Carrier 19XRV specifications Unused State

Models: 19XRV

1 40
Download 40 pages 42.18 Kb
Page 18
Image 18

Table 5 — ICVC Alarm Codes (cont)

CHILLER PROTECTIVE LIMIT FAULTS (cont)

ICVC FAULT

PRIMARY

SECONDARY

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

STATE

MESSAGE

MESSAGE

 

 

245

PROTECTIVE LIMIT

HIGH VFD SPEED

245Actual VFD Speed

Actual VFD Speed on COMPRESS screen must

 

 

 

exceeded limit of Target VFD

not exceed Target VFD Speed by more than

 

 

 

Speed + 10%.

10%.

246

PROTECTIVE LIMIT

INVALID DIFFUSER

246Diffuser Control Invalid

Check 25%, 50%, and 75% Guide Vane and Dif-

 

 

CONFIG.

Configuration: Check SETUP2

fuser Load Point entries in SETUP2 screen.

 

 

 

Entries.

 

247

PROTECTIVE LIMIT

DIFFUSER POSITION

247Diffuser Position Fault:

Confirm that Diffuser Option in SETUP 2 screen

 

 

FAULT

Check Guide Vane/Diffuser

has not been Enabled if compressor does not

 

 

 

Actuator.

have a split ring diffuser. May indicate rotating

 

 

 

 

stall condition.

 

 

 

 

Check rotating stall transducer wiring accuracy

 

 

 

 

and sealing.

 

 

 

 

Check diffuser schedule and guide vane sched-

 

 

 

 

ule in SETUP2 screen.

 

 

 

 

Check for proper operation of diffuser and inlet

 

 

 

 

guide vane actuators including inlet guide vane

 

 

 

 

calibration.

 

 

 

 

Check diffuser actuator coupling for rotational

 

 

 

 

slip.

 

 

 

 

Check RC snubber on CCM J4-23 and J4-24.

 

 

 

 

Check 4.3k ohm resistor between CCM termi-

 

 

 

 

nals J3-7 and J3-8.

 

 

 

 

Check for electrical noise in CCM Diffuser Pres-

 

 

 

 

sure wiring. Do not continue to operate com-

 

 

 

 

pressor except for diagnostic purposes.

248

PROTECTIVE LIMIT

SPARE TEMPERATURE

248Spare Temperature #1

Check Spare Temperature Enable and Spare

 

 

#1

[VALUE] exceeded limit of

Temperature Limit in SETUP1 Screen.

 

 

 

[LIMIT]*.

 

249

PROTECTIVE LIMIT

SPARE TEMPERATURE

249Spare Temperature #2

Check Spare Temperature Enable and Spare

 

 

#2

[VALUE] exceeded limit of

Temperature Limit in SETUP1 Screen.

 

 

 

[LIMIT]*.

 

250

UNUSED

UNUSED

250Unused State.

 

251

PROTECTIVE LIMIT

VFD CONFIG CONFLICT

251VFD Config Conflict

The VFD_CONF table in the Gateway does not

 

 

 

(VFD Uploaded): Verify to

match that which is in the ICVC. This is a normal

 

 

 

Reset Alarm.

fault if an ICVC has been uploaded with soft-

 

 

 

 

ware when it was not attached to the CCM.

 

 

 

 

Enter VFD_CONF screen and then exit

 

 

 

 

VFD_CONF screen by pressing EXIT then

 

 

 

 

CANCEL. Re-enter the VFD_CONF screen,

 

 

 

 

press EXIT then SAVE. Parameters stored in

 

 

 

 

the Gateway will be uploaded into the ICVC.

 

 

 

 

Confirm valid settings in VFD_CONF screen.

252

PROTECTIVE LIMIT

VFD CONFIG CONFLICT

252VFD Config Conflict

The VFD_CONF table in the Gateway does not

 

 

 

(VFD Downloaded): Verify to

match that which is in the ICVC.

 

 

 

Reset Alarm.

 

253

PROTECTIVE LIMIT

GUIDE VANE

253Guide Vane Fault

Enter CONTROL TEST and execute Guide

 

 

CALIBRATION

[VALUE]. Check Calibration.

Vane Calibration.

 

 

 

 

Check CCM guide vane feedback terminals J4-9

 

 

 

 

and J4-10.

