stage 2 followed by heating stage 2 then reduces capacity to heating stage 1. Operates for 1 minute per step. DEHUMIDIFICATION TEST — Tests dehumidification mode. Operates for 2 minutes.

AUXILIARY HEATING TEST — Tests auxiliary heat. Sequences fan on and enables heating coil for 1 minute.

H2O ECONOMIZER TEST — Tests entering/returning water loop economizer operation. Sequences fan and opens economizer water valve for one minute.

OPEN VENT DAMPER 100% TEST — Tests outside air (OA) damper operation.

PREPOSITION OA DAMPER — Prepositions OA damper actuator to set proper preload.

NOTE: The auxiliary heating test, H2O economizer test, open vent damper 100% test, and preposition OA damper features will not be visible on the screen unless configured.

Once tests are complete, set unit test back to disable. Unit will automatically reset to disable after 1 hour.

Retry Mode — In Retry mode, the status LED will start to flash slowly to signal that the control is trying to recover from an input fault. The control will stage off the outputs and try to again satisfy the thermostat used to terminal Y. Once the ther- mostat input calls are satisfied, the control will continue normal operation.

NOTE: If 3 consecutive faults occur without satisfying the thermostat input call to terminal Y, the control will go into lockout mode. The last fault causing the lockout is stored in memory and can be viewed by entering Test mode.

TEST LED — Test LED will be activated any time the De- luxe D control is in test mode. The Test LED light is yellow. FAULT LED — Fault LED light is red. The fault LED will al- ways flash a code representing the last fault in memory. If there is no fault in memory, the fault LED will flash code 1 on the and appear as 1 fast flash alternating with a 10-second pause. See Table 31.

Table 29 — Complete C Control Current LED

Status and Alarm Relay Operations

LED STATUS

DESCRIPTION OF OPERATION

ALARM RELAY

 

On

Normal Mode

Open

 

Normal Mode with PM Warning

Cycle (closed 5

 

 

sec., Open 25 sec.)

 

 

 

 

 

 

Off

Complete C Control is

Open

 

non-functional

 

 

 

Slow Flash

 

Fault Retry

 

Open

 

Fast Flash

 

Lockout

 

Closed

Slow Flash

Over/Under Voltage Shutdown

Open (Closed after

15 minutes)

 

 

 

 

 

Flashing Code 1

Test Mode — No fault in memory

Cycling Code 1

Flashing Code 2

Test Mode — HP Fault in memory

Cycling Code 2

Flashing Code 3

Test Mode — LP Fault in memory

Cycling Code 3

Flashing Code 4

Test Mode — FP1 Fault in memory

Cycling Code 4

Flashing Code 5

Test Mode — FP2 Fault in memory

Cycling Code 5

Flashing Code 6

Test Mode — CO Fault in memory

Cycling Code 6

Flashing Code 7

Test Mode — Over/Under shutdown

Cycling Code 7

 

 

 

in memory

 

 

Flashing Code 8

Test Mode — PM in memory

Cycling Code 8

Flashing Code 9

Test Mode — FP1/FP2 Swapped

Cycling Code 9

Fault in memory

 

 

 

 

 

LEGEND

 

 

CO

Condensate Overflow

LED

Light-Emitting Diode

FP

Freeze Protection

LP

Low Pressure

HP

High Pressure

PM

Performance Monitor

Aquazone™ Deluxe D Control LED Indica-

tors — There are 3 LED indicators on the Deluxe D control: STATUS LED — Status LED indicates the current status or mode of the Deluxe D control. The Status LED light is green.

NOTES:

1.Slow flash is 1 flash every 2 seconds.

2.Fast flash is 2 flashes every 1 second.

3.EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by a 10-second pause. This sequence will repeat continually until the fault is cleared.

Table 30 — Complete C Control LED Code and

Fault Descriptions

 

LED

 

 

FAULT

 

DESCRIPTION

 

CODE

 

 

 

 

 

 

 

 

 

 

 

1

 

 

No fault in memory

There has been no fault since the last power-down to power-up sequence

 

2

 

 

High-Pressure Switch

HP open instantly

 

3

 

 

Low-Pressure Switch

LP open for 30 continuous seconds before or during a call (bypassed for first 60 seconds)

 

4

 

 

Freeze Protection Coax — FP1

FP1 below Temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)

 

5

 

 

Freeze Protection Air Coil — FP2

FP2 below Temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)

 

6

 

 

Condensate overflow

Sense overflow (grounded) for 30 continuous seconds

7 (Autoreset)

 

 

Over/Under Voltage Shutdown

"R" power supply is <19VAC or >30VAC

 

8

 

 

PM Warning

 

Performance Monitor Warning has occurred.

 

9

 

FP1 and FP2 Thermistors are swapped

FP1 temperature is higher than FP2 in heating/test mode, or FP2 temperature is higher than

 

 

 

 

 

 

 

FP1 in cooling/test mode.

 

 

 

 

LEGEND

 

 

 

FP

Freeze Protection

LP

Low Pressure

 

HP

High Pressure

 

PM

Performance Monitor

LED

Light-Emitting Diode

 

 

 

37

Page 37
Image 37
Carrier 50PCH specifications Aquazone Deluxe D Control LED Indica, Complete C Control LED Code Fault Descriptions, Led

50PCH specifications

The Carrier 50PCH is a cutting-edge series of air-cooled chillers designed to deliver exceptional cooling performance in a wide range of commercial applications. Engineered with efficiency and reliability in mind, the 50PCH stands out for its innovative technologies and robust construction, making it a preferred choice for facility managers and HVAC professionals.

One of the main features of the Carrier 50PCH is its advanced scroll compressor technology. This system consists of high-efficiency scroll compressors that optimize energy consumption while maintaining consistent cooling output. The incorporation of variable speed technology enables the chillers to adapt to fluctuating load demands, resulting in significant energy savings and reduced operational costs.

The 50PCH chillers also boast a high energy efficiency ratio (EER) and coefficient of performance (COP), ensuring compliance with stringent energy regulations and standards. They are designed with eco-friendly refrigerants, which contribute to lower greenhouse gas emissions, making them an environmentally responsible choice for modern buildings.

In addition to its energy-efficient operation, the 50PCH series is equipped with advanced controls that allow for seamless integration into building management systems. The intuitive interface facilitates monitoring and adjustment of set points, ensuring optimal comfort conditions. Furthermore, the chillers come with extensive diagnostic capabilities, enabling proactive maintenance and reducing the risk of unexpected downtime.

The robust construction of the 50PCH series enhances durability and reliability. With an all-weather aluminum cabinet, these chillers are designed to withstand harsh environmental conditions, ensuring long-term performance. The units undergo rigorous testing to meet high industry standards for quality and reliability.

Another distinguishing characteristic of the Carrier 50PCH is its whisper-quiet operation. Engineered for low sound levels, these chillers minimize noise pollution in sensitive environments, such as hospitals, schools, or residential areas.

In summary, the Carrier 50PCH series combines exceptional performance, energy efficiency, and innovative technology in a robust and reliable package. It highlights the best in modern HVAC design, making it an ideal solution for a wide array of climate control needs in commercial and institutional settings. With its advanced features and commitment to sustainability, the 50PCH is undoubtedly a leader in the air-cooled chiller market.