FIELD SELECTABLE INPUTS
Jumpers and DIP (dual
IMPORTANT: Jumpers and DIP switches should only be clipped when power to control board has been turned off.
Complete C Control Jumper Settings (See Fig. 17, 18, and 21)
WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3,
ALARM RELAY SETTING — Select jumper 1 (JW1) for connecting alarm relay terminal (AL2) to
Complete C Control DIP Switches — The Com- plete C control has one DIP switch block with five switches. See Fig. 17, 18, and 21.
PERFORMANCE MONITOR (PM) — DIP switch 1 will enable or disable this feature. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.
STAGE 2 — DIP switch 2 will enable or disable compressor delay. Set DIP switch to OFF for Stage 2 in which the compres- sor will have a
SWITCH 3 AND SWITCH 4 — Not used.
FREEZE PROTECTION (FP1) — DIP switch 5 is used to initiate one or 3 tries for the FP1 fault. If there is water freeze protection for the water coil then DIP switch 5 can be set to lock out on the FP1 fault after one try. ON = One try. OFF = 3 tries.
Deluxe D Control Jumper Settings (See Fig. 19, 20, and 22)
WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3,
ALARM RELAY SETTING — Select jumper 4
LOW PRESSURE SETTING — The Deluxe D control can be configured for low pressure setting (LP). Select jumper 1
Deluxe D Control DIP Switches — The Deluxe D control has 2 DIP switch blocks. Each DIP switch block has 8 switches and is labeled either S1 or S2 on the circuit board. See Fig. 19, 20, and 22.
DIP SWITCH BLOCK 1 (S1) — This set of switches offers the following options for Deluxe D control configuration:
Performance Monitor (PM) — Set switch 1 to enable or dis- able performance monitor. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.
Compressor Relay Staging Operation — Switch 2 will en- able or disable compressor relay staging operation. The
compressor relay can be set to turn on with Stage 1 or Stage 2 call from the thermostat. This setting is used with dual stage units (units with 2 compressors and 2 Deluxe D controls) or in master/slave applications. In master/slave applications, each compressor and fan will stage according to its switch 2 setting. If switch is set to Stage 2, the compressor will have a
NOTE: If DIP switch is set for Stage 2, the alarm relay will not cycle during Test mode.
Heating/Cooling Thermostat Type — Switch 3 provides selec- tion of thermostat type. Heat pump or heat/cool thermostats can be selected. Select OFF for heat/cool thermostats. When in heat/cool mode, Y1 is used for Cooling Stage 1, Y2 is used for Cooling Stage 2, W1 is used for Heating Stage 1 and O/W2 is used for Heating Stage 2. Select ON for heat pump applica- tions. In heat pump mode, Y1 used is for Compressor Stage 1, Y2 is used for Compressor Stage 2, W1 is used for Heating Stage 3 or emergency heat, and O/W2 is used for RV (heating or cooling) depending upon switch 4 setting.
O/B Thermostat Type — Switch 4 provides selection for heat pump O/B thermostats. O is cooling output. B is heating out- put. Select ON for heat pumps with O output. Select OFF for heat pumps with B output.
Dehumidification Fan Mode — Switch 5 provides selection of normal or dehumidification fan mode. Select OFF for dehu- midification mode. The fan speed relay will remain OFF dur- ing Cooling Stage 2. Select ON for normal mode. The fan speed relay will turn on during Cooling Stage 2 in normal mode.
Switch 6 — Not used.
Boilerless Operation — Switch 7 provides selection of boiler- less operation and works in conjunction with switch 8. In boil- erless operation mode, only the compressor is used for heating when FP1 is above the boilerless changeover temperature set by switch 8 below. Select ON for normal operation or select OFF for boilerless operation.
Boilerless Changeover Temperature — Switch 8 on S1 pro- vides selection of boilerless changeover temperature set point. Select OFF for set point of 50 F or select ON for set point of 40 F.
If switch 8 is set for 50 F, then the compressor will be used for heating as long as the FP1 is above 50 F. The compressor will not be used for heating when the FP1 is below 50 F and the compressor will operate in emergency heat mode, staging on EH1 and EH2 to provide heat. If a thermal switch is being used instead of the FP1 thermistor, only the compressor will be used for heating mode when the FP1 terminals are closed. If the FP1 terminals are open, the compressor is not used and the control goes into emergency heat mode.
DIP SWITCH BLOCK 2 (S2) — The following set of DIP switches is used to configure accessory relay options.
Switches 1 to 3 — These DIP switches provide selection of Accessory 1 relay options. See Table 10 for DIP switch combinations.
Table 10 — DIP Switch Block S2 —
Accessory 1 Relay Options
ACCESSORY 1 | DIP SWITCH POSITION | ||
RELAY OPTIONS | 1 | 2 | 3 |
Digital NSB | Off | On | On |
Water Valve — Slow Opening | On | Off | On |
LEGEND |
|
|
|
NSB — Night Setback
NOTE: All other DIP switch combinations are invalid.
Switches 4 to 6 — These DIP switches provide selection of Accessory 2 relay options. See Table 11 for DIP switch combinations.
36