Table 12 — 30RAP Electrical Data — Hydronic Package with Optional Value Sound Fans (cont)
38RAP UNIT | VOLTAGE |
|
| PUMP SIZE 3 hp |
|
| PUMP SIZE 5 hp |
|
|
| PUMP SIZE 7.5 hp |
| |||
| PUMP OPTIONS "4" OR "C" | PUMP OPTIONS "5" OR "6" OR "D" OR "F" |
| PUMP OPTIONS "7" OR "G" | |||||||||||
SIZE |
|
| |||||||||||||
|
| MCA |
| MOCP | ICF | REC FUSE | MCA | MOCP | ICF | REC FUSE | MCA |
| MOCP | ICF | REC FUSE |
| 75.3 |
| 110 | 260.2 | 90 | 80.1 | 125 | 265.0 | 100 | 86.7 |
| 125 | 271.6 | 100 | |
010 | 61.9 |
| 60 | 153.6 | 45 | 64.7 | 60 | 156.4 | 50 | 68.6 |
| 60 | 160.2 | 60 | |
30.5 |
| 45 | 132.2 | 40 | 32.8 | 50 | 134.5 | 40 | 35.9 |
| 50 | 137.7 | 45 | ||
|
|
| |||||||||||||
| 24.1 |
| 35 | 105.7 | 30 | 26.0 | 40 | 107.6 | 30 | 28.5 |
| 40 | 110.1 | 35 | |
| 85.0 |
| 125 | 355.2 | 100 | 89.8 | 125 | 360.0 | 110 | 96.4 |
| 150 | 366.6 | 125 | |
015 | 85.1 |
| 80 | 204.6 | 60 | 87.9 | 80 | 207.4 | 70 | 91.7 |
| 90 | 211.2 | 70 | |
40.8 |
| 60 | 186.2 | 50 | 43.1 | 70 | 188.5 | 50 | 46.3 |
| 70 | 191.7 | 60 | ||
|
|
| |||||||||||||
| 35.3 |
| 50 | 137.7 | 45 | 37.2 | 60 | 139.6 | 45 | 39.7 |
| 60 | 142.1 | 50 | |
| 97.0 |
| 125 | 280.2 | 110 | 101.8 | 125 | 285.0 | 125 | 108.4 |
| 125 | 291.6 | 125 | |
018 | 75.0 |
| 70 | 171.7 | 70 | 77.8 | 70 | 174.5 | 70 | 81.6 |
| 80 | 178.4 | 70 | |
48.1 |
| 60 | 141.2 | 60 | 50.4 | 60 | 143.5 | 60 | 53.5 |
| 70 | 146.7 | 60 | ||
|
|
| |||||||||||||
| 38.4 |
| 50 | 101.7 | 45 | 40.3 | 50 | 103.6 | 45 | 42.7 |
| 50 | 106.0 | 50 | |
| 102.4 |
| 125 | 296.6 | 125 | 107.2 | 125 | 301.4 | 125 | 113.8 |
| 125 | 308.0 | 125 | |
020 | 89.6 |
| 80 | 181.2 | 80 | 92.4 | 90 | 184.0 | 80 | 96.2 |
| 90 | 187.9 | 80 | |
50.8 |
| 60 | 153.4 | 60 | 53.1 | 70 | 155.7 | 60 | 56.2 |
| 70 | 158.9 | 70 | ||
|
|
| |||||||||||||
| 40.5 |
| 50 | 102.6 | 45 | 42.4 | 50 | 104.5 | 50 | 44.9 |
| 50 | 107.0 | 50 | |
| 137.2 |
| 175 | 373.1 | 175 | 142.0 | 175 | 377.9 | 175 | 148.6 |
| 175 | 384.5 | 175 | |
025 | 99.9 |
| 90 | 178.4 | 80 | 102.7 | 100 | 181.2 | 90 | 106.6 |
| 100 | 185.0 | 90 | |
62.5 |
| 80 | 183.6 | 70 | 64.8 | 80 | 185.9 | 80 | 67.9 |
| 90 | 189.1 | 80 | ||
|
|
| |||||||||||||
| 53.1 |
| 70 | 137.2 | 60 | 55.0 | 70 | 139.1 | 60 | 57.5 |
| 70 | 141.6 | 70 | |
| 147.4 |
| 200 | 417.6 | 175 | 152.2 | 200 | 422.4 | 175 | 158.8 |
| 200 | 429.0 | 175 | |
030 | 123.0 |
| 110 | 242.5 | 100 | 125.8 | 125 | 245.3 | 110 | 129.6 |
| 125 | 249.1 | 110 | |
71.0 |
| 90 | 216.4 | 80 | 73.3 | 100 | 218.7 | 90 | 76.5 |
| 100 | 221.9 | 90 | ||
|
|
| |||||||||||||
| 61.6 |
| 80 | 164.0 | 70 | 63.5 | 80 | 165.9 | 70 | 66.0 |
| 80 | 168.4 | 80 | |
| 175.8 |
| 200 | 350.2 | 200 | 180.6 | 200 | 355.0 | 200 | 187.2 |
| 200 | 361.6 | 200 | |
035 | 131.9 |
| 125 | 211.9 | 125 | 134.7 | 125 | 214.7 | 125 | 138.6 |
