APPLICATION DATA
Condensate trap — A
1” (25mm) MIN.
TRAP OUTLET
2” (50mm) MIN.
Ductwork — Secure downflow discharge ductwork to roof curb. For horizontal discharge applications, attach ductwork to unit with flanges.
To convert a unit to downflow discharge — Units are equipped with
Minimum cooling ambient operating temperature — All stan- dard units have a minimum ambient operating temperature of 55°F (12.7°C). With
Maximum operating outdoor air temperature — Maximum out- door operating air temperature for cooling is 125°F (51.6°C).
Balance Point Worksheet
|
|
| 70 | Based on Entering Indoor Air of 70 Deg. F and Rated CFM |
| ||||||
|
|
|
|
| |||||||
Building Heat Loss, 1000BTUH | Unit Integrated Heating Capacity, |
| 60 |
|
|
|
|
|
|
|
|
| 50 |
|
|
|
|
|
|
|
| ||
1000BTUH | 40 |
|
|
|
|
|
|
|
| ||
30 |
|
|
|
|
|
|
|
| |||
20 |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |||
|
|
| 10 |
|
|
|
|
|
|
|
|
|
|
| 0 |
|
|
|
|
|
|
|
|
|
|
| 0 | 10 | 20 | 30 | 40 | 50 | 60 |
Outdoor Air Temp (Deg F)
060
048
042
036
030 024
C03008