50XT SUGGESTED RIGGING
DETAIL A
A06298
SELECTION PROCEDURE
Determine cooling and heating requirements at design conditions
Given:
REQUIRED COOLING CAPACITY (TC) . . . . . . 34,500 BTUH SENSIBLE HEAT CAPACITY (SHC) . . . . . . . . . 24,000 BTUH REQUIRED HEATING CAPACITY (SHC) . . . . . 36,000 BTUH CONDENSER ENTERING AIR TEMPERATURE 95°F (35°C)
EVAPORATOR AIR QUANTITY . . . . . . . . . . . . . . . 1200 CFM ELECTRICAL CHARACTERISTICS . . . . . . . . . . . . .
Select unit based on required cooling capacity
Enter Net Cooling Capacities table at condenser entering temperature of 95°F (35°C). The 036 unit at 1200 cfm and 67°F (19.4°C) ewb (entering wet bulb) will provide a total capacity of 34,600 Btuh and a SHC of 24,220 Btuh. Calculate SHC correction, if required, using Note 4 under Cooling Capacities tables.
Select electric heat
Enter the 036 unit Heating Extended Performance table at 1200 cfm. At 70°F (21.1°C) return indoor air and 20°F
The required heating capacity is 36,000 Btuh. Therefore, at least 19,190 Btuh additional electric heat is required.
Determine additional electric heat capacity in kW.
19,190 Btuh
3414 Btuh/kW
= 5.6kW of heat required
|
|
|
| A06296 |
|
|
|
|
|
CABINET | MODEL | RIGGING WT |
| |
|
|
| ||
|
| lb |
| kg |
Small | 418 |
| 190 | |
448 |
| 203 | ||
|
| |||
|
|
|
|
|
| 469 |
| 213 | |
Large | 491 |
| 223 | |
497 |
| 225 | ||
|
| |||
| 548 |
| 249 | |
NOTE: See dimensional drawing for corner weight distribution. Corner | ||||
weights shown on drawing are based on | ||||
not include packaging. |
|
|
|
Enter the Electric Heater table on page 5 for 208/230v,
7.2 kW x 0.92 = 6.6 kW
6.6kW x 3414 Btuh/kW = 22,532 Btuh Total unit heating capacity is 39,342 Btuh (16,810 + 22,532).
Select unit that corresponds to power source available
The Electrical Data table shows that the unit is designed to operate at