Table 11 — 30RAP Electrical Data — Hydronic Package with Standard Low-Sound AeroAcoustic™ Fan

38RAP UNIT

VOLTAGE

 

 

PUMP SIZE 1 hp

 

 

 

PUMP SIZE 1.5 hp

 

 

 

PUMP SIZE 2 hp

 

 

PUMP OPTIONS "1" OR "8"

 

PUMP OPTIONS "2" OR "9"

 

PUMP OPTIONS "3" OR "B"

SIZE

V-Hz (3 Ph)

 

 

 

 

 

MCA

 

MOCP

ICF

REC FUSE

MCA

 

MOCP

ICF

REC FUSE

MCA

 

MOCP

ICF

REC FUSE

 

208/230-60

69.4

 

110

254.3

90

70.6

 

110

255.4

90

71.7

 

110

256.6

90

010

380-60

35.5

 

50

253.0

45

36.2

 

50

151.6

45

60.5

 

60

152.2

45

460-60

27.8

 

45

252.6

35

28.4

 

45

130.1

35

28.9

 

45

130.6

35

 

 

 

 

 

575-60

22.1

 

35

252.3

30

22.6

 

35

104.2

30

22.9

 

35

104.5

30

 

208/230-60

79.0

 

125

349.3

100

80.2

 

125

350.4

100

81.4

 

125

351.6

100

015

380-60

48.4

 

80

348.0

60

49.1

 

80

202.6

60

83.7

 

80

203.2

60

460-60

38.2

 

60

347.6

45

38.7

 

60

184.1

50

39.2

 

60

184.6

50

 

 

 

 

 

575-60

33.3

 

50

347.3

40

33.8

 

50

136.2

40

34.2

 

50

136.5

45

 

208/230-60

90.4

 

110

273.7

100

91.6

 

110

274.8

100

92.8

 

125

276.0

110

018

380-60

53.0

 

70

272.4

60

53.8

 

70

169.7

60

73.6

 

70

170.3

60

460-60

45.0

 

60

272.0

50

45.6

 

60

138.7

50

46.1

 

60

139.2

60

 

 

 

 

 

575-60

36.2

 

45

271.7

40

36.7

 

50

100.0

45

37.0

 

50

100.3

45

 

208/230-60

95.8

 

125

290.1

110

97.0

 

125

291.2

110

98.2

 

125

292.4

110

020

380-60

63.1

 

80

288.8

70

63.9

 

80

179.2

70

88.2

 

80

179.8

80

460-60

47.7

 

60

288.4

60

48.3

 

60

150.9

60

48.8

 

60

151.4

60

 

 

 

 

 

575-60

38.3

 

50

288.1

45

38.8

 

50

100.9

45

39.2

 

50

101.3

45

 

208/230-60

130.7

 

175

366.6

150

131.9

 

175

367.7

150

133.0

 

175

368.9

150

025

380-60

70.3

 

90

365.3

80

71.0

 

90

176.4

80

98.5

 

90

177.0

80

460-60

59.4

 

80

364.9

70

60.0

 

80

181.1

70

60.5

 

80

181.6

70

 

 

 

 

 

575-60

50.9

 

70

364.6

60

51.4

 

70

135.5

60

51.7

 

70

135.8

60

 

208/230-60

140.8

 

175

411.1

175

142.0

 

175

412.2

175

143.2

 

175

413.4

175

030

380-60

86.3

 

110

409.8

100

87.0

 

110

240.5

100

121.6

 

110

241.1

100

460-60

68.0

 

90

409.4

80

68.5

 

90

213.9

80

69.0

 

90

214.4

80

 

 

 

 

 

575-60

59.4

 

80

409.1

70

59.9

 

80

162.3

70

60.3

 

80

162.6

70

 

208/230-60

168.6

 

200

344.9

200

169.8

 

200

346.0

200

171.0

 

200

347.2

200

035

380-60

105.5

 

125

343.6

125

106.2

 

125

209.9

125

130.5

 

125

210.5

125

460-60

84.0

 

100

343.2

90

84.6

 

100

178.5

90

85.1

 

100

179.0

90

 

 

 

 

 

575-60

67.5

 

80

342.9

80

67.9

 

80

122.8

80

68.3

 

80

123.2

80

 

208/230-60

198.0

 

225

380.3

225

199.2

 

225

381.4

225

200.4

 

225

382.6

225

040

380-60

114.4

 

125

379.0

125

115.2

 

125

218.8

125

139.5

 

125

219.4

125

460-60

87.8

 

100

378.6

100

88.4

 

100

182.3

100

88.9

 

100

182.8

100

 

 

 

 

 

575-60

70.1

 

80

378.3

80

70.6

 

80

145.5

80

71.0

 

80

145.9

80

 

208/230-60

232.9

 

250

454.0

250

234.1

 

250

455.1

250

235.2

 

250

456.3

250

045

380-60

121.6

 

125

452.7

125

122.3

 

125

219.2

125

149.8

 

125

219.8

125

460-60

99.5

 

110

452.3

110

100.1

 

110

217.0

110

100.6

 

110

217.5

110

 

 

 

 

 

575-60

82.7

 

100

452.0

90

83.2

 

100

165.3

90

83.5

 

100

165.6

90

 

208/230-60

239.3

 

250

457.2

250

240.5

 

250

458.3

250

241.6

 

250

459.5

250

050

380-60

128.0

 

150

455.9

150

128.7

 

150

222.4

150

156.2

 

150

223.0

150

460-60

108.5

 

125

455.5

125

109.1

 

125

221.5

125

109.6

 

125

222.0

125

 

 

 

 

 

575-60

93.1

 

110

455.2

100

93.6

 

110

170.5

100

93.9

 

110

170.8

100

 

208/230-60

255.4

 

300

506.2

300

256.6

 

300

507.3

300

257.8

 

300

508.5

300

055

380-60

147.9

 

175

504.9

175

148.6

 

175

293.6

175

183.2

 

175

294.2

175

460-60

120.0

 

125

504.5

125

120.5

 

125

258.1

125

121.0

 

125

258.6

125

 

 

 

 

 

575-60

104.0

 

125

504.2

110

104.5

 

125

201.1

125

104.9

 

125

201.4

125

 

208/230-60

264.4

 

300

510.7

300

265.6

 

300

511.8

300

266.8

 

300

513.0

300

060

380-60

162.1

 

175

509.4

175

162.8

 

175

300.7

175

197.4

 

175

301.3

175

460-60

127.6

 

150

509.0

150

128.1

 

150

261.9

150

128.6

 

150

262.4

150

 

 

 

 

 

575-60

111.6

 

125

508.7

125

112.1

 

125

204.9

125

112.5

 

125

205.2

125

LEGEND

ICF — Instantaneous Current Flow

MCA — Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NOTES:

1.Units are suitable for use on electrical systems where voltage supplied to the unit ter- minals is not below or above the listed minimum and maximum limits. Maximum allow- able phase imbalance is: voltage, 2%; amps 10%.