LEGEND and NOTES for Fig.
LEGEND
AHA | Ð Adjustable Heat Anticipator | IFC | Ð Indoor Fan Contactor | TC | Ð Thermostat Cooling |
BP | Ð Building Pressure | IFCB | Ð Indoor Fan Circuit Breaker | TH | Ð Thermostat Heating |
BR | Ð Burner Relay | IFM | Ð | TRAN | Ð Transformer |
C | Ð Contactor, Compressor | IFR | Ð | UL | Ð Compressor Unloader |
CAP | Ð Capacitor | IGC | Ð Integrated Gas Unit Controller | VFD | Ð Variable Frequency Drive |
CB | Ð Circuit Breaker | IP | Ð Internal Protector |
| Terminal (Marked) |
CC | Ð Cooling Compensator | L | Ð Light |
| |
CCB | Ð Controller Circuit Breaker | LPS | Ð |
|
|
CCH | Ð Crankcase Heater | MGV | Ð Main Gas Valve |
| Terminal (Unmarked) |
COM | Ð Communication | NC | Ð Normally Closed |
|
|
COMP | Ð Compressor Motor | NO | Ð Normally Open |
| Terminal Block |
CR | Ð Control Relay | OAT | Ð |
| |
|
| ||||
DM | Ð Damper Motor | OFC | Ð |
| Splice |
DP | Ð Duct Pressure | OFM | Ð |
| |
EC | Ð Enthalpy Control | PEC | Ð Power Exhaust Contactor |
| Factory Wiring |
EQUIP | Ð Equipment | PEM | Ð Power Exhaust Motor |
| |
FLA | Ð Full Load Amps | PES | Ð Power Exhaust Sequencer |
| Field Wiring |
FPT | Ð Freeze Protection Thermostat | PESC Ð Power Exhaust Sequencer |
| ||
|
| ||||
FU | Ð Fuse |
| Controller |
| To Indicate Common Potential Only, |
GRD | Ð Ground | PL | Ð Plug Assembly |
| |
| Not To Represent Wiring | ||||
GVR | Ð Gas Valve Relay | R | Ð Relay |
| |
|
| ||||
HPS | Ð | RAT | Ð |
|
|
HS | Ð Hall Effect Sensor | RS | Ð Rollout Switch |
|
|
HV | Ð High Voltage | SAT | Ð |
|
|
IDM | Ð | TB | Ð Terminal Block |
|
|
NOTES:
1.Connect TRAN1 to H4 for 460 v units. Connect to H3 for 230 v. If 208/230 v units are run with a 208 v power supply connect to H2.
2.Connect TRAN2 to black lead for 460 v units. Connect to orange lead for 230 v units. If 208/230 v units are run with a 208 v power supply connect to red lead.
3.Circuit breaker must trip amps are equal to or less than 156% FLA for CB1 and CB2. All others are 140%.
4.If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
5.Compressors and/or fan motors are thermally protected.
6.Three phase motors are protected against primary single phasing conditions.
7.Red wire and violet wire are spliced together at the factory. The brown wire has a wire nut added at the factory.
TABLE A
THE FOLLOWING COMPRESSORS HAVE TWO PARALLEL WIRES RUN FROM TB1 TO THE COMPRESSORS
(NOT SHOWN ON LABEL DIAGRAM)
COMPRESSOR | VOLTAGE | WIRE | |
MODEL | QUANTITY | ||
| |||
2 |
TABLE B
THE FOLLOWING FAN MOTORS HAVE TWO PARALLEL WIRES RUN FROM TB1 TO THE FAN MOTORS
(NOT SHOWN ON LABEL DIAGRAM)
INDOOR | VOLTAGE | WIRE | |
MOTOR | QUANTITY | ||
| |||
20 HP | 2 |
50