Table 1 - Physical Data - Unit 48VT-A Cont’d)

48VT-- A

Table 1 - Physical Data - Unit 48VT-A Cont’d)

 

 

 

 

 

 

 

 

 

UNIT SIZE

 

048090

048115

048130

 

060090

060115

060130

NOMINAL CAPACITY ---

ton

 

4

 

4

 

4

 

 

5

 

5

 

5

SHIPPING WEIGHT---

lb

513

513

513

 

543

543

546

 

 

(kg)

233

233

233

 

246

246

246

COMPRESSORS

 

 

 

 

 

 

Scroll

 

 

 

 

 

Quantity

 

 

 

 

 

 

1

 

 

 

 

 

 

REFRIGERANT (R 410A)---

17.0

17.0

17.0

 

16.0

16.0

16.0

Quantity ---

lb

 

 

 

 

(kg )

 

 

7.7

 

7.7

 

7.7

 

 

7.3

 

7.3

 

7.3

REFRIGERANT METERING DEVICE

 

 

 

 

 

TXV

 

 

 

 

 

 

OUTDOOR ORIFICE in. (qty)---

 

 

0.040 (2)

 

 

 

 

 

0.049 (2)

 

 

 

 

(mm)

 

 

1.02

 

 

 

 

 

1.24

 

 

OUTDOOR COIL

 

2

...21

2

...21

2

...21

 

2

...21

2

...21

2

...21

Rows...Fins--- in.

 

 

Face Area---

sq ft

 

19.4

19.4

19.4

 

23.3

23.3

23.3

OUTDOOR FAN

 

3500

3500

3500

 

3800

3800

3800

Nominal Cfm

 

 

Diameter---

in.

 

 

22

 

22

 

22

 

 

22

 

22

 

22

 

 

(mm)

559

559

559

 

559

559

559

Motor Hp---

Rpm

 

1/4 (1100)

1/4 (1100)

1/4 (1100)

 

1/3 (1100)

1/3 (1100)

1/3 (1100)

INDOOR COIL

 

3

...17

3

...17

3

...17

 

4

...17

4

...17

4

...17

Rows...Fins--- in.

 

 

Face Area---

sq ft

 

 

5.7

 

5.7

 

5.7

 

 

5.7

 

5.7

 

5.7

INDOOR BLOWER

 

1600

1600

1600

 

1750

1750

1750

Nominal Cooling Airflow---

(CFM)

 

Size ---

in.

 

11x10

11x10

11x10

 

11x10

11x10

11x10

 

(mm)

 

279x254

279x254

279x254

 

279x254

279x254

279x254

Motor

---hp

 

 

1.0

 

1.0

 

1.0

 

 

1.0

 

1.0

 

1.0

FURNACE SECTION*

 

 

 

 

 

 

 

 

 

 

 

 

 

Burner Orifice

 

3

...38

3

...33

3

...31

 

3

...38

3

...33

3

...31

Natural Gas Qty...

Drill Size

 

Propane GasQty...

Drill Size

3

...53

3

...51

3

...49

 

3

...53

3

...51

3

...49

HIGH --- PRESSURE SWITCH (psig)

 

 

 

 

 

650 +/ ---

15

 

 

 

 

 

Cut---

out

 

 

 

 

 

 

 

 

 

 

 

Reset (Auto)

 

 

 

 

 

 

420 +/ ---

25

 

 

 

 

 

LOSS--- OF---

CHARGE /

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW--- PRESSURE SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

(Liquid Line) (psig)

 

 

 

 

 

 

20 +/ ---

5

 

 

 

 

 

Cut---

out

 

 

 

 

 

 

 

 

 

 

 

Reset (auto)

 

 

 

 

 

 

45 +/ ---

10

 

 

 

 

 

RETURN---AIR FILTERS †

 

 

 

 

 

24x36x1

 

 

 

 

 

Throwaway

(in.)

 

 

 

 

 

 

 

 

 

 

 

(mm)

 

 

 

 

 

 

 

(610x914x25)

 

 

 

 

 

*Based on altitude of 0 to 2000 ft (0---610 m).

{Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for high ---capacity type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C.

}If using accessory filter rack refer to filter rack installation instructions for correct filter size and quantity.

Table 2 – Maximum Gas Flow Capacity*

NOMINAL

INTERNAL

 

 

 

 

 

LENGTH OF PIPE, FT (m)†

 

 

 

 

 

IRON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIAMETER

10

20

30

40

50

60

70

80

90

100

125

150

175

200

PIPE, SIZE

(IN.)

(IN.)

(3.0)

(6.1)

(9.1)

(12.2)

(15.2)

(18.3)

(21.3)

(24.4)

(27.4)

(30.5)

(31.1)

(45.7)

(53.3)

(61.0)

1/2

.622

175

120

97

82

73

66

61

57

53

50

44

40

3/4

.824

360

250

200

170

151

138

125

118

110

103

93

84

77

72

1

1.049

680

465

375

320

285

260

240

220

205

195

175

160

145

135

1---1/4

1.380

1400

950

770

600

580

530

490

460

430

400

360

325

300

280

1---1/2

1.610

2100

1460

1180

990

900

810

750

690

650

620

550

500

460

430

*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5--IN. W.C. (based on a 0.60 specific gravity gas). Refer to Table 2 and the NFGC NFPA 54/ANSI.

† This length includes an ordinary number of fittings.

Table 3 – Heating Inputs

HEATING INPUT

 

NUMBER OF

 

GAS SUPPLY PRESSURE (IN. W.C.)

MANIFOLD PRESSURE

 

 

Natural{

Propane*{

(IN. W.C.)

(BTUH)

 

ORIFICES

 

 

 

 

Min

 

Max

Min

 

Max

Natural{

Propane*†

40,000

 

2

4.0

 

13.0

11.0

 

13.0

3.23.8

10.011.0

60,000

 

2

4.0

 

13.0

11.0

 

13.0

3.23.8

10.011.0

90,000

 

3

4.0

 

13.0

11.0

 

13.0

3.23.8

10.011.0

115,000

 

3

4.0

 

13.0

11.0

 

13.0

3.23.8

10.011.0

130,000

 

3

4.0

 

13.0

11.0

 

13.0

3.23.8

10.011.0

*When a unit is converted to propane, different size orifices must be used. See separate, natural ---

to propane conversion kit instructions.---

 

{Based on altitudes from sea level to 2000 ft (610 m) above sea level. In th e U.S.A. for altitudes above 2000 ft (610 m), reduce input rating 4 percent for each additional 1000 ft (305 m) above sea level. In Canada, from 2000 ft (610 m) above sea level to 4500 ft (1372 m) above sea level, derate the unit 10 percent.

10

Page 10
Image 10
Carrier 48VT(N) Physical Data - Unit 48VT-ACont’d, Maximum Gas Flow Capacity, Heating Inputs, 48VT--A