Deluxe D |
12
|
| LEGEND | |
AL | — Alarm Relay Contacts | LOC | — Loss of Charge Pressure Switch |
BM | — Blower Motor | MV | — Motorized Valve |
BMC | — Blower Motor Capacitor | MVES | — Motorized Valve End Switch |
CB | — Circuit Breaker | NEC | — National Electrical Code |
CC | — Compressor Contactor | P1 | — Field Wiring Terminal Block |
CO | — Sensor, Condensate Overflow | RVS | — Reversing Valve Solenoid |
FP1 | — Sensor, Low Temperature Protection Water Coil | TRANS | — Transformer |
FP2 | — Sensor, Low Temperature Protection Air Coil | TXV | — Thermostatic Expansion Valve |
HP | — |
| Field Line Voltage Wiring |
HPWS — |
| ||
| Field Low Voltage Wiring | ||
HWTS | — High Leaving Water Temperature Switch |
| |
JW1 | — Jumper, Alarm |
| Printed Circuit Trace |
*Optional. |
|
| Optional Wiring |
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Thermistor
Ground
Wire Nut
NOTES:
1.Compressor thermally protected internally.
2.All wiring to the unit must comply with NEC and local codes.
3.Transformer is wired to
4.FP1 thermistor provides freeze protection for water. When using anti- freeze solutions, cut JW3 jumper.
5.Refer to microprocessor control, LON, or thermostat installation instruc- tions for wiring to the unit. Wire “Y” from thermostat to “Y1” Deluxe D
a50-8491
when motorized valve is not used. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage. Heat/cool thermostats not compatible with motorized water valve.
6.
7.Transformer secondary ground via green wire with yellow stripe from “C” terminal to control box.
8.Blower motor is factory wired for medium and high speeds. For any other combination of speeds, attach black wire to the higher of the two desired speed taps and the blue wire to the lower of the two desired speed taps.
Fig. 14 — 50PCH,PCV Units with Deluxe D Controller,