Table 12 — 30RAP Electrical Data — Hydronic Package with Optional Value Sound Fans (cont)

38RAP UNIT

VOLTAGE

 

 

PUMP SIZE 3 hp

 

 

PUMP SIZE 5 hp

 

 

 

PUMP SIZE 7.5 hp

 

 

PUMP OPTIONS "4" OR "C"

PUMP OPTIONS "5" OR "6" OR "D" OR "F"

 

PUMP OPTIONS "7" OR "G"

SIZE

V-Hz (3 Ph)

 

 

 

 

MCA

 

MOCP

ICF

REC FUSE

MCA

MOCP

ICF

REC FUSE

MCA

 

MOCP

ICF

REC FUSE

 

208/230-60

75.3

 

110

260.2

90

80.1

125

265.0

100

86.7

 

125

271.6

100

010

380-60

61.9

 

60

153.6

45

64.7

60

156.4

50

68.6

 

60

160.2

60

460-60

30.5

 

45

132.2

40

32.8

50

134.5

40

35.9

 

50

137.7

45

 

 

 

 

575-60

24.1

 

35

105.7

30

26.0

40

107.6

30

28.5

 

40

110.1

35

 

208/230-60

85.0

 

125

355.2

100

89.8

125

360.0

110

96.4

 

150

366.6

125

015

380-60

85.1

 

80

204.6

60

87.9

80

207.4

70

91.7

 

90

211.2

70

460-60

40.8

 

60

186.2

50

43.1

70

188.5

50

46.3

 

70

191.7

60

 

 

 

 

575-60

35.3

 

50

137.7

45

37.2

60

139.6

45

39.7

 

60

142.1

50

 

208/230-60

97.0

 

125

280.2

110

101.8

125

285.0

125

108.4

 

125

291.6

125

018

380-60

75.0

 

70

171.7

70

77.8

70

174.5

70

81.6

 

80

178.4

70

460-60

48.1

 

60

141.2

60

50.4

60

143.5

60

53.5

 

70

146.7

60

 

 

 

 

575-60

38.4

 

50

101.7

45

40.3

50

103.6

45

42.7

 

50

106.0

50

 

208/230-60

102.4

 

125

296.6

125

107.2

125

301.4

125

113.8

 

125

308.0

125

020

380-60

89.6

 

80

181.2

80

92.4

90

184.0

80

96.2

 

90

187.9

80

460-60

50.8

 

60

153.4

60

53.1

70

155.7

60

56.2

 

70

158.9

70

 

 

 

 

575-60

40.5

 

50

102.6

45

42.4

50

104.5

50

44.9

 

50

107.0

50

 

208/230-60

137.2

 

175

373.1

175

142.0

175

377.9

175

148.6

 

175

384.5

175

025

380-60

99.9

 

90

178.4

80

102.7

100

181.2

90

106.6

 

100

185.0

90

460-60

62.5

 

80

183.6

70

64.8

80

185.9

80

67.9

 

90

189.1

80

 

 

 

 

575-60

53.1

 

70

137.2

60

55.0

70

139.1

60

57.5

 

70

141.6

70

 

208/230-60

147.4

 

200

417.6

175

152.2

200

422.4

175

158.8

 

200

429.0

175

030

380-60

123.0

 

110

242.5

100

125.8

125

245.3

110

129.6

 

125

249.1

110

460-60

71.0

 

90

216.4

80

73.3

100

218.7

90

76.5

 

100

221.9

90

 

 

 

 

575-60

61.6

 

80

164.0

70

63.5

80

165.9

70

66.0

 

80

168.4

80

 

208/230-60

175.8

 

200

350.2

200

180.6

200

355.0

200

187.2

 

200

361.6

200

035

380-60

131.9

 

125

211.9

125

134.7

125

214.7

125

138.6

 

125

218.5

125

460-60

87.5

 

100

180.2

100

89.8

100

182.5

100

92.9

 

110

185.7

100

 

 

 

 

575-60

69.8

 

80

124.1

80

71.7

80

126.0

80

74.2

 

80

128.5

80

 

208/230-60

205.2

 

250

385.6

225

210.0

250

390.4

225

216.6

 

250

397.0

250

040

380-60

140.9

 

125

220.8

125

143.7

125

223.6

125

147.5

 

125

227.5

125

460-60

91.3

 

100

184.0

100

93.6

110

186.3

100

96.7

 

110

189.5

110

 

 

 

 

575-60

72.5

 

80

146.8

80

74.4

80

148.7

80

76.9

 

90

151.2

90

 

208/230-60

240.0

 

250

459.3

250

244.8

250

464.1

250

251.4

 

300

470.7

300

045

380-60

151.2

 

150

221.2

150

154.0

150

224.0

150

157.9

 

150

227.8

150

460-60

103.0

 

125

218.7

110

105.3

125

221.0

125

108.4

 

125

224.2

125

 

 

 

 

575-60

85.1

 

100

166.6

100

87.0

100

168.5

100

89.5

 

100

171.0

100

 

208/230-60

246.4

 

250

462.5

250

251.2

300

467.3

300

257.8

 

300

473.9

300

050

380-60

157.6

 

150

224.4

150

160.4

150

227.2

150

164.3

 

150

231.0

150

460-60

112.0

 

125

223.2

125

114.3

125

225.5

125

117.4

 

125

228.7

125

 

 

 

 

575-60

95.5

 

110

171.8

110

97.4

110

173.7

110

99.9

 

110

176.2

110

 

208/230-60

263.2

 

300

511.5

300

268.0

300

516.3

300

274.6

 

300

522.9

300

055

380-60

184.6

 

175

295.6

175

187.4

175

298.4

175

191.2

 

175

302.2

175

460-60

123.8

 

150

259.8

150

126.1

150

262.1

150

129.3

 

150

265.3

150

 

 

 

 

575-60

106.6

 

125

202.4

125

108.5

125

204.3

125

111.0

 

125

206.8

125

 

208/230-60

272.2

 

300

516.0

300

277.0

300

520.8

300

283.6

 

300

527.4

300

060

380-60

198.8

 

175

302.7

175

201.6

200

305.5

200

205.4

 

200

309.3

200

460-60

131.4

 

150

263.6

150

133.7

150

265.9

150

136.9

 

150

269.1

150

 

 

 

 

575-60

114.2

 

125

206.2

125

116.1

125

208.1

125

118.6

 

125

210.6

125

LEGEND

ICF — Instantaneous Current Flow

MCA — Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NOTES:

1.Units are suitable for use on electrical systems where voltage supplied to the unit ter- minals is not below or above the listed minimum and maximum limits. Maximum allow- able phase imbalance is: voltage, 2%; amps 10%.