R
Y1
Y2
W1
W2
G
C
X
CONTROL
BOX
LEGEND
Field Supplied Wiring
REMOTE
START/STOP
SWITCH
VARIABLE AIR VOLUME (VAV) APPLICATIONS
Features with
Heating and cooling in both on and off modes is con- trolled to default values by the base unit control. Set points may be changed with appropriate input devices.
The control has an
During both the on and off periods, cooling operation is controlled to the supply air setting and heating is controlled to the return air setting (or to the optional space temperature sensor). During the on period, the supply fan runs continu- ously. During the off period, the supply fan will be activated if the return air sensor is outside of the set points and will run log enough to accurately sample the space temperature. The supply fan will then continue to run until any heating or cooling load is satis®ed, at which point it will turn off.
The use of a space sensor will allow for supply air reset to conserve energy and maintain comfort. If equipped with an override feature, the sensor will allow operation during
Fig. 14 Ð Field Control Remote Start/Stop
JUMPER CONNECTION
FOR VOLTAGE OUTPUT
JUMPER CONNECTION
FOR CURRENT OUTPUT
Fig. 15 Ð Indoor Air Quality Sensor Con®guration
Features with Sensor Control of Unit (Network Applica- tions) Ð The base control board provides, as standard, a con- nection for use with a Carrier VVT system and can also be integrated into a Carrier Comfort Network.
When the unit is accessed via a PC equipped with Com- fortWorks™, Building Supervisor, or Service Tool software, or accessory
·
·occupancy schedules can be programmed
·unit set points can be changed
·alarms can be monitored
This access is available on the base control board via a
the off period for a ®xed length of time.
Base unit control supports a Heat Interlock Relay (®eld supplied) to fully open the VAV terminal devices during heat- ing operation.
Standard features of a VAV unit with a remote start/stop switch are:
·control board diagnostics
·control of an outdoor condenser fan based upon outdoor air temperature
·control of modulating economizer to provide free cooling when outdoor conditions are suitable, using
·support of remote occupied/unoccupied input to start or stop the unit
·provide power exhaust output to an external power ex- haust controller
·support
·support a ®eld test for ®eld check out
·support linkage to DAV systems
·cooling capacity control of up to 6 stages plus economizer with compressors and unloaders to maintain supply air tem- perature set point during occupied periods
·control of one stage of heat to maintain
·provide a variable frequency drive high voltage relay out- put to enable VFD
·control of heat interlock relay
·compressor Time Guard override (power up, minimum off and on times)
With the addition of a remote start/stop switch heating or cooling is enabled during unoccupied periods as required to maintain space temperature to within unoccupied set points.
Additional features may be provided with Electronic Access to Unit Control Board. These features are:
·additional control board diagnostics
·electronic expansion board features (if installed)
·control of the economizer damper and indoor fan to obtain unoccupied free cooling
·
·holiday table containing up to 18 holiday schedules
·occupancy control with 8 periods for unit operation
·support a set of display, maintenance, con®guration, serv- ice, and set point data tables for interface with Building Supervisor, ComfortWorks, or Service Tool software soft- ware or accessory
15