Carrier 37HS Ð Lay Out Terminals, Ð Recommended Maximum Cfm Per Terminal, Ð Terminal Location

Models: 37HS

1 84
Download 84 pages 16.18 Kb
Page 25
Image 25
Table 3 Ð Recommended Maximum Cfm

As a result, slightly higher maximum cfm per unit is al- lowed as compared to interior zones or the north perimeter, which have relatively constant loads.

The maximum cfm per unit also is affected by the desired sound level in the room and the type of use of the space.

For example, an executive office uses low sound levels but the furnishings generally absorb more sound so the al- lowable cfm/unit is only slightly lower than other types of rooms.

Table 3 Ð Recommended Maximum Cfm

Per Terminal

 

 

 

 

MODULINE UNITS

 

 

TYPE OF

37HS1

37HS2

 

37HS4

East

Interior

East

Interior

 

East

Interior

SPACE USE

 

West

West

 

West

 

 

and

and

 

and

 

 

and

and

 

and

 

 

North

North

 

North

 

 

South

South

 

South

 

 

 

 

 

 

General

 

110

95

220

190

 

400

350

Office

 

 

 

 

 

 

 

 

 

 

 

With

100

90

200

180

 

330

300

Private

Carpet

 

 

 

 

 

 

 

 

Office

With

90

80

180

160

 

300

270

 

Tile

 

 

 

 

 

 

 

 

 

Executive

85

75

170

150

 

280

250

Office

 

 

 

 

 

 

 

 

 

 

Step 2 Ð Lay Out Terminals

LOCATE UNITS IN T-BAR GRID Ð In making a layout, begin with a plan view of the ceiling. Normally, the ceiling grid and the lighting is done ®rst and the diffuser plan must ®t the layout.

The center of the room is the ideal location, but where that space has been reserved for lighting, the Moduline dif- fuser has enough ¯exibility to provide good distribution when not centered in the room.

For a two-way blow diffuser, anywhere from the 1¤4 point to the 1¤4 point (wall to wall) is usually suitable. Outside of the 1¤4 points, a one-way blow diffuser may be needed. Use two-way blow diffuser wherever possible and one-way blow only when really necessary. (See Fig. 14.)

Fig. 14 Ð Diffuser Locations for

Preferred 2-Way or One-Way Blow

Most jobs use a 2- x 4-ft grid T-Bar ceiling with 2- x 4-ft or 2- x 2 ft tiles.

The ®rst consideration in making a layout is to place the terminals as economically as possible in the grid, which means locating the terminals perpendicular to the main tees.

Main tees (the ones with hangers) are 4 ft on center (nor- mally) and the cross tees are spaced 2 ft apart between the mains to make up a 2- x 4-ft T-bar grid. Additional trim tees may be used to divide the ceiling into a 2- x 2-ft grid.

The Moduline units use mounting brackets and hang from (run perpendicular to) the main tees. While the units can be installed anywhere between mains, the most common loca- tion is on the center line of the cross tee (replaces the cross tee). The next most common location is half way between cross tees. See Fig. 15.

While less desirable, the units can be run parallel to the main tees. Unless absolutely necessary the units should not replace the main tee because this means the main tee must be cut. A location halfway between the mains is common and in this case additional hangers are required to the upper plenum of the unit or to the cross tee near the unit.

Special units are available for many other types of ceilings.

Fig. 15 Ð Terminal Location

25

Page 25
Image 25
Carrier 37HS Ð Lay Out Terminals, Ð Recommended Maximum Cfm Per Terminal, Ð Diffuser Locations for, Ð Terminal Location