Fig. 74 Ð Connection for Electric Interlock

Fig. 73 Ð Heating/Cooling Unit Ð Heating, Hot Air in Duct, Electric Changeover in Heating,

Thermostat Closed, Controller Bleeding, Unit Heating

VAV COOLING WITH ELECTRIC HEAT INTERLOCK Ð A conditioned space may contain a Moduline system for cool- ing and a separate heating system such as baseboard electric or hot water or an overhead fan coil. The electric interlock switch enables the cooling and heating systems to operate as the load dictates with overlap.

The electric interlock switch compares the bellows pres- sure with the low pressure, as a practical means of detecting the operating level of the unit. When the unit is delivering, the bellows pressure is signi®cantly lower than the low pres- sure and the electric interlock (differential pressure) switch is open, interrupting the power supply to the heating system. When the unit is shut off, the pressures are approximately equal and the switch closes, allowing the heating system to be energized. It is ®eld installed with the low pressure port piped to the auxiliary bellows pressure stub of the ®lter. (See Fig. 74.) The high pressure port is connected by a ``T'' into the line between the volume regulator and the thermostat.

Fig. 74 Ð Connection for Electric Interlock