Carrier 37HS specifications Ð Air Throw Data Ð, Wayand 2-WayBlow, 2-SlotDiffusers

Models: 37HS

1 84
Download 84 pages 16.18 Kb
Page 82
Image 82

Throw for Standard Diffusers Ð Tables 24 and 25 provide the suggested minimum and maximum coverages the Moduline® air terminals can handle in a typical instal- lation while maintaining the desired room conditions.

Table 24 Ð Air Throw Data Ð

1-Way and 2-Way Blow, 2-Slot Diffusers

37HS1 UNIT

 

OPTIMUM AIR THROW (ft)

 

 

 

 

 

 

AIRFLOW

1-Way Blow

2-Way Blow

(Cfm)

 

 

 

 

 

Min

Max

Min

 

Max

 

 

40

2.0

7.0

2.0

 

5.0

50

4.0

9.0

3.0

 

6.0

60

7.5

12.0

3.5

 

7.5

70

8.0

15.0

4.0

 

9.0

80

9.0

18.0

4.5

 

10.5

90

10.0

20.0

5.0

 

11.5

100

11.0

22.0

6.0

 

13.0

110

12.0

24.0

7.0

 

15.0

 

 

 

 

 

37HS2 UNIT

 

OPTIMUM AIR THROW (ft)

 

 

 

 

 

 

AIRFLOW

1-Way Blow

2-Way Blow

(Cfm)

 

 

 

 

 

Min

Max

Min

 

Max

 

 

 

 

 

 

 

 

80

2.0

7.0

2.0

 

5.0

100

4.0

9.0

3.0

 

6.0

120

7.5

12.0

3.5

 

7.5

140

8.0

15.0

4.0

 

9.0

160

9.0

18.0

4.5

 

10.5

180

10.0

20.0

5.0

 

11.5

200

11.0

22.0

6.0

 

13.0

220

12.0

24.0

7.0

 

15.0

 

 

 

 

 

37HS4 UNIT

 

OPTIMUM AIR THROW (ft)

 

 

 

 

 

 

AIRFLOW

1-Way Blow

2-Way Blow

(Cfm)

 

 

 

 

 

Min

Max

Min

 

Max

 

 

 

 

 

 

 

 

160

8.5

16.0

5.0

 

7.0

200

10.0

20.0

6.0

 

10.0

250

11.0

21.0

7.0

 

13.0

300

12.0

22.0

8.0

 

17.0

350

14.0

23.0

9.0

 

19.0

400

15.0

25.0

10.0

 

21.0

440

17.0

29.0

13.0

 

24.0

NOTES:

1.Minimum air throw refers to the distance from the diffuser where the air ve- locity is 150 fpm. In maximum air throw, this velocity has dropped to 50 fpm.

2.Data is based on an area with a 9-ft ceiling. For higher ceilings, values may be reduced by one foot for each foot of height increase. For speci®c instal- lations, minimum values can be reduced if properly quali®ed. Values are dependent on cfm only and are not affected by duct pressure.

The optimum air throw values given in the table are dis- tances from the unit centerline to the outside wall or nearest obstruction (wall, light ®xture or opposing air stream).

Table 25 Ð Air Throw Data Ð

2-Way and 1-Way Director, 3-Slot Diffusers

37HS1 UNIT

 

 

OPTIMUM AIR THROW (ft)

 

 

 

 

 

 

 

 

 

Heating

Cooling

 

AIRFLOW

 

 

 

 

 

 

 

1-Way Blow

2-Way Blow

(Cfm)

 

Min

 

 

Max

Min

 

Max

 

 

 

 

 

 

 

 

40

2.0

 

7.0

2.0

 

5.0

50

4.0

 

9.0

3.0

 

6.0

60

7.5

 

12.0

3.5

 

7.5

70

8.0

 

15.0

4.0

 

9.0

80

9.0

 

18.0

4.5

 

10.5

90

10.0

 

20.0

5.0

 

11.5

100

11.0

 

22.0

6.0

 

13.0

110

12.0

 

24.0

7.0

 

15.0

 

 

 

 

 

 

 

37HS2 UNIT

 

 

OPTIMUM AIR THROW (ft)

 

 

 

 

 

 

 

 

Heating

Cooling

 

AIRFLOW

 

 

 

 

 

 

 

1-Way Blow

2-Way Blow

(Cfm)

 

Min

 

 

Max

Min

 

Max

80

2.0

 

7.0

2.0

 

5.0

100

4.0

 

9.0

3.0

 

6.0

120

7.5

 

12.0

3.5

 

7.5

140

8.0

 

15.0

4.0

 

9.0

160

9.0

 

18.0

4.5

 

10.5

180

10.0

 

20.0

5.0

 

11.5

200

11.0

 

22.0

6.0

 

13.0

220

12.0

 

24.0

7.0

 

15.0

 

 

 

 

 

 

37HS4 UNIT

 

 

OPTIMUM AIR THROW (ft)

 

 

 

 

 

 

 

Heating

Cooling

 

AIRFLOW

 

 

 

 

 

 

 

(Cfm)

1-Way Blow

2-Way Blow

 

Min

 

 

Max

Min

 

Max

 

 

 

 

 

 

 

160

8.5

 

16.0

5.0

 

7.0

200

10.0

 

20.0

6.0

 

10.0

250

11.0

 

21.0

7.0

 

13.0

300

12.0

 

22.0

8.0

 

17.0

350

14.0

 

23.0

9.0

 

19.0

400

15.0

 

25.0

10.0

 

21.0

440

17.0

 

29.0

13.0

 

24.0

82

Page 82
Image 82
Carrier 37HS specifications Ð Air Throw Data Ð, Wayand 2-WayBlow, 2-SlotDiffusers, Wayand 1-WayDirector, 3-SlotDiffusers