Carrier specifications 50PCH,PCV Unit Electrical Data, a50-8162

Models: 50PCH

1 52
Download 52 pages 49.25 Kb
Page 19
Image 19
Table 3 — 50PCH,PCV Unit Electrical Data

Table 3 — 50PCH,PCV Unit Electrical Data

50PCH,PCV

VOLTAGE

RATED

VOLTAGE

COMPRESSOR

 

STANDARD UNITS

 

UNITS WITH HIGH-STATIC BLOWER

UNIT

CODE

VOLTAGE

MIN/MAX

QTY

RLA

LRA

Fan Motor

Total Unit

Min Circuit

Max Fuse/

Fan Motor

Total Unit

Min Circuit

Max Fuse/

V-Ph-Hz*

FLA

FLA

AMP

HACR

FLA

FLA

AMP

HACR

006

3

208/230-1-60

197/254

1

3.3

17.7

0.40

3.7

4.5

15

4

265-1-60

239/292

1

2.9

13.5

0.40

3.3

4.0

15

 

009

3

208/230-1-60

197/254

1

5.6

22.2

0.80

6.4

7.8

15

4

265-1-60

239/292

1

3.8

18.8

0.70

4.5

5.5

15

 

012

3

208/230-1-60

197/254

1

5.1

32.5

0.80

5.9

7.2

15

4

265-1-60

239/292

1

4.0

31.5

0.70

4.7

5.7

15

 

015

3

208/230-1-60

197/254

1

6.0

29.0

1.00

7.0

8.5

15

1.00

7.0

8.5

15

4

265-1-60

239/292

1

5.4

28.0

0.86

6.3

7.6

15

0.86

6.3

7.6

15

 

018

3

208/230-1-60

197/254

1

7.2

33.0

1.00

8.2

10.0

15

1.50

8.7

10.5

15

4

265-1-60

239/292

1

5.9

28.0

0.86

6.8

8.2

15

1.30

7.2

8.7

15

 

024

3

208/230-1-60

197/254

1

12.8

58.3

1.50

14.3

17.5

30

3.00

15.8

19.0

30

4

265-1-60

239/292

1

9.6

54.0

1.30

10.9

13.3

20

2.70

12.3

14.7

20

 

 

3

208/230-1-60

197/254

1

14.1

73.0

3.00

17.1

20.6

30

3.00

17.1

20.6

30

030

4

265-1-60

239/292

1

11.2

60.0

2.70

13.9

16.7

25

2.70

13.9

16.7

25

5

208/230-3-60

197/254

1

8.9

58.0

3.00

11.9

14.1

20

3.00

11.9

14.1

20

 

 

6

460-3-60

414/506

1

4.2

28.0

1.70

5.9

7.0

15

1.70

5.9

7.0

15

 

3

208/230-1-60

197/254

1

16.7

79.0

1.80

18.5

22.7

35

3.00

19.7

23.9

40

036

4

265-1-60

239/292

1

13.5

72.0

2.00

15.5

18.9

30

2.70

16.2

19.6

30

5

208/230-3-60

197/254

1

10.4

73.0

1.80

12.2

14.8

25

3.00

13.4

16.0

25

 

 

6

460-3-60

414/506

1

5.8

38.0

1.24

7.0

8.5

15

1.70

7.5

9.0

15

 

3

208/230-1-60

197/254

1

17.9

112.0

3.00

20.9

25.4

40

3.00

20.9

25.4

40

042

5

208/230-3-60

197/254

1

13.5

88.0

3.00

16.5

19.9

30

3.00

16.5

19.9

30

6

460-3-60

414/506

1

6.0

44.0

1.70

7.7

9.2

15

1.70

7.7

9.2

15

 

 

1

575-3-60

518/633

1

4.9

34.0

1.40

6.3

7.5

15

1.40

6.3

7.5

15

 

3

208/230-1-60

197/254

1

21.8

117.0

3.40

25.2

30.7

50

4.90

26.7

32.2

50

048

5

208/230-3-60

197/254

1

13.7

83.1

3.40

17.1

20.5

30

4.90

18.6

22.0

35

6

460-3-60

414/506

1

6.2

41.0

1.80

8.0

9.6

15

2.50

8.7

10.3

15

 

 

1

575-3-60

518/633

1

4.8

33.0

1.40

6.2

7.4

15

1.90

6.7

7.9

15

 

3

208/230-1-60

197/254

1

26.3

134.0

4.90

31.2

37.8

60

5.80

32.1

38.7

60

060

5

208/230-3-60

197/254

1

15.6

110.0

4.90

20.5

24.4

40

5.80

21.4

25.3

40

6

460-3-60

414/506

1

7.8

52.0

2.50

10.3

12.3

20

2.60

10.4

12.4

20

 

 

1

575-3-60

518/633

1

5.8

38.9

1.90

7.7

9.2

15

2.30

8.1

9.6

15

 

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

LRA

Locked Rotor Amps

RLA

Rated Load Amps

*Units using 460-v and ECM (electronically commutated motor), modulating HWR (hot water reheat), and/or internal secondary pump will require a neutral wire from the supply side in order to feed accessory with 265-v.

NOTES:

1.HACR circuit breaker in U.S.A. only.

2.All fuses

3.Class RK-5.

a50-8162

Fig. 21 — Typical Single-Phase Line Voltage Power Connection

19

Page 19
Image 19
Carrier specifications 50PCH,PCV Unit Electrical Data, a50-8162