Wet coil air delivery - low stage
|
|
|
| 208/230 VOLT |
|
|
|
|
|
| ||
UNIT | SYSTEM SETTING |
|
|
| EXTERNAL STATIC PRESSURE (in. wc) |
|
|
| ||||
SIZE | 0.1 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 | 1.0 | ||
| ||||||||||||
| COMFORT (Default) |
|
|
| Variable based on Comfort Settings |
|
|
| ||||
024 | EFFICIENCY | 525 | 525 | 525 | 525 | 525 | 525 | 525 | 525 | 525 | 525 | |
| MAX | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | |
| COMFORT (Default) |
|
|
| Variable based on Comfort Settings |
|
|
| ||||
030 | EFFICIENCY | 613 | 613 | 613 | 613 | 613 | 613 | 613 | 613 | 613 | 613 | |
| MAX | 700 | 700 | 700 | 700 | 700 | 700 | 700 | 700 | 700 | 700 | |
| COMFORT (Default) |
|
|
| Variable based on Comfort Settings |
|
|
| ||||
036 | EFFICIENCY | 743 | 743 | 743 | 743 | 743 | 743 | 743 | 743 | 743 | 743 | |
| MAX | 850 | 850 | 850 | 850 | 850 | 850 | 850 | 850 | 850 | 850 | |
| COMFORT (Default) |
|
|
| Variable based on Comfort Settings |
|
|
| ||||
042 | EFFICIENCY | 853 | 853 | 853 | 853 | 853 | 853 | 853 | 853 | 853 | 853 | |
| MAX | 975 | 975 | 975 | 975 | 975 | 975 | 975 | 975 | 975 | 975 | |
| COMFORT (Default) |
|
|
| Variable based on Comfort Settings |
|
|
| ||||
048 | EFFICIENCY | 963 | 963 | 963 | 963 | 963 | 963 | 963 | 963 | 963 | 963 | |
| MAX | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | |
| COMFORT (Default) |
|
|
| Variable based on Comfort Settings |
|
|
| ||||
060 | EFFICIENCY | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | |
| MAX | 1372 | 1372 | 1372 | 1372 | 1372 | 1372 | 1372 | 1372 | 1372 | 1372 |
Wet coil air delivery - high stage
|
|
|
| 208/230 VOLT |
|
|
|
|
|
| ||
UNIT | SYSTEM SETTING |
|
|
| EXTERNAL STATIC PRESSURE (in. wc) |
|
|
| ||||
SIZE | 0.1 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 | 1.0 | ||
| ||||||||||||
| COMFORT (Default) |
|
|
| Variable based on Comfort Settings |
|
|
| ||||
024 | EFFICIENCY | 700 | 700 | 700 | 700 | 700 | 700 | 700 | 700 | 700 | 700 | |
| MAX | 800 | 800 | 800 | 800 | 800 | 800 | 800 | 800 | 800 | 800 | |
| COMFORT (Default) |
|
|
| Variable based on Comfort Settings |
|
|
| ||||
030 | EFFICIENCY | 875 | 875 | 875 | 875 | 875 | 875 | 875 | 875 | 875 | 875 | |
| MAX | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | |
| COMFORT (Default) |
|
|
| Variable based on Comfort Settings |
|
|
| ||||
036 | EFFICIENCY | 1050 | 1050 | 1050 | 1050 | 1050 | 1050 | 1050 | 1050 | 1050 | 1050 | |
| MAX | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | |
| COMFORT (Default) |
|
|
| Variable based on Comfort Settings |
|
|
| ||||
042 | EFFICIENCY | 1225 | 1225 | 1225 | 1225 | 1225 | 1225 | 1225 | 1225 | 1225 | 1225 | |
| MAX | 1400 | 1400 | 1400 | 1400 | 1400 | 1400 | 1400 | 1400 | 1400 | 1400 | |
| COMFORT (Default) |
|
|
| Variable based on Comfort Settings |
|
|
| ||||
048 | EFFICIENCY | 1400 | 1400 | 1400 | 1400 | 1400 | 1400 | 1400 | 1400 | 1400 | 1400 | |
| MAX | 1600 | 1600 | 1600 | 1600 | 1600 | 1600 | 1600 | 1600 | 1600 | 1600 | |
| COMFORT (Default) |
|
|
| Variable based on Comfort Settings |
|
|
| ||||
060 | EFFICIENCY | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | |
| MAX | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 |
Air delivery values are based on operating voltage of 230v, and wet coil. Filter and electric heater will not change air delivery values.
NOTES:
1.See User Interface instructions for more information on Max, Efficiency, and Comfort Settings
2.Efficiency Setting operates at 350 cfm/ton (nominal) and Max Setting operates at 400 cfm/ton (nominal)
30