of the Carrier 19XRV is its robust controls system. Equipped with Carrier’s advanced ComfortLink™ controls, this chiller offers precise monitoring and control over its operation. Users can easily integrate the chiller into building management systems for real-time data access and efficiency analytics. This connectivity ensures that operators can make informed decisions to optimize performance continuously.

The 19XRV also includes features aimed at enhancing reliability and durability. Its structural design incorporates corrosion-resistant materials, allowing the unit to withstand harsh environmental conditions. This reliability translates to lower maintenance requirements and extended equipment lifespan, providing excellent value over time.

Moreover, the chiller is designed for quiet operation, making it suitable for applications where low noise levels are essential. Sound-dampening measures ensure that the 19XRV can be utilized in urban environments or near sensitive areas without causing disturbances.

In conclusion, the Carrier 19XRV is a state-of-the-art rooftop chiller that combines efficiency, technology, and durability. Its inverter-driven compressor, microchannel coil design, advanced controls, and robust construction make it an ideal choice for those looking to maintain comfort while minimizing energy usage and environmental impact. Whether for commercial or industrial applications, the 19XRV stands out as a reliable and innovative cooling solution for the modern age.