Table 13 — Operating Limits — 50PCH,PCV Units
OPERATING LIMITS | COOLING (F) | HEATING (F) |
AIR LIMITS |
|
|
Min. Ambient Air – db | 45 | 39 |
Rated Ambient Air – db | 80.6 | 68 |
Max. Ambient Air – db | 110 | 85 |
Min. Entering Air – db/wb | 50 | 40 |
Rated Entering Air – db/wb | 80.6/66.2 | 68 |
Max. Entering Air – db/wb | 110/83 | 80 |
WATER LIMITS |
|
|
Min. Entering Water | 30 | 20 |
Normal Entering Water | ||
Max. Entering Water | 120 | 90 |
Normal Water Flow | ||
LEGEND |
|
|
db — Dry Bulb wb — Wet Bulb
Scroll Compressor Rotation — It is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the prop- er direction:
1.Connect service gages to suction and discharge pressure fittings.
2.Energize the compressor.
3.The suction pressure should drop and the discharge pressure should rise, as is normal on any
If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
1.Turn off power to the unit. Install disconnect tag.
2.Reverse any two of the unit power leads.
3.Reapply power to the unit and verify pressures are correct.
The suction and discharge pressure levels should now move to their normal
When the compressor is rotating in the wrong direction, the unit makes more noise and does not provide cooling.
After a few minutes of reverse operation, the scroll com- pressor internal overload protection will open, thus activating the unit lockout. This requires a manual reset. To reset, turn the thermostat on and then off.
NOTE: There is a
Unit Start-Up Cooling Mode
1.Adjust the unit thermostat to the warmest position. Slowly reduce the thermostat position until the compres- sor activates.
2.Check for cool air delivery at unit grille a few minutes after the unit has begun to operate.
3.Verify that the compressor is on and that the water flow rate is correct by measuring pressure drop through the heat exchanger using P/T plugs. See Table 14. Check the elevation and cleanliness of the condensate lines; any dripping could be a sign of a blocked line. Be sure the condensate trap includes a water seal.
4.Check the temperature of both supply and discharge wa- ter. Compare to Tables
5.Check air temperature drop across the coil when com- pressor is operating. Air temperature drop should be between 15 and 25 F.
Table 14 — Water Temperature Change
Through Heat Exchanger
| COOLING | HEATING | |||
WATER FLOW RATE (GPM) | RISE (F) | DROP (F) | |||
| Min | Max | Min | Max | |
For Closed Loop: Ground Source or | 9 | 12 | 4 | 8 | |
Cooling/Boiler Systems at 3 gpm/ton | |||||
|
|
|
| ||
For Open Loop: Ground Water Systems at | 20 | 26 | 10 | 17 | |
1.5 gpm/ton | |||||
|
|
|
|
26