Carrier Performance Data-Standardecm Indoor Motor, Heating Capacity 50XT030 Low, Dry Bulb

Models: 50XT

1 38
Download 38 pages 34.13 Kb
Page 16
Image 16
Heating Capacity

50XT

PERFORMANCE DATA-STANDARD ECM INDOOR MOTOR

Heating Capacity

50XT030 Low

 

INDOOR AIR

 

 

 

 

 

OUTDOOR COIL ENTERING AIR TEMPERATURES _F (_C)

 

 

 

 

 

 

 

 

 

 

 

-10 (-23.3)

 

 

0 (-17.7)

 

 

10 (-12.2)

 

 

17 (-8.3)

 

 

20 (-6.6)

 

 

EDB

 

 

Capacity

 

Total

Capacity

 

Total

Capacity

 

Total

Capacity

 

Total

Capacity

 

Total

 

 

_F

 

CFM

MBtuh

 

System

MBtuh

 

System

MBtuh

 

System

MBtuh

 

System

MBtuh

 

System

 

(_C)

 

 

 

 

 

KW

 

 

 

KW

 

 

 

KW

 

 

 

KW

 

 

 

KW

 

 

Total

Integ

Total

Integ

Total

Integ

Total

Integ

Total

Integ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

615

3.77

3.47

 

1.12

5.75

5.29

 

1.20

8.06

7.40

 

1.27

9.90

9.03

 

1.32

10.75

9.75

 

1.34

 

(15.6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

700

3.81

3.51

 

1.12

5.82

5.36

 

1.19

8.16

7.49

 

1.25

10.01

9.13

 

1.29

10.87

9.86

 

1.31

 

 

70

 

615

3.34

3.07

 

1.29

5.44

5.00

 

1.38

7.66

7.03

 

1.46

9.47

8.64

 

1.51

10.31

9.35

 

1.53

 

(21.1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

700

3.42

3.15

 

1.29

5.55

5.10

 

1.37

7.75

7.11

 

1.44

9.60

8.75

 

1.48

10.45

9.47

 

1.50

 

 

80

 

615

2.85

2.62

 

1.47

4.84

4.45

 

1.57

7.16

6.57

 

1.65

8.97

8.18

 

1.71

9.80

8.89

 

1.73

 

(26.7)

 

700

2.91

2.68

 

1.47

4.93

4.54

 

1.56

7.27

6.67

 

1.63

9.10

8.30

 

1.68

9.94

9.02

 

1.70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50XT030 Low Con’t.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR AIR

 

 

 

 

 

OUTDOOR COIL ENTERING AIR TEMPERATURES _F (_C)

 

 

 

 

 

 

 

 

 

 

 

30 (-1.1)

 

 

40 (4.4)

 

 

 

47 (8.3)

 

 

 

50 (10)

 

 

 

60 (15.5)

 

 

EDB

 

 

Capacity

 

Total

Capacity

 

Total

Capacity

 

Total

Capacity

 

Total

Capacity

 

Total

 

 

_F

 

CFM

MBtuh

 

System

MBtuh

 

System

MBtuh

 

System

MBtuh

 

System

MBtuh

 

System

 

(_C)

 

 

 

 

 

KW

 

 

 

KW

 

 

 

KW

 

 

 

KW

 

 

 

KW

 

 

Total

Integ

Total

Integ

Total

Integ

Total

Integ

Total

Integ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

615

13.95

12.23

 

1.41

17.78

17.78

 

1.50

20.83

20.83

 

1.57

22.25

22.25

 

1.61

27.83

27.83

 

1.75

 

(15.6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

700

14.14

12.39

 

1.37

18.04

18.04

 

1.45

21.17

21.17

 

1.51

22.64

22.64

 

1.54

28.00

28.00

 

1.62

 

 

70

 

615

13.39

11.73

 

1.61

17.11

17.11

 

1.70

20.08

20.08

 

1.78

21.45

21.45

 

1.81

26.70

26.70

 

1.96

 

(21.1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

700

13.58

11.90

 

1.57

17.39

17.39

 

1.65

20.40

20.40

 

1.71

21.80

21.80

 

1.74

27.26

27.26

 

1.87

 

 

80

 

615

12.86

11.27

 

1.82

16.41

16.41

 

1.92

19.37

19.37

 

2.01

20.70

20.70

 

2.05

25.66

25.66

 

2.20

 

(26.7)

 

700

13.03

11.42

 

1.78

16.66

16.66

 

1.86

19.66

19.66

 

1.93

21.02

21.02

 

1.96

26.16

26.16

 

2.09

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cap.— Heating Capacity (1000 Btuh) (Includes Indoor-Fan Motor Heat)

 

 

 

 

 

 

 

 

 

 

 

 

 

db

— Dry Bulb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

kW — Total Power Input (Includes Compressor Motor Power Input Outdoor-Fan Motor Input, and Indoor-Fan Motor Input)

 

 

 

 

 

 

rh

— Relative Humidity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.

 

 

 

 

 

Page 16
Image 16
Carrier manual Performance Data-Standardecm Indoor Motor, Heating Capacity 50XT030 Low, 50XT030 Low Con’t, Dry Bulb