| 125 | 218.5 | 125 | |
87.5 |
| 100 | 180.2 | 100 | 89.8 | 100 | 182.5 | 100 | 92.9 |
| 110 | 185.7 | 100 | ||
|
|
| |||||||||||||
| 69.8 |
| 80 | 124.1 | 80 | 71.7 | 80 | 126.0 | 80 | 74.2 |
| 80 | 128.5 | 80 | |
| 205.2 |
| 250 | 385.6 | 225 | 210.0 | 250 | 390.4 | 225 | 216.6 |
| 250 | 397.0 | 250 | |
040 | 140.9 |
| 125 | 220.8 | 125 | 143.7 | 125 | 223.6 | 125 | 147.5 |
| 125 | 227.5 | 125 | |
91.3 |
| 100 | 184.0 | 100 | 93.6 | 110 | 186.3 | 100 | 96.7 |
| 110 | 189.5 | 110 | ||
|
|
| |||||||||||||
| 72.5 |
| 80 | 146.8 | 80 | 74.4 | 80 | 148.7 | 80 | 76.9 |
| 90 | 151.2 | 90 | |
| 240.0 |
| 250 | 459.3 | 250 | 244.8 | 250 | 464.1 | 250 | 251.4 |
| 300 | 470.7 | 300 | |
045 | 151.2 |
| 150 | 221.2 | 150 | 154.0 | 150 | 224.0 | 150 | 157.9 |
| 150 | 227.8 | 150 | |
103.0 |
| 125 | 218.7 | 110 | 105.3 | 125 | 221.0 | 125 | 108.4 |
| 125 | 224.2 | 125 | ||
|
|
| |||||||||||||
| 85.1 |
| 100 | 166.6 | 100 | 87.0 | 100 | 168.5 | 100 | 89.5 |
| 100 | 171.0 | 100 | |
| 246.4 |
| 250 | 462.5 | 250 | 251.2 | 300 | 467.3 | 300 | 257.8 |
| 300 | 473.9 | 300 | |
050 | 157.6 |
| 150 | 224.4 | 150 | 160.4 | 150 | 227.2 | 150 | 164.3 |
| 150 | 231.0 | 150 | |
112.0 |
| 125 | 223.2 | 125 | 114.3 | 125 | 225.5 | 125 | 117.4 |
| 125 | 228.7 | 125 | ||
|
|
| |||||||||||||
| 95.5 |
| 110 | 171.8 | 110 | 97.4 | 110 | 173.7 | 110 | 99.9 |
| 110 | 176.2 | 110 | |
| 263.2 |
| 300 | 511.5 | 300 | 268.0 | 300 | 516.3 | 300 | 274.6 |
| 300 | 522.9 | 300 | |
055 | 184.6 |
| 175 | 295.6 | 175 | 187.4 | 175 | 298.4 | 175 | 191.2 |
| 175 | 302.2 | 175 | |
123.8 |
| 150 | 259.8 | 150 | 126.1 | 150 | 262.1 | 150 | 129.3 |
| 150 | 265.3 | 150 | ||
|
|
| |||||||||||||
| 106.6 |
| 125 | 202.4 | 125 | 108.5 | 125 | 204.3 | 125 | 111.0 |
| 125 | 206.8 | 125 | |
| 272.2 |
| 300 | 516.0 | 300 | 277.0 | 300 | 520.8 | 300 | 283.6 |
| 300 | 527.4 | 300 | |
060 | 198.8 |
| 175 | 302.7 | 175 | 201.6 | 200 | 305.5 | 200 | 205.4 |
| 200 | 309.3 | 200 | |
131.4 |
| 150 | 263.6 | 150 | 133.7 | 150 | 265.9 | 150 | 136.9 |
| 150 | 269.1 | 150 | ||
|
|
| |||||||||||||
| 114.2 |
| 125 | 206.2 | 125 | 116.1 | 125 | 208.1 | 125 | 118.6 |
| 125 | 210.6 | 125 |
LEGEND
ICF — Instantaneous Current Flow
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NOTES:
1.Units are suitable for use on electrical systems where voltage supplied to the unit ter- minals is not below or above the listed minimum and maximum limits. Maximum allow- able phase imbalance is: voltage, 2%; amps 10%.
2.All units/modules have single point primary power connection. (Each unit/module requires its own power supply.) Main power must be supplied from a
3.Cooler heater is wired into the control circuit so it is always operable as long as the power supply disconnect is on, even if any safety device is open.
25