Carrier 23XRV manual Insulation, → Minimum fluid loop volume, Condensation Vs Relative Humidity

Models: 23XRV

1 32
Download 32 pages 17.21 Kb
Page 23
Image 23
Insulation

Insulation

23XRV MINIMUM FIELD-INSTALLED INSULATION

REQUIREMENTS

COMPONENT

SIZE

INSULATION

ft2

m2

 

 

 

30-32

96

8.9

 

35-37

108

10.0

Cooler

40-42

109

10.1

45-47

122

11.3

 

 

50-52

115

10.7

 

55-57

130

12.1

Misc. Liquid Lines

All Sizes

21

2.0

Economizer

All Sizes

20

1.9

Compressor Motor

All Sizes

17

1.6

Factory insulation — Thermal insulation is factory- provided to the following areas:

Cooler (not including waterbox)

Suction line

Compressor and motor

Oil cooling line and oil return system line (oil and refrig- erant lines at or near evaporator pressure are insulated)

VFD cooling line (oil and refrigerant lines at or near evaporator pressure are insulated)

Motor cooling line

Vaporizer

Liquid line and discharge line

Float chamber

Optional economizer (including vent line and econo- mizer muffler)

Factory insulation is not available for the waterboxes.

Insulation applied at the factory is 1/2-in. (13 mm) thick closed cell and 1/2-in. (13 mm) open cell PVC-Nitrile foam. Some parts of the chiller are also treated with an outer layer of 3/16-in. (5 mm) thick vinyl. The 1/2-in. (13 mm) closed cell foam has a thermal conductivity K value of 0.28 (BTU in.)/(hr sqft °F) [0.0404 W/(m °C)] and

conforms with Underwriters Laboratories (UL) Standard 94, Classification 94 HF-1. Both the 1/2-in. foam and the 3/16-in. vinyl layer will pass flammability test method MVSS 302.

Field insulation — As indicated in the Condensation vs Relative Humidity table, the factory insulation provides excellent protection against condensation under most op- erating conditions. If temperatures in the equipment area exceed the maximum design conditions, extra insulation is recommended.

If the machine is to be field insulated, obtain the approx- imate areas from the 23XRV Minimum Field-Installed Insu- lation Requirements table.

Insulation of waterbox is made only in the field and this area is not included in 23XRV Minimum Field-Installed In- sulation Requirements table. When insulating the covers, allow for service access and removal of covers. To estimate water-box cover areas, refer to certified drawings.

High humidity jobsite locations may require field sup- plied and installed insulation on the float chamber, suction housing, and the lower half of the condenser.

CONDENSATION VS RELATIVE HUMIDITY*

AMOUNT OF

ROOM DRY-BULB TEMPERATURE

80 F (27 C)

90 F (32 C)

100 F (38 C)

CONDENSATION

% Relative Humidity

 

None

80

76

70

Slight

87

84

77

Extensive

94

91

84

*These approximate figures are based on 35 F (1.7 C) saturated suction temperature. A 2° F (1.1° C) change in saturated suction temperature changes the relative humidity values by 1% in the same direction.

Minimum fluid loop volume

Minimum fluid volume must be in excess of 1.5 gal per ton (20 L per kW) for comfort cooling applications and apply 3 to 5 gal per ton (40 to 66 L per kW) fluid loop volume for process applications.

910

23

Page 23
Image 23
Carrier manual Insulation, → Minimum fluid loop volume, 23XRV MINIMUM FIELD-INSTALLED INSULATION REQUIREMENTS