DELUXE D

a50-8328

DELUXE D

 

 

LEGEND

AL

Alarm Relay Contacts

BM

Blower Motor

CAP

Capacitor

CB

Circuit Breaker

CO

Sensor, Condensate Overflow

CR

Compressor Relay

DM

Damper Motor

FP1

Sensor, Water Coil Freeze Protection

FP2

Sensor, Air Coil Freeze Protection

FSS

Fan Speed Switch

HP

High-Pressure Switch

JW1

Jumper Wire for Alarm

LOC

Loss of Charge Pressure Switch

PB

Power Terminal Block

RVS

Reversing Valve Solenoid

TRANS

Transformer

WV

Water Valve

----------Field Line Voltage Wiring

Field Low-Voltage Wiring Printed Circuit Trace

*Optional wiring.

>>

Relay/Contactor Coil

Solenoid Coil

Thermistor

Circuit Breaker

Relay Contacts-N.O.

Switch-Temperature

Switch-High Pressure

Switch-Low Pressure

Ground

Wire Nut

Mate-N-Lock

NOTES:

1.Compressor and blower motor thermally pro- tected internally.

2.All wiring to the unit must comply with local codes.

3.Transformer is wired to 115-V (WHT) lead for 115/1/60 units, 265-V (BRN) lead for 265/1/60 units, 240-V (ORG) lead for 240/1/50 units, or 208-V (RED) lead for 208/1/60 units.

Rewire transformer L1 connection if voltage is 230-1-60 or 220-1-50, insulate unused lead.

4.FP1 thermistor provides freeze protection for WATER. When using ANTI-FREEZE solutions, cut JW3 jumper.

5.Refer to Microprocessor Control Installation, Application, and Operation manual for control wiring to the unit. Low voltage wiring must be “class 1” and voltage rated equal to or greater than unit supply voltage.

6.Factory-cut jumper (JW4). Dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via Deluxe D board standoffs and screws to control box. (Ground available from top 2 standoffs as shown.)

Fig. 19 — 50PEC Unit with Deluxe D and LON Controllers

20

Page 20
Image 20
Carrier 50PEC09-18 specifications A50-8328, Sensor, Water Coil Freeze Protection