COMPLETE C

a50-8327.eps

COMPLETE C

PEC

PEC12-18

PEC

LEGEND

NOTES:

AL

Alarm Relay Contacts

BM

Blower Motor

BR

Blower Relay

CAP

Capacitor

CB

Circuit Breaker

CO

Sensor, Condensate Overflow

CR

Compressor Relay

DM

Damper Motor

FP1

Sensor, Water Coil Freeze Protection

FP2

Sensor, Air Coil Freeze Protection

FSS

Fan Speed Switch

HP

High-Pressure Switch

JW1

Jumper Wire for Alarm

LOC

Loss of Charge Pressure Switch

PB

Power Terminal Block

RVS

Reversing Valve Solenoid

TRANS

Transformer

WV

Water Valve

----------

 

Field Line Voltage Wiring

 

 

 

 

 

Field Low-Voltage Wiring

 

 

 

 

 

Option Low-Voltage Wiring

 

 

 

 

 

 

 

 

 

 

Printed Circuit Trace

 

Relay/Contactor Coil

 

Solenoid Coil

 

Thermistor

 

Circuit Breaker

 

Relay Contacts-N.O.

 

Switch-Temperature

 

Switch-High Pressure

 

Switch-Low Pressure

 

Ground

>>

Wire Nut

Mate-N-Lock

 

*Optional wiring.

†Registered trademark of Echelon Corporation.

1.Compressor and blower motor thermally pro- tected internally.

2.All wiring to the unit must comply with local codes.

3.Transformer is wired to 115-V (WHT) lead for 115/1/60 units, 265-V (BRN) lead for 265/1/60 units, 240-V (ORG) lead for 240/1/50 units, or 208-V (RED) lead for 208/1/60 units.

Rewire transformer L1 connection if voltage is 230-1-60 or 220-1-50, insulate unused lead.

4.FP1 thermistor provides freeze protection for WATER. When using ANTI-FREEZE solutions, cut JW3 jumper.

5.Refer to LonWorks† Installation, Application, and Operation manual for control wiring to the unit. Low voltage wiring must be “class 1” and voltage rated equal to or greater than unit supply voltage.

6.Factory-cut jumper (JW1). Dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground available from top 2 standoffs as shown.)

Fig. 18 — 50PEC Unit with Complete C and LON Controllers

19

Page 19
Image 19