Carrier 50PCH APPENDIX A - WSHP OPEN SCREEN CONFIGURATION cont, BAS - Building Automation System

Models: 50PCH

1 52
Download 52 pages 49.25 Kb
Page 45
Image 45

APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)

SCREEN NAME

POINT NAME

 

PASSWORD

EDITABLE

RANGE

DEFAULT

NOTES

 

LEVEL

 

 

 

 

 

 

 

 

 

 

Occupied Heating

 

 

X

40 - 90 ° F

72 ° F

Defines the Occupied

 

 

 

 

Heating Set Point

 

 

 

 

 

 

 

 

 

 

Occupied Cooling

 

 

X

55 - 99 ° F

76 ° F

Defines the Occupied

 

 

 

 

Cooling Set Point

 

 

 

 

 

 

 

 

 

 

Unoccupied Heating

 

 

X

40 - 90 ° F

55 ° F

Defines the Unoccupied

 

 

 

 

Heating Set Point

 

 

 

 

 

 

 

 

 

 

Unoccupied Cooling

 

 

X

55 - 99 ° F

90 ° F

Defines the Unoccupied

 

 

 

 

Cooling Set Point

 

 

 

 

 

 

 

 

 

 

Effective Heating

 

 

X

0 - 10 ° F

 

Takes into effect bias (maximum

 

 

Set Point

 

 

 

allowable set point deviation)

 

 

 

 

 

 

 

 

 

Effective Cooling

 

 

X

0 - 10 ° F

 

Takes into effect bias (maximum

 

 

Set Point

 

 

 

allowable set point deviation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Uses historical data to calculate

 

 

Optimal Start

 

 

 

 

 

ramp up time so as to be at set point

Configuration

 

 

 

 

 

 

at occupied/unoccupied time

 

 

User/Admin

 

 

 

Defines the control set point used

 

 

 

 

 

 

 

 

Occupied RH

 

 

 

 

during occupied periods (Viewable

 

 

Password level

 

 

 

 

 

X

0 - 100%

65%

only if Humidity Sensor = Installed/

 

 

Set Point

 

access

 

 

 

Determines when to start

Set Points

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification when occupied)

 

 

 

 

 

 

 

 

Defines the control set point used

 

 

Unoccupied RH

 

 

 

 

 

during unoccupied periods

 

 

 

 

X

0 - 100%

90%

(Viewable only if Humidity Sensor =

 

 

Set Point

 

 

 

 

 

 

 

 

 

Installed/Determines when to start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification when unoccupied)

 

 

 

 

 

 

 

 

Defines the control set point used to

 

 

DCV CTRL Start

 

 

X

0 - 9999 ppm

500 ppm

start increasing ventilation during

 

 

Set Point

 

 

occupied periods (Viewable only if

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ventilation DMP Type = DCV)

 

 

 

 

 

 

 

 

Defines the control set point

 

 

 

 

 

 

 

 

used to define where the ventilation

 

 

DCV Max CTRL

 

 

 

 

 

will reach its maximum limit during

 

 

 

 

X

0 - 9999 ppm

1050 ppm

occupied periods (Viewable only if

 

 

Set Point

 

 

 

 

 

 

 

 

 

Ventilation DMP Type = DCV/Used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to determine DCV ending control

 

 

 

 

 

 

 

 

point)

 

 

Start Time

 

 

X

00:00 - 23:59

06:00

Defines the start time for an

 

 

 

 

occupied period

 

 

 

 

 

 

 

 

 

 

End Time

 

 

X

00:00 - 24:00

18:00

Defines the ending time of an

 

 

 

 

occupied period

 

 

 

 

 

 

 

 

Configuration

Mon

 

 

X

No/Yes

Yes

Determines if this day is included

 

 

in this schedule

 

Tue

 

 

X

No/Yes

Yes

Determines if this day is included

 

 

User/Admin

in this schedule

Schedule

 

 

 

 

 

Determines if this day is included

Wed

 

Password level

X

No/Yes

Yes

 

in this schedule

 

 

 

 

access

 

 

 

 

Thur

 

X

No/Yes

Yes

Determines if this day is included

 

 

 

 

 

 

 

 

 

 

 

in this schedule

Weekly Schedule

Fri

 

 

X

No/Yes

Yes

Determines if this day is included

 

 

 

 

in this schedule

 

 

 

 

 

 

 

 

 

 

Sat

 

 

X

No/Yes

No

Determines if this day is included

 

 

 

 

in this schedule

 

 

 

 

 

 

 

 

 

 

Sun

 

 

X

No/Yes

No

Determines if this day is included

 

 

 

 

in this schedule

 

 

 

 

 

 

 

 

 

 

Start Month

 

 

X

0 - 12

0

Defines the start month of this

Configuration

 

 

hoilday schedule

 

 

 

 

 

 

Start Day

 

 

X

0 - 31

0

Defines the start day of this holiday

 

 

 

 

 

 

 

schedule

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Start Time

 

User/Admin

X

00:00 - 23:59

0:00

Determines the start time for this

Schedule

 

schedule

 

 

Password level

 

 

 

 

 

 

 

 

 

 

Defines the month to end this

 

End Month

 

access

X

0 - 12

0

 

 

hoilday schedule

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exception

End Day

 

 

X

0 - 31

0

Defines the day to end this holiday

 

 

schedule

 

 

 

 

 

 

Schedules 1 - 12

 

 

 

 

 

 

 

End Time

 

 

X

00:00 - 24:00

0:00

Determines the time to end this

 

 

 

 

 

 

 

 

schedule

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

BAS — Building Automation System

 

 

 

 

 

DCV

Demand Controlled Ventilation

 

 

 

 

 

IAQ

Indoor Air Quality

 

 

 

 

 

OAT

Outdoor Air Temperature

 

 

 

 

 

RH

Relative Humidity

 

 

 

 

 

SAT — Supply Air Temperature

 

 

 

 

 

SPT

Space Temperature

 

 

 

 

 

TPI

Third Party Integration

 

 

 

 

 

45

Page 45
Image 45
Carrier 50PCH APPENDIX A - WSHP OPEN SCREEN CONFIGURATION cont, BAS - Building Automation System, Indoor Air Quality