 

 

 

 

Check guide vane feedback potentiometer.

 

 

 

 

Alarm before start indicates guide vane opening

 

 

 

 

is not less than 4%. Alarm running indicates

 

 

 

 

guide vane position is < -1% or > 103%, or feed-

 

 

 

 

back voltage is < .045 or > 3.15 VDC.

254

PROTECTIVE LIMIT

VFD CHECKSUM ERROR

254Checksum Error:

Actual VFD checksum does not match calcu-

 

 

 

Press Reset to Restore

lated value.

 

 

 

Configuration.

 

255

PROTECTIVE LIMIT

VFD DEW PREVENTION

255Dew Prevention - Cool-

VFD COLDPLATE TEMP is too close to dew

 

 

 

ant Too Cold. Check Solenoid

point based on VFD ENCLOSURE TEMP and

 

 

 

& Cond T.

RELATIVE HUMIDITY in POWER screen.

 

 

 

 

Check for moisture in VFD enclosure.

 

 

 

 

Check Humidity Sensor in CONTROLS TEST.

 

 

 

 

Check for contamination on CCM J3-7 and J3-9

 

 

 

 

Humidity Sensor.

 

 

 

 

Check that VFD refrigerant cooling modulating

 

 

 

 

valve is closing.

256

PROTECTIVE LIMIT

INDUCTOR OVERTEMP

256Inductor Overtemp Trip -

Check for cooling fan air flow obstructions.

 

 

 

Check Temp Switch and Cool-

 

 

 

 

ing Fans.

 

257

PROTECTIVE LIMIT

VFD START INHIBIT

257VFD Start Inhibit: Check

The VFD Start Inhibit is derived from the Alarm

 

 

 

VFD Diagnostic Parameters

bit being set in the VFD. The conditions causing

 

 

 

212/214.

the alarm must be corrected in the VFD to

 

 

 

 

enable subsequent starts and operation. See

 

 

 

 

VFD parameters 212/214.

258

UNUSED STATE

UNUSED

258Unused.

 

*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

18

Page 18
Image 18
Carrier 19XRV specifications Unused State

19XRV specifications

The Carrier 19XRV is a cutting-edge rooftop chiller designed to provide reliable and efficient cooling solutions for a wide range of applications, including commercial buildings and industrial facilities. This advanced system integrates the latest technologies and innovative features to ensure optimal performance, energy efficiency, and ease of use.

One of the most prominent features of the 19XRV is its advanced inverter-driven compressor technology. This allows the chiller to adjust its capacity seamlessly based on the building's cooling demand. By varying the speed of the compressor, the 19XRV maximizes energy efficiency and minimizes operational costs, especially during partial load conditions. This capability not only enhances comfort but also contributes to reduced energy consumption, making it a sustainable choice for environmentally conscious users.

In addition to the inverter technology, the 19XRV incorporates a microchannel coil design. This design optimizes heat exchange efficiency and reduces the refrigerant charge, which is an essential factor in lowering greenhouse gas emissions. The microchannel coils also allow for more compact dimensions, making installation easier and maximizing rooftop space usage.

Another significant aspect of the Carrier 19XRV is its robust controls system. Equipped with Carrier’s advanced ComfortLink™ controls, this chiller offers precise monitoring and control over its operation. Users can easily integrate the chiller into building management systems for real-time data access and efficiency analytics. This connectivity ensures that operators can make informed decisions to optimize performance continuously.

The 19XRV also includes features aimed at enhancing reliability and durability. Its structural design incorporates corrosion-resistant materials, allowing the unit to withstand harsh environmental conditions. This reliability translates to lower maintenance requirements and extended equipment lifespan, providing excellent value over time.

Moreover, the chiller is designed for quiet operation, making it suitable for applications where low noise levels are essential. Sound-dampening measures ensure that the 19XRV can be utilized in urban environments or near sensitive areas without causing disturbances.

In conclusion, the Carrier 19XRV is a state-of-the-art rooftop chiller that combines efficiency, technology, and durability. Its inverter-driven compressor, microchannel coil design, advanced controls, and robust construction make it an ideal choice for those looking to maintain comfort while minimizing energy usage and environmental impact. Whether for commercial or industrial applications, the 19XRV stands out as a reliable and innovative cooling solution for the modern age.