Tables
Table 24 Ð I/O Channel Designations Base Module Ð CV
TERMINAL NO. | ASSIGNMENT | TERMINAL NO. |
| ASSIGNMENT |
SPT (CCN) Ð 10K V Thermistor | Compressor 2 Safety Ð DI (24 vac) | |||
STO (CCN) Ð 10K V Thermistor | Outside Air Enthalpy Ð DI (24 vac) | |||
OAT Ð 5K V Thermistor | Economizer Pos. Ð AO | |||
SAT Ð 5K V Thermistor | Heat 1 Relay Ð DO (24 vac) | |||
Ð | Heat 2 Relay Ð DO (24 vac) | |||
SAT Reset Ð AI (4 to 20 mA) | CV Power Exhaust 1/Modulating Power Exhaust Ð DO (115 vac) | |||
Ð | CV Power Exhaust 2 Ð DO (115 vac) | |||
Ð | Condenser Fan Ð DO (115 vac) | |||
Y1 or Remote Start/Stop Ð DI (24 vac) | OFC2 Ð DO (115 vac) | |||
Y2 Ð DI (24 vac) |
| Ð | ||
W1 Ð DI (24 vac) |
| Ð | ||
W2 Ð DI (24 vac) | K1 | Indoor Fan Relay Ð DO (LV) | ||
G Ð DI (24 vac) | K2 | Compr. 1 Ð DO | (HV) | |
Compressor 1 Safety Ð DI (24 vac) | K3 | Compr. 2 Ð DO | (HV) | |
|
|
|
|
|
Table 25 Ð I/O Channel Designations Base Module Ð VAV
TERMINAL NO. | ASSIGNMENT | TERMINAL NO. | ASSIGNMENT | |
SPT (CCN) Ð 10K V Thermistor | Compressor 2 Safety Ð DI (24 vac) | |||
RAT Ð 5K V Thermistor | Outside Air Enthalpy Ð DI (24 vac) | |||
OAT Ð 5K V Thermistor | Economizer Pos. Ð AO | |||
SAT Ð 5K V Thermistor | Heat 1 Relay − DO (24 vac) | |||
Ð | Heat Interlock Relay Ð DO (24 vac) | |||
SAT Reset Ð AI (4 to 20 mA) | Modulated Power Exhaust Ð DO (115 vac) | |||
Ð | Ð |
| ||
Ð | Condenser Fan Ð DO (115 vac) | |||
Remote Start/Stop Ð DI (24 vac) | OFC2 Ð DO (115 vac) |
| ||
Ð | Unloader 1 Ð DO (115 | vac) | ||
Ð | Unloader 2 Ð DO (115 | vac) | ||
Ð | K1 | Indoor Fan Relay Ð DO (LV) | ||
Ð | K2 | Compr. 1 (HV) |
| |
Compressor 1 Safety Ð DI (24 vac) | K3 | Compr. 2 Ð DO (HV) |
|
Table 26 Ð I/O Channel Designations Expansion Module
TERMINAL NO. | ASSIGNMENT | TERMINAL NO. | ASSIGNMENT |
|
Ð | Fire Ð Evacuation Ð DI (24 vac) |
| ||
Ð | Fire Ð Smoke Purge Ð DI (24 vac) |
| ||
Ð | Ð |
| ||
Ð | Ð |
| ||
Ð | Alarm Light Indicator Ð DO (24 vac) |
| ||
IAQ Indoor Ð AI (4 to 20 mA) | Power Exhaust Fire No. 1 Ð DO (115 | vac) | ||
IAQ Outdoor Ð AI (4 to 20 mA) | Power Exhaust Fire No. 2 Ð DO (115 | vac) | ||
Ð | Power Exhaust Fire No. 3 Ð DO (115 | vac) | ||
Fan Status Ð DI (24 vac) | Power Exhaust Fire No. 4 Ð DO (115 | vac) | ||
Filter Status − DI (24 vac) | Ð |
| ||
Field Applied Status Ð DI (24 vac) | Ð |
| ||
Demand Limit Ð DI (24 vac) | K1 | Ð |
| |
Fire Ð Unit Shutdown Ð DI (24 vac) | K2 | Ð |
| |
Fire Ð Pressurization Ð DI (24 vac) | K3 | Ð |
|
| LEGEND (Tables | KV | Ð |
AI | Ð Analog Input | LV | Ð Low Voltage |
AO | Ð Analog Output | OAT Ð | |
CCN Ð Carrier Comfort Network | OFC Ð Outdoor Fan Contactor | ||
CV | Ð Constant Volume | RAT | Ð |
DI | Ð Direct Input | SAT | Ð |
DO | Ð Direct Output | SPT | Ð Space Temperature |
HV | Ð High Voltage | STO | Ð Space Temperature Offset |
IAQ | Ð Indoor Air Quality | T | Ð Terminal |
|
| VAV | Ð Variable Air Volume |
NOTE: For 4 to 20 mA signals, all even numbered terminals are negative (−) polarity, and all odd numbered terminals are positive (+) polarity.
61