Carrier 37HS specifications Cfm, HK08ZZ030, Ð Multiple Unit Air¯ow Variation

Models: 37HS

1 84
Download 84 pages 16.18 Kb
Page 72
Image 72
% CFM  120

S O

OPEN

S HK08ZZ030 O

MINIMUM CFM

STAR WHEEL

% CFM Table 17 Ð Multiple Unit Air¯ow Variation 120

100

 

HK08ZZ030

40

80

 

%

CFM Manual background 120

100

Manual background40 Manual background 80 Manual background

MAXIMUM CFM LEVER

VOLUME CONTROLLER

Fig. 84 Ð Minimum and Maximum Air¯ow Adjustments, 37HS Controller

Variation in Maximum Air¯ow Ð As explained in the Terminal Selection and Layout section, Moduline units in air series can be controlled individually with a volume controller at each unit, or with a master/slave combination, where one controller is used with multiple units. All the units on one controller must be of the same model (capacity).

In master/slave combinations, some variation in maxi- mum air¯ow among the terminals in air series will occur. The variation in maximum air¯ow is a function of the unit plenum size, the model, and the number of units in an air series on one controller. Table 17 shows the expected varia- tion from the unit with the smallest air¯ow to the unit with the largest air¯ow.

For single units with controller, the cfm variation from the lever setting is ± 10%.

Table 17 Ð Multiple Unit Air¯ow Variation

 

 

APPROXIMATE AIRFLOW VARIATION (Cfm)

 

PLENUM

LOWEST UNIT TO HIGHEST UNIT IN AIR SERIES*

MODEL

 

Number of Units in Air Series On

SIZE (in.)

 

 

 

 

 

One Controller

 

 

 

2

 

3

4

5

 

7 x 7

10

 

15

20

Ð

37HS1

9 x 9

10

 

15

20

25

 

11 x 11

10

 

15

20

25

 

7 x 7

20

 

Ð

Ð

Ð

37HS2

9 x 9

20

 

30

40

Ð

 

11 x 11

20

 

30

40

Ð

 

9 x 9

40

 

Ð

Ð

Ð

37HS4

11 x 11

40

 

60

Ð

Ð

 

13 x 13

40

 

60

80

Ð

 

 

 

 

 

 

 

*Values shown are based on a typical short, straight duct run be- tween units. Variation shown may be affected if there are excessive duct pressure losses between units.

NOTE: The variation value shown in Table 17 for a given number of units of a certain model size (capacity) is the same for all size ple- nums used in an air series of recommended combinations for that model size. Thus, 3 units of model size 37HS2, plenum size 9 x 9, will have a maximum variation of 30 cfm; 3 units, plenum sizes 9 x 9 (2) and 7 x 7 (1) will also have a maximum variation of 30 cfm. A dash indicates that the quantity of a particular plenum size is not recom- mended in air series for that unit size.