PNEUMATIC SEQUENCED HEATING/COOLING (HOT WATER) Ð By using a 20 psi pneumatic source, one ther- mostat can control both heating and Moduline cooling in the conditioned space. The pneumatic circuit is interfaced with the
Figure 75 shows the piping diagram. Figure 76 shows the sequence diagram for a direct acting thermostat with a nor- mally open pilot valve. With the system shut down and the space temperature low, at
If the space temperature continues to rise, the NO pilot valve will modulate toward closed, raising the low side pres- sure, opening the bleed, reducing the bellows pressure, and opening the Moduline unit air valve. The air¯ow will rise until the volume controller setting is reached.
Note that the spring rates of the hot water valve and the pilot valve must be properly matched to accomplish the ac- tion described above.
A heating/cooling sequence can also be accomplished with a reverse acting circuit (Fig. 77 and 78). At
LEGEND FOR FIG. 75 - 78
DA | Ð Direct Acting | NC Ð Normally Closed |
HW | Ð Hot Water | NO Ð Normally Open |
M | Ð Main | RA Ð Reverse Acting |
Fig. 75 Ð Piping Diagram, Heating/Cooling
Sequence, DA Thermostat
Fig. 76 Ð Sequence Diagram Ð DA Thermostat
Fig. 77 Ð Piping Diagram, Heating/Cooling
Sequence, RA Thermostat
Fig. 78 Ð Sequence Diagram, RA Thermostat
69