Carrier 23XRV manual Control sequence, Controls cont

Models: 23XRV

1 32
Download 32 pages 17.21 Kb
Page 14
Image 14
Control sequence

Controls (cont)

CONTROL SEQUENCE

Control sequence

To start — Local start-up (manual start-up) is initiated by

MACHINE SAFETIES, EVAPORATOR PUMP

CONDENSER WATER PUMP

WATER FLOWS

CHILLED WATER TEMP,TOWER FAN CONTROL

OILPUMP

OILPRESSURE

VERIFIED

VDF FAULT TEST COMPRESSOR, PHASE REVERSAL, COMPRESSOR AND SERVICE ONTIME

RAMP VDF TO

TARGET SPEED

15-MINUTE START-TO-START TIMER

1-MINUTE STOP-TO-START TIMER (SOFTWARE VERSION 13)

0

 

 

 

 

 

 

 

0

 

 

 

 

COMPRESSOR

 

 

 

 

 

 

 

RUNNING

 

 

 

A B

C

D

E

F

G

H I

J

L O/A

 

TIME

 

 

 

 

 

 

K

 

 

 

 

 

 

 

 

pressing the LOCAL or CCN menu softkey, which is indi- cated on the default international chiller visual control (ICVC) screen. Time schedule 01 or 03, respectively, must be in the Occupied mode and the internal 15-minute start- to-start and the 1-minute stop-to-start inhibit timers must have expired. All pre-start safeties are checked to verify that all prestart alerts and safeties are within limits (if one is not, an indication of the fault displays and the start will be delayed or is aborted). The signal is sent to start the cooler liquid pump. Five seconds later, the condenser liquid pump is energized. If satisfied, it checks the chilled liquid temper- ature against the control point. If the temperature is less than or equal to the chilled liquid control point, the con- denser liquid pump is deenergized and the chiller goes into a recycle mode.

If the chilled liquid temperature is high enough, the start- up sequence continues. The oil pump is started and waits a minimum of 45 sec to verify oil flow. Once oil flow is veri- fied, the VFD is energized. The control will monitor for a phase reversal condition. At this time, the following occurs:

The “start-to-stop” timer is activated.

The “compressor on-time” and “service on-time” timers are activated.

The “starts in 12-hour counter” advances by one.

The “total compressor starts counter” advances by one.

Once started — If the VFD average current >5% within 15 seconds after VFD start, the machine enters run mode and speed will be ramped up to meet VFD target speed. Once the target speed is met the controls, enter the capac- ity control mode.

0Phase reversal monitored

ASTART INITIATED: Pre-start checks are made; evaporator pump started

BCondenser liquid pump started (5 seconds after A); tower fan control enabled

CLiquid flows verified (30 sec to 5 minutes maximum after B)

DChilled liquid temperature checked against control point; oil pump on.

EOil pressure verified (oil pressure verified 45-300 sec after D).

FVFD starts; phase reversal conditions monitored; compressor ontime and service ontime start; 15-minute inhibit timer starts (VFD fault tests for 15 sec after F)

GVerify average current >5% within 15 sec after VFD start, ramp to VFD target speed.

HCompressor reaches target speed, chiller set to running status

IShutdown initiated: Target VFD speed to 0% (or J occurs)

JRamp down until percent line current < soft stop amps threshold (0-60 sec after I)

KOil pump relay off (1-20 sec after J)

LEvaporator pump deenergized (60 sec after K); condenser pump and tower fan control may continue to operate if condenser pressure

is high; evaporator pump may continue if in RECYCLE mode

O/A — Restart permitted (both inhibit timers expired) (minimum of 15 min- utes after F; minimum of 3 minutes after L)

Shutdown sequence — The chiller shutdown is initiated if any of the following occur:

The Stop button is pressed for at least one second (the alarm light blinks once to confirm the stop command).

A recycle shutdown is initiated.

The time schedule has gone into unoccupied mode.

The chiller protective limit has been reached and the chiller is in alarm.

The start/stop status is overridden to stop from the ICVC, CCN system, or building management system.

Once the controls shutdown sequence is initiated, the compressor is stopped and the VFD target speed is set to 0. If optional soft stop unloading is activated when the Stop button is pressed or the remote contacts open, motor speed decreases to a configured amperage level, and the compressor is stopped. The display indicates “Shutdown in Progress” while the motor speed decreases. Compressor ontime and service ontime timers stop once the current in all phases is <5%, indicating a VFD Stop Complete. The oil pump and cooler liquid pump are then deenergized. The condenser liquid pump shuts down when the refrigerant temperature or entering condenser liquid temperature is be- low pre-established limits. The 3-minute start-to-stop timer starts.

Restart — Restart is permitted after both inhibit timers have expired. If shutdown was due to a safety shutdown, the reset button must be depressed before restarting the chiller.