When a VAV unit with a space temperature sensor is ac- cessed via a computer, the following additional features are available:
·ability to initiate timed override from
·temperature compensated start to calculate early start time before occupancy
·provide space temperature reset to reset the supply air set point upward when the temperature falls below the occu- pied cooling set point
An electronic expansion board may be
·fan status
·®lter status
·
·demand limiting
·IAQ Sensor
·OAQ Sensor
·alarm light
·®re unit shutdown
·®re pressurization
·®re evacuation
·®re smoke purge
When the unit is connected to the CCN (Carrier Comfort Network), the following expansion board features can be utilized:
·CCN IAQ (indoor air quality) participation
·CCN OAQ (outdoor air quality) participation
·CCN demand limit participation
·modulated power exhaust override
·ability to use multiple space temperature sensors (mul- tiples of 4 and 9 only) to average space temperature (DAV only)
A
When the unit is equipped with a
NOTE: For units without a space temperature sensor and which have not had the base unit control board accessed via soft- ware to set an occupancy schedule, the remote start/stop clo- sure will allow the unit to operate in the
Features with Network Applications Ð The base control board provides, as standard, a connection for use with a Carrier Comfort System and can also be integrated into a Carrier Comfort Network. When the unit is accessed via a PC equipped with ComfortWorks™, Building Supervisor, or Service Tool software or
·
·occupancy schedules can be programmed
·unit set points can be changed
·alarms can be monitored
This access is available on the base control board via a
Step 8 Ð Make Electrical Connections
POWER WIRING Ð Units are factory wired for the voltage shown on the unit nameplate.
When installing units, provide a disconnect per NEC (National Electrical Code) of adequate size (MOCP [maxi- mum overcurrent protection] of unit is on the informative plate). All ®eld wiring must comply with NEC and all local codes. Size wire based on MCA (minimum circuit amps) on the unit informative plate. See Fig. 17 for power wiring con- nections to the unit power terminal block and equipment ground.
The main power terminal block is suitable for use with aluminum or copper wire. See Fig. 17. Units have circuit breakers for compressors, fan motors, and control circuit. If required by local codes, provide an additional disconnect switch. Whenever external electrical sources are used, unit must be electrically grounded in accordance with local codes, or in absence of local codes, with NEC, ANSI
All ®eld wiring must comply with NEC and local code requirements.
FIELD POWER SUPPLY Ð Unit is factory wired for volt- age shown on unit nameplate. See Table 4 for electrical data.
Field wiring can be brought into the unit from bottom (through basepan and roof curb) or through side of unit (cor- ner post next to control box).
A
If disconnect box is mounted to corner post, be careful not to drill any screws into the condenser coil.
Routing Through Bottom of Unit Ð If wiring is brought in through bottom of unit, use
Use strain relief going into control box through
Install conduit connector in unit basepan as shown in Fig.
Routing Through Side of Unit Ð Route power wiring in ®eld- supplied watertight conduit into unit through
Use
Bring
After wiring is in control box, make connection to proper terminals on terminal blocks (see Field Control Wiring sec- tion on page 21).
16