FILLING THE SYSTEM — The initial fill of the chilled water system must accomplish three purposes:
1.The entire piping system must be filled with water.
2.The pressure at the top of the system must be high enough to vent air from the system (usually 4 psig is adequate for most vents).
3.The pressure at all points in the system must be high enough to prevent flashing in the piping or cavitation in the pump.
The pressure created by an operating pump affects system pressure at all points except one — the connection of the compression tank to the system. This is the only location in the system where pump operation will not give erroneous pressure indications during the fill. Therefore, the best location to install the fill connection is close to the expansion tank. An air vent should be installed close by to help eliminate air that enters during the fill procedure.
Ensure the following when filling the system:
1.Remove temporary bypass piping and cleaning/flushing equipment.
2.Check to make sure all drain plugs are installed.
3.Open the
Normally, a closed system needs to be filled only once. The actual filling process is generally a fairly simple procedure. All air should be purged or vented from the system. Thorough venting at the high points and circulation at room temperature for several hours is recommended.
NOTE: Local codes concerning backflow devices and other protection of the city water system should be consulted and followed to prevent contamination of the public water supply. This is especially important when antifreeze is used in the system.
Set Water Flow Rate — Once the system is cleaned, pressur- ized, and filled, the flow rate through the chiller needs to be established. On units with the hydronic package, this can best be done using the balancing valve.
In order to adjust the balancing valve, put a differential pressure gage across the pressure taps on the valve. Make sure that all system isolation and control valves are open. Use Tables
1.Measure the pressure drop across the balancing valve. If the pressure reading is in psig, multiply psig by 2.31 to convert to feet of water before using Tables 4A and 5A.
2.Go to the row in the chart corresponding to the setting on the valve, interpolating if necessary.
3.The gpm corresponding to the pressure drop measured is the flow through the balancing valve.
NOTE: Carrier recommends a differential pressure gage when measuring pressures across the pumps or balancing valves. This provides for greater accuracy and reduces error
that often occurs when subtracting pressures made by different gages.
On primary/secondary systems, it is advisable to set the 30RAP balancing valve to maintain design flow plus 10% through the chiller.
A rough estimate of water flow can also be obtained from the pressure gages across the 30RAP heat exchanger. Figures
Minimum Loop Volume — The minimum volume of fluid re- quired to be in circulation is a function of the number of com- pressors in the chiller as well as the type of application. The minimum fluid in circulation must equal or exceed the values in the following table. See Table 6.
To achieve this fluid volume, it is often necessary to install a tank in the loop. The tank should be baffled to ensure there is no stratification and that water (or brine) entering the tank is adequately mixed with liquid in the tank. See Fig. 18.
A properly baffled storage tank is available from the factory as an accessory. These tanks are designed to physically fit beneath the corresponding 30RAP unit, taking up the same footprint.
• | 83 gallons (314 liters) | |
• | 119 gallons (450 liters) | |
• | 241 gallons (912 liters) |
Storage tank weight (water weight included) is as follows:
• | 1673 lb (759 kg) | |
• | 2193 lb (995 kg) | |
• | 4361 lb (1978 kg) |
Maximum Loop Volume (Units with Hydronic Package) — Since the minimum size of the expansion tank is dependent upon loop volume, units with the integrated hydronic kit must not exceed the maximum loop volume limits below (see Table 7). The limits are dependent on the maximum and mini- mum temperatures of the water, the maximum and minimum pressures seen by the expansion tank, and the heat transfer flu- id. Expansion tank and maximum loop volume data is as follows.
Volume gal (L) | 5.0 (18.9) | 10.0 | (37.9) |
Acceptance Volume gal (L) | 2.9 (11.0) | 5.5 | (20.8) |
SYSTEM
SYSTEM
DILUTED
POT FEEDER AND TRANSFER PUMP
DILUTED
POT FEEDER AND TRANSFER PUMP
CLEANING
AGENT
| x |
TEMPORARY | 30RA UNIT |
PUMP |
|
x
SIDE STREAM FILTER
CLEANING
AGENT
| x |
TEMPORARY | 30RA UNIT |
PUMP |
|
x
TEMPORARY
BYPASS
TO DRAIN
Fig. 14 — Typical Set Up for Cleaning Process
TEMPORARY
BYPASS
TO DRAIN
Fig. 15 — Cleaning Using a Side Stream Filter
16