VAV HEATING AND COOLING WITH SYSTEM- POWERED CHANGEOVER Ð This application uses a CV control package along with a wall-mounted thermostat pack- age (cooling/heating) and a system-powered changeover con- trol package. The cooling thermostat is direct acting (DA) while the heating thermostat is reverse acting (RA).

Fig. 61 Ð Location of CV Unit for Warm-Up Application

VAV HEATING AND COOLING WITH SYSTEM- POWERED CHANGEOVER Ð This application uses a CV control package along with a wall-mounted thermostat pack- age (cooling/heating) and a system-powered changeover con- trol package. The cooling thermostat is direct acting (DA) while the heating thermostat is reverse acting (RA).

Operation is very similar to system-powered warm-up. The changeover switch assembly is ®eld installed in the unit ple- num and is piped in-line between the volume controller and the thermostat. It consists of 2 thermally operated pneumatic valves, one for each thermostat. The tube from the volume controller is connected by a `T' into the valve assembly,

making control air available to each valve. The valve for the DA cooling thermostat is normally open as long as there is cool supply air in the plenum (Fig. 62). The other valve is normally open when warm air is being supplied, matching the RA heating thermostat (Fig. 63). Each valve is con- nected to the corresponding thermostat by a separate tube. In the cooling mode (Fig. 64), the cooling valve is open, activating the cooling thermostat, while the heating thermo- stat is isolated by the closed heating valve. On changeover from cooling to heating, the cooling valve closes and the heating valve opens, shifting control to the heating thermo- stat (Fig. 65).

60