![Guide specifications (cont)](/images/new-backgrounds/63481/6348151x1.webp)
Guide specifications (cont)
equipment to dissipate the motor heat as per the following formula:
Btuh = (FLkW motor) (0.05) (3413) Btuh = (FLkW motor) (171)
and, alternately Tons = Btuh/12,000
The additional piping, valves,
8.Also, if an open motor is provided, a mechani- cal room thermostat shall be provided and set at 104 F (40 C). If this temperature is exceeded, the chillers shall shut down and an alarm signal shall be generated to the central Energy Management System (EMS) display module, prompting the service personnel to diagnose and repair the cause of the overtem- perature condition. The mechanical contractor shall be responsible for all changes to the design, including coordination with temperature control, electrical and other trades. In addition, the electrical power consumption of any auxil- iary ventilation and/or mechanical cooling required to maintain the mechanical room con- ditions stated above shall be considered in the determination of conformance to the scheduled chiller energy efficiency requirement.
D.
The compressor shall be
1.Design:
a.The VFD shall be refrigerant cooled, microprocessor based, pulse width modu- lated design. Water cooled designs are not acceptable.
b.Input and output power devices shall be Insulated Gate Bipolar Transistors (IGBTs).
c.Rectifier shall convert incoming fixed volt- age/frequency to fixed DC voltage.
d.Transistorized inverter and control regulator shall convert fixed DC voltage to a sinusoidal PWM waveform.
e.Low voltage control sections and main power sections shall be physically isolated.
f. Integrated controls shall coordinate motor speed to optimize chiller performance over a wide variety of operating conditions.
2.Enclosure:
a.
b.The VFD shall have a short circuit interrupt and withstand rating of at least 65,000 amps.
c.Provisions to padlock main disconnect han- dle in the “Off” positions shall be provided. Mechanical interlock to prevent opening cabinet door with disconnect in the “On” position or moving disconnect to the “On” position while the door is open shall be provided.
d.Provisions shall be made for top entry of incoming line power cables.
3.Heat Sink:
a.The heat sink shall be refrigerant cooled. Heat sink and mating flanges shall be suit- able for ASME design working pressure of 185 psig (1276 kPa).
b.Refrigerant cooling shall be metered to maintain heat sink temperature within acceptable limits for ambient temperature.
4.VFD Rating:
a.Drive shall be suitable for operation at name- plate voltage ±10%.
b.Drive shall be suitable for continuous opera- tion at 100% of nameplate amps and 150% of nameplate amps for 5 seconds.
c.Drive shall comply with applicable ANSI, NEMA, UL and NEC standards.
d.Drive shall be suitable for operation in ambient temperatures between 40 and 122 F (4 and 50 C), 95% humidity
5.User Interface:
A single display shall provide interface for pro- gramming and display of VFD and chiller parameters. Viewable parameters include:
a.Operating, configuration and fault messages
b.Frequency in hertz
c.Load and line side voltage and current (at the VFD)
d.kW
e.IGBT temperature
6.VFD Performance:
a.The VFD Voltage Total Harmonic Distortion (THD) and Harmonic Current Total Demand Distortion (TDD) shall not exceed
26