VAV HEATING AND COOLING WITH ELECTRIC CHANGEOVER Ð This application uses a CV control pack- age along with a wall-mounted thermostat package (cooling/ heating) and an electric changeover package. The change- over valve permits control of the unit to be switched between the cooling and heating sides of a cooling/heating thermo- stat. It is ®eld-installed in-line between the volume control- ler and the thermostat.

VAV HEATING AND COOLING WITH ELECTRIC CHANGEOVER Ð This application uses a CV control pack- age along with a wall-mounted thermostat package (cooling/ heating) and an electric changeover package. The change- over valve permits control of the unit to be switched between the cooling and heating sides of a cooling/heating thermo- stat. It is ®eld-installed in-line between the volume control- ler and the thermostat.

Refer to Fig. 70-73. In cooling operation, the NO port of the valve opens the control circuit between the volume

controller and the cooling side of the thermostat. Because the NC port is closed, the heating side of the thermostat is locked out of the system. Upon changeover to heating, the solenoid valve is energized. The NO port closes and the NC port is opened, and the control circuit switches to the heat- ing side of the thermostat. Typically, the solenoid valve is wired to activate automatically when the heating system is turned on, although it may be operated by a simple on/off switch.

Fig. 70 Ð Heating/Cooling Unit Ð Cooling, Cold Air in Duct, Electric Changeover in Cooling,

Thermostat Open, Controller Shut Off, Unit Shut Off