Carrier 50PEC09-18 specifications Complete C Control LED Code and Fault Descriptions

Models: 50PEC09-18

1 60
Download 60 pages 53.46 Kb
Page 44
Image 44

label. For example, flashing code 1 will have an alarm relay cycling code 1. Code 1 indicates the control has not faulted since the last power-off to power-on sequence.

WSHP Open Test Mode — To enter WSHP Open test mode, navigate from the BACview6 home screen to the config- uration screen. Choose the service screen and enable unit test. The controller will then test the following:

FAN TEST — Tests all fan speeds, sequences fan from low to high, and operates each speed for one minute. Resets to disable on completion.

COMPRESSOR TEST — Tests compressor cooling and heating operation. Sequences cooling stage 1 then cooling stage 2 followed by heating stage 2 then reduces capacity to heating stage 1. Operates for 1 minute per step.

DEHUMIDIFICATION TEST — Tests dehumidification mode. Operates for 2 minutes.

AUXILIARY HEATING TEST — Tests auxiliary heat. Sequences fan on and enables heating coil for 1 minute.

H2O ECONOMIZER TEST — Tests entering/returning water loop economizer operation. Sequences fan and opens economizer water valve for one minute.

OPEN VENT DAMPER 100% TEST — Tests outside air (OA) damper operation.

PREPOSITION OA DAMPER — Prepositions OA damper actuator to set proper preload.

NOTE: The auxiliary heating test, H2O economizer test, open vent damper 100% test, and preposition OA damper features will not be visible on the screen unless configured.

Once tests are complete, set unit test back to disable. Unit will automatically reset to disable after 1 hour.

Retry Mode — In Retry mode, the status LED will start to flash slowly to signal that the control is trying to recover from an input fault. The control will stage off the outputs and try to again satisfy the thermostat used to terminal Y. Once the thermostat in- put calls are satisfied, the control will continue normal operation.

NOTE: If 3 consecutive faults occur without satisfying the thermostat input call to terminal Y, the control will go into lockout mode. The last fault causing the lockout is stored in memory and can be viewed by entering Test mode.

Aquazone™ Deluxe D Control LED Indica-

tors — There are 3 LED indicators on the Deluxe D control:

STATUS LED — Status LED indicates the current status or mode of the Deluxe D control. The Status LED light is green.

TEST LED — Test LED will be activated any time the De- luxe D control is in Test mode. The Test LED light is yellow.

FAULT LED — Fault LED light is red. The fault LED will always flash a code representing the last fault in memory. If there is no fault in memory, the fault LED will flash code 1 and appear as 1 fast flash alternating with a 10-second pause. See Table 17.

Table 15 — Complete C Control Current LED Status and Alarm Relay Operations

LED STATUS

DESCRIPTION OF OPERATION

ALARM RELAY

On

Normal Mode

Open

Normal Mode with PM Warning

Cycle (Closed 5 sec, Open 25 sec)

 

Off

Complete C Control is non-functional

Open

Slow Flash

Fault Retry

Open

Over/Under Voltage Shutdown

Open (Closed after 15 minutes)

 

Fast Flash

Lockout

Closed

Flashing Code 1

Test Mode — No fault in memory

Cycling Code 1

Flashing Code 2

Test Mode — HP Fault in memory

Cycling Code 2

Flashing Code 3

Test Mode — LP Fault in memory

Cycling Code 3

Flashing Code 4

Test Mode — FP1 Fault in memory

Cycling Code 4

Flashing Code 5

Test Mode — FP2 Fault in memory

Cycling Code 5

Flashing Code 6

Test Mode — CO Fault in memory

Cycling Code 6

Flashing Code 7

Test Mode — Over/Under shutdown in memory

Cycling Code 7

Flashing Code 8

Test Mode — PM in memory

Cycling Code 8

Flashing Code 9

Test Mode — FP1/FP2 swapped fault in memory

Cycling Code 9

 

 

LEGEND

 

 

 

CO

Condensate Overflow

LED

Light-Emitting Diode

FP

Freeze Protection

LP

Low Pressure

HP

High Pressure

PM

Performance Monitor

NOTES:

1.Slow flash is 1 flash every 2 seconds.

2.Fast flash is 2 flashes every 1 second.

3.EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by a 10-second pause. This sequence will repeat continually until the fault is cleared.

Table 16 — Complete C Control LED Code and Fault Descriptions

 

LED CODE

 

FAULT

DESCRIPTION

1

 

No fault in memory

There has been no fault since the last power-off to power-on sequence

2

 

High-Pressure Switch

HP open instantly

3

 

Low-Pressure Switch

LP open for 30 continuous seconds before or during a call (bypassed for first 60 seconds)

4

 

Freeze Protection Coax — FP1

FP1 below temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)

5

 

Freeze Protection Air Coil — FP2

FP2 below temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)

6

 

Condensate overflow

Sensor overflow (grounded) for 30 continuous seconds

7 (Autoreset)

Over/Under Voltage Shutdown

"R" power supply is <19-vac or >30-vac

8

 

PM Warning

 

Performance monitor Warning has occurred.

9

 

FP1 and FP2 Thermistors are swapped

FP1 temperature is higher than FP2 in heating/test mode, or FP2 temperature is higher than FP1 in

 

 

 

 

cooling/test mode.

 

 

LEGEND

 

 

FP

Freeze Protection

LP — Low Pressure

 

HP

High Pressure

PM — Performance Monitor

LED — Light-Emitting Diode

44

Page 44
Image 44
Carrier 50PEC09-18 specifications Complete C Control LED Code and Fault Descriptions