Carrier 50XT manual Performance Data Cont, Multiplication Factors

Models: 50XT

1 38
Download 38 pages 34.13 Kb
Page 29
Image 29
PERFORMANCE DATA (CONT)

PERFORMANCE DATA (CONT)

Multiplication Factors

Heater kW

Voltage Distribution

Multiplication Factor

Rating

V/3/60

 

 

 

 

 

200

.69

 

 

 

240

208

.75

 

 

230

.92

 

 

 

 

 

240

1.00

LEGEND

BF— Bypass Factor edb— Entering Dry-Bulb Ewb— Entering Wet-Bulb kW — Total Unit Power Input ldb— Leaving Dry-Bulb lwb— Leaving Wet-Bulb

SHC— Sensible Heat Capacity (1000 Btuh) TC — Total Capacity (1000 Btuh) (net)

*At 75°F (23.8°C) entering dry bulb (Tennessee Valley Authority [TVA] rating conditions); all other at 80°F (26.6°C) entering dry bulb.

COOLING NOTES:

1.Ratings are net; they account for the effects of the evaporator fan motor power and heat.

2.Direct interpolation is permissible. Do not extrapolate.

3.The following formulas may be used:

Example: 15.0 kW (at 240v) heater on 208v

=15.0 (.75 mult factor)

=11.25 capacity at 208v

Sensible capacity (Btuh) tldb = tedb --1.10 x cfm

tlwb = Wet---bulb temperature corresponding to enthalpy air leaving evaporator coil (hlwb)

total capacity (Btuh) hlwb = hewb ---

4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

4.The SHC is based on 80_F (26.6_C) edb temperature of air entering evaporator coil. Below 80_F (26.6_C) edb, subtract (corr factor x cfm) from SHC.

Above 80_F (26.6_C) edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 + BF) x (edb + 80).

5.Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.

50XT

29

Page 29
Image 29
Carrier 50XT manual Performance Data Cont, Multiplication Factors