GUIDE SPECIFICATIONS
CONSTANT VOLUME APPLICATION
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 2 TO 5 TONS, NOMINAL (COOLING)
MODEL NUMBER: 50XT
PART I - GENERAL
SYSTEM DESCRIPTION
Outdoor rooftop or ground mounted heat pump unit utilizing a hermetic,
QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standards 210/240 and 270.
B. Unit shall be designed in accordance with UL Standard 1995.
C.Unit shall be manufactured in a facility registered to ISO 9001 manufacturing quality standard
D.Unit shall be UL listed and
E.Roof curb shall be designed to conform to NRCA Standards.
F.Insulation and adhesives shall meet NFPA 90A requirements for flame spread and smoke generation.
G.Cabinet insulation shall meet ASHRAE Standard 62P.
DELIVERY, STORAGE, AND HANDLING
Unit shall be stored and handled per manufacturer’s recommen- dations.
PART 2- PRODUCTS
EQUIPMENT
A. General:
B.Unit Cabinet:
1.Unit cabinet shall be constructed of phosphated,
2.Normal service shall be through a single removable cabinet panel.
3.The unit shall be constructed on a rust proof unit base that has an externally trapped, integrated sloped drain pan.
4.Indoor fan compartment top surface shall be insulated with a
minimum
5.Unit shall have a
C.Fans:
1.The indoor fan shall be
2.Fan wheel shall be made from steel, be
3.Outdoor fan shall be of the
D.Compressor:
1.Fully hermetic,
2.Scroll compressors shall be standard on all units.
3.Compressor Protection:
Defrost control shall protect compressor by preventing “short cycling.”
E.Coils:
1.Indoor and outdoor coils shall have aluminum plate fins mechanically bonded to seamless copper tubes with all joints brazed.
2.Tube sheet openings shall be bellied to prevent tube wear.
F.Refrigerant Metering Device:
Refrigerant metering device shall be of the single body, fixed orifice feed type (outdoor) and TXV (indoor).
G.Filters:
Filter section shall consist of
H.Controls and Safeties:
1.Unit controls shall be complete with
2.Units shall incorporate an internal compressor protector that provides reset capability.
3.Unit shall provide high- and
I.Operating Characteristics:
1.Unit shall be capable of starting and running at 125°F (51.6_C) ambient outdoor temperature, exceeding maximum load criteria of ARI Standard 240.
2.Compressor shall be capable of operation down to 55°F (12.7_C) ambient outdoor temperature in cooling and
3.Unit shall be capable of
J.Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single location.
K.Motors:
1.Compressor motors shall be of the
2.All fan motors shall have permanently lubricated bearings and inherent
3.Outdoor fan motor shall be totally enclosed.
L.Grille
1.Louvered Grille:
Louvered grille shall be standard on all units.
36