Table 9 Ð Maximum Cfm Through the Inlet Collar

Table 9 Ð Maximum Cfm Through the Inlet Collar

of a Single Unit or of Units in Air Series

 

PLENUM

INLET

MAXIMUM TOTAL

 

COLLAR

MODEL

SIZE

AIRFLOW

DIAM

 

(in.)

(Cfm)

 

(in.)

 

 

 

 

5 x 7

4

110

37HS1

7 x 7

6

400

9 x 9

8

800

 

 

11 x 11

10

1100

 

7 x 7

6

400

37HS2

9 x 9

8

800

 

11 x 11

10

1100

 

9 x 9

8

800

37HS4

11 x 11

10

1100

 

13 x 13

12

1600

 

 

 

 

In general, units in an air series should not be of mixed sizes (cfm capacities). If units of different capacities are used, a controller must be applied for each size unit. For example, an application for 800 cfm using different capacity units, as shown in Fig. 21, is acceptable only with multiple controls. This arrangement, although not preferred, can be used if care is taken to use the necessary controllers. In this case, 3 con- trollers are required. However, the best installation for an 800 cfm (nominal cfm total) would be one in which all the units are the same size. (Fig. 22.) In this case, a single con- troller can be used in the space.