1 40
Download 40 pages 58.51 Kb
Page 23
Image 23
AeroAcoustic™ Fan (cont)

Table 11 — 30RAP Electrical Data — Hydronic Package with Standard Low-Sound

AeroAcoustic™ Fan (cont)

38RAP UNIT

VOLTAGE

 

 

PUMP SIZE 3 hp

 

 

PUMP SIZE 5 hp

 

 

 

PUMP SIZE 7.5 hp

 

 

PUMP OPTIONS "4" OR "C"

PUMP OPTIONS "5" OR "6" OR "D" OR "F"

 

PUMP OPTIONS "7" OR "G"

SIZE

V-Hz (3 Ph)

 

 

 

 

MCA

 

MOCP

ICF

REC FUSE

MCA

MOCP

ICF

REC FUSE

MCA

 

MOCP

ICF

REC FUSE

 

208/230-60

74.7

 

110

259.6

90

79.5

125

264.4

100

86.1

 

125

271.0

100

010

380-60

61.9

 

60

153.6

45

64.7

60

156.4

50

68.6

 

60

160.2

60

460-60

30.1

 

45

131.8

35

32.4

50

134.1

40

35.5

 

50

137.3

45

 

 

 

 

575-60

23.9

 

35

105.5

30

25.8

40

107.4

30

28.3

 

40

109.9

35

 

208/230-60

84.4

 

125

354.6

100

89.2

125

359.4

110

95.8

 

150

366.0

110

015

380-60

85.1

 

80

204.6

60

87.9

80

207.4

70

91.7

 

90

211.2

70

460-60

40.4

 

60

185.8

50

42.7

60

188.1

50

45.9

 

70

191.3

60

 

 

 

 

575-60

35.1

 

50

137.5

45

37.0

60

139.4

45

39.5

 

60

141.9

50

 

208/230-60

95.8

 

125

279.0

110

100.6

125

283.8

110

107.2

 

125

290.4

125

018

380-60

75.0

 

70

171.7

70

77.8

70

174.5

70

81.6

 

80

178.4

70

460-60

47.3

 

60

140.4

60

49.6

60

142.7

60

52.7

 

60

145.9

60

 

 

 

 

575-60

38.0

 

50

101.3

45

39.9

50

103.2

45

42.3

 

50

105.6

50

 

208/230-60

101.2

 

125

295.4

125

106.0

125

300.2

125

112.6

 

125

306.8

125

020

380-60

89.6

 

80

181.2

80

92.4

90

184.0

80

96.2

 

90

187.9

80

460-60

50.0

 

60

152.6

60

52.3

70

154.9

60

55.4

 

70

158.1

60

 

 

 

 

575-60

40.1

 

50

102.2

45

42.0

50

104.1

50

44.5

 

50

106.6

50

 

208/230-60

136.0

 

175

371.9

150

140.8

175

376.7

175

147.4

 

175

383.3

175

025

380-60

99.9

 

90

178.4

80

102.7

100

181.2

90

106.6

 

100

185.0

90

460-60

61.7

 

80

182.8

70

64.0

80

185.1

70

67.1

 

90

188.3

80

 

 

 

 

575-60

52.7

 

70

136.8

60

54.6

70

138.7

60

57.1

 

70

141.2

70

 

208/230-60

146.2

 

200

416.4

175

151.0

200

421.2

175

157.6

 

200

427.8

175

030

380-60

123.0

 

110

242.5

100

125.8

125

245.3

110

129.6

 

125

249.1

110

460-60

70.2

 

90

215.6

80

72.5

90

217.9

80

75.7

 

100

221.1

90

 

 

 

 

575-60

61.2

 

80

163.6

70

63.1

80

165.5

70

65.6

 

80

168.0

80

 

208/230-60

174.0

 

200

350.2

200

178.8

200

355.0

200

185.4

 

200

361.6

200

035

380-60

131.9

 

125

211.9

125

134.7

125

214.7

125

138.6

 

125

218.5

125

460-60

86.3

 

100

180.2

100

88.6

100

182.5

100

91.7

 

100

185.7

100

 

 

 

 

575-60

69.2

 

80

124.1

80

71.1

80

126.0

80

73.6

 

80

128.5

80

 

208/230-60

203.4

 

250

385.6

225

208.2

250

390.4

225

214.8

 

250

397.0

250

040

380-60

140.9

 

125

220.8

125

143.7

125

223.6

125

147.5

 

125

227.5

125

460-60

90.1

 

100

184.0

100

92.4

110

186.3

100

95.5

 

110

189.5

110

 

 

 

 

575-60

71.9

 

80

146.8

80

73.8

80

148.7

80

76.3

 

90

151.2

80

 

208/230-60

238.2

 

250

459.3

250

243.0

250

464.1

250

249.6

 

300

470.7

300

045

380-60

151.2

 

150

221.2

150

154.0

150

224.0

150

157.9

 

150

227.8

150

460-60

101.8

 

110

218.7

110

104.1

125

221.0

110

107.2

 

125

224.2

125

 

 

 

 

575-60

84.5

 

100

166.6

90

86.4

100

168.5

100

88.9

 

100

171.0

100

 

208/230-60

244.6

 

250

462.5

250

249.4

300

467.3

300

256.0

 

300

473.9

300

050

380-60

157.6

 

150

224.4

150

160.4

150

227.2

150

164.3

 

150

231.0

150

460-60

110.8

 

125

223.2

125

113.1

125

225.5

125

116.2

 

125

228.7

125

 

 

 

 

575-60

94.9

 

110

171.8

100

96.8

110

173.7

110

99.3

 

110

176.2

110

 

208/230-60

260.8

 

300

511.5

300

265.6

300

516.3

300

272.2

 

300

522.9

300

055

380-60

184.6

 

175

295.6

175

187.4

175

298.4

175

191.2

 

175

302.2

175

460-60

122.2

 

125

259.8

125

124.5

150

262.1

150

127.7

 

150

265.3

150

 

 

 

 

575-60

105.8

 

125

202.4

125

107.7

125

204.3

125

110.2

 

125

206.8

125

 

208/230-60

269.8

 

300

516.0

300

274.6

300

520.8

300

281.2

 

300

527.4

300

060

380-60

198.8

 

175

302.7

175

201.6

200

305.5

200

205.4

 

200

309.3

200

460-60

129.8

 

150

263.6

150

132.1

150

265.9

150

135.3

 

150

269.1

150

 

 

 

 

575-60

113.4

 

125

206.2

125

115.3

125

208.1

125

117.8

 

125

210.6

125

LEGEND

ICF — Instantaneous Current Flow

MCA — Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NOTES:

1.Units are suitable for use on electrical systems where voltage supplied to the unit ter- minals is not below or above the listed minimum and maximum limits. Maximum allow- able phase imbalance is: voltage, 2%; amps 10%.

2.All units/modules have single point primary power connection. (Each unit/module requires its own power supply.) Main power must be supplied from a field-supplied disconnect.

3.Cooler heater is wired into the control circuit so it is always operable as long as the power supply disconnect is on, even if any safety device is open.

23

Page 23
Image 23
Carrier 30RAP010-060 installation instructions AeroAcoustic Fan cont