50XT
PERFORMANCE
Heating Capacity
50XT024 High
INDOOR AIR |
|
|
|
|
| OUTDOOR COIL ENTERING AIR TEMPERATURES _F (_C) |
|
|
|
|
| ||||||||||
|
|
|
|
| 0 |
|
| 10 |
|
| 17 |
|
| 20 |
| ||||||
EDB |
| Capacity |
| Total | Capacity |
| Total | Capacity |
| Total | Capacity |
| Total | Capacity |
| Total | |||||
_F | CFM | MBtuh |
| System | MBtuh |
| System | MBtuh |
| System | MBtuh |
| System | MBtuh |
| System | |||||
(_C) |
|
|
|
| KW |
|
|
| KW |
|
|
| KW |
|
|
| KW |
|
|
| KW |
| Total | Integ | Total | Integ | Total | Integ | Total | Integ | Total | Integ | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
60 | 700 | 4.21 | 3.88 |
| 1.12 | 6.40 | 5.89 |
| 1.21 | 9.38 | 8.61 |
| 1.32 | 11.90 | 10.85 |
| 1.42 | 14.22 | 12.90 |
| 1.45 |
(15.6) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
800 | 4.24 | 3.90 |
| 1.11 | 6.47 | 5.95 |
| 1.20 | 9.46 | 8.69 |
| 1.31 | 11.94 | 10.89 |
| 1.43 | 14.27 | 12.94 |
| 1.44 | |
70 | 700 | 3.97 | 3.65 |
| 1.25 | 6.12 | 5.63 |
| 1.35 | 9.01 | 8.27 |
| 1.46 | 11.51 | 10.49 |
| 1.55 | 12.36 | 11.21 |
| 1.49 |
(21.1) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
800 | 4.02 | 3.70 |
| 1.24 | 6.20 | 5.71 |
| 1.34 | 9.12 | 8.37 |
| 1.45 | 11.60 | 10.58 |
| 1.55 | 12.46 | 11.30 |
| 1.66 | |
80 | 700 | 3.77 | 3.47 |
| 1.38 | 5.83 | 5.36 |
| 1.49 | 8.62 | 7.91 |
| 1.61 | 11.03 | 10.06 |
| 1.70 | 11.85 | 10.75 |
| 1.75 |
(26.7) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
800 | 3.82 | 3.51 |
| 1.38 | 5.91 | 5.43 |
| 1.48 | 8.74 | 8.02 |
| 1.59 | 11.17 | 10.19 |
| 1.69 | 12.00 | 10.88 |
| 1.72 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
50XT024 High Con’t.
| INDOOR AIR |
|
|
|
|
| OUTDOOR COIL ENTERING AIR TEMPERATURES _F (_C) |
|
|
|
|
| |||||||||
|
|
|
|
|
| 30 |
|
| 40 (4.4) |
|
| 47 (8.3) |
|
| 50 (10) |
|
| 60 (15.5) |
| ||
| EDB |
|
| Capacity |
| Total | Capacity | Total | Capacity | Total | Capacity | Total | Capacity |
| Total | ||||||
|
| _F |
| CFM | MBtuh |
| System | MBtuh | System | MBtuh | System | MBtuh | System | MBtuh |
| System | |||||
| (_C) |
|
|
|
|
| KW |
|
| KW |
|
| KW |
|
| KW |
|
|
| KW | |
|
| Total | Integ | Total | Integ | Total | Integ | Total | Integ | Total | Integ | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 60 |
| 700 | 16.65 | 14.60 |
| 1.58 | 19.30 | 19.30 | 1.69 | 21.15 | 21.15 | 1.75 | 22.00 | 22.00 | 1.78 | 25.14 | 25.14 |
| 1.92 |
| (15.6) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 800 | 16.84 | 14.76 |
| 1.53 | 19.36 | 19.36 | 1.61 | 21.27 | 21.27 | 1.66 | 22.16 | 22.16 | 1.70 | 25.40 | 25.40 |
| 1.82 | |||
12 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 70 |
| 700 | 16.03 | 14.05 |
| 1.62 | 18.69 | 18.69 | 1.86 | 20.68 | 20.68 | 1.95 | 21.51 | 21.51 | 1.98 | 24.54 | 24.54 |
| 2.11 | |
|
|
|
|
| |||||||||||||||||
| (21.1) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 800 | 16.25 | 14.24 |
| 1.68 | 18.95 | 18.95 | 1.79 | 20.80 | 20.80 | 1.85 | 21.65 | 21.65 | 1.87 | 24.82 | 24.82 |
| 2.00 | |||
|
| 80 |
| 700 | 14.91 | 13.06 |
| 1.89 | 17.97 | 17.97 | 2.03 | 20.04 | 20.04 | 2.14 | 20.96 | 20.96 | 2.20 | 23.91 | 23.91 |
| 2.32 |
| (26.7) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| 800 | 15.10 | 13.23 |
| 1.84 | 18.27 | 18.27 | 1.96 | 20.30 | 20.30 | 2.05 | 21.13 | 21.13 | 2.08 | 24.20 | 24.20 |
| 2.21 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| LEGEND |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| Cap.— Heating Capacity (1000 Btuh) (Includes |
|
|
|
|
|
|
|
|
|
| ||||||||||
| db | — Dry Bulb |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| kW — Total Power Input (Includes Compressor Motor Power Input |
|
|
|
|
| |||||||||||||||
| rh | — Relative Humidity |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| NOTES: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it. |
|
|
|
|
|