Guide specifications (cont)
liquid refrigerant to a reduced temperature, thereby increasing the refrigeration cycle efficiency.
F.Refrigerant Flow Control:
To improve part load efficiency, liquid refrigerant shall be metered from the condenser to the cooler using a
G.Controls, Safeties, and Diagnostics:
1.Controls:
a.The chiller shall be provided with a factory- installed and
b.All chiller and motor control monitoring shall be displayed at the chiller control panel.
c.The controls shall make use of
d.The chiller control system shall have the ability to interface and communicate directly to the building control system.
e.The default standard display screen shall simul- taneously indicate the following minimum information:
1)Date and time of day
2)
3)
4)Chiller operating hours
5)Entering chilled water temperature
6)Leaving chilled water temperature
7)Evaporator refrigerant temperature
8)Entering condenser water temperature
9)Leaving condenser water temperature
10)Condenser refrigerant temperature
11)Oil supply pressure
12)Oil sump temperature
13)Percent motor rated load amps (RLA)
f.In addition to the default screen, status screens shall be accessible to view the status of every point monitored by the control center including:
1)Evaporator pressure
2)Condenser pressure
3)Compressor speed
4)Bearing oil supply temperature
5)Compressor discharge temperature
6)Motor winding temperature
7)Number of compressor starts
8)Control point settings
9)Discrete output status of various devices
10)Variable frequency drive status
11)Optional spare input channels
12)Line current and voltage for each phase
13)Frequency, kW, kWhr, demand kW
g.Schedule Function:
The chiller controls shall be configurable for manual or automatic
1)A minimum of two
2)Minimum of 8 separate occupied/unoc- cupied periods per day
3)Daylight savings start/end
4)18
5)Means of configuring an occupancy timed override
6)Chiller
h.Service Function:
The controls shall provide a password protected service function which allows authorized individuals to view an alarm history file which shall contain the last 25 alarm/alert messages with time and date stamp. These messages shall be displayed in text form, not codes.
i.Network Window Function:
Each chiller control panel shall be capable of viewing multiple point values and statuses from other like controls connected on a common network, including controller main- tenance data. The operator shall be able to alter the remote controller’s set points or time schedule and to force point values or statuses for those points that are operator forcible. The control panel shall also have access to the alarm history file of all like con- trollers connected on the network.
j.Pump Control:
Upon request to start the compressor, the control system shall start the chilled and condenser water pumps and shall verify that flows have been established.
k.Ramp Loading:
A
28