Table 10—Model 58TMA Orifice Size and Manifold Pressure for Correct Input—Continued

(TABULATED DATA BASED ON 21,000 BTUH HIGH HEAT/13,500 BTUH LOW HEAT PER BURNER,

DERATED 4% FOR EACH 1000 FT ABOVE SEA LEVEL)*

 

 

 

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

ALTITUDE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

HEAT VALUE

 

 

 

 

 

 

 

RANGE

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(FT)

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTU/CU FT)

No.

 

No.

 

No.

 

No.

 

No.

 

 

 

 

 

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

 

725

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.4

43

 

3.6/1.5

43

 

3.7/1.5

 

 

 

750

44

 

3.5/1.5

44

 

3.6/1.5

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.4

Only

 

 

775

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.5

44

 

3.6/1.5

44

 

3.7/1.5

 

4001

800

45

 

3.7/1.5

44

 

3.2/1.3

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.5

 

 

825

46

 

3.7/1.5

46

 

3.8/1.6

45

 

3.8/1.6

44

 

3.2/1.3

44

 

3.3/1.4

U.S.A.

 

 

 

 

 

 

 

 

to

850

46

 

3.5/1.4

46

 

3.6/1.5

46

 

3.7/1.5

46

 

3.8/1.6

45

 

3.8/1.6

 

 

875

47

 

3.7/1.5

46

 

3.4/1.4

46

 

3.5/1.5

46

 

3.6/1.5

46

 

3.7/1.5

 

 

5000

900

47

 

3.5/1.5

47

 

3.6/1.5

47

 

3.8/1.6

46

 

3.4/1.4

46

 

3.5/1.5

 

 

 

925

48

 

3.8/1.6

47

 

3.4/1.4

47

 

3.6/1.5

47

 

3.7/1.5

47

 

3.8/1.6

 

 

 

950

48

 

3.6/1.5

48

 

3.7/1.5

48

 

3.8/1.6

47

 

3.5/1.4

47

 

3.6/1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

ALTITUDE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

HEAT VALUE

 

 

 

 

 

 

 

RANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(FT)

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTU/CU FT)

No.

 

No.

 

No.

 

No.

 

No.

 

 

 

 

 

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

 

700

44

 

3.5/1.5

44

 

3.6/1.5

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.4

 

 

 

725

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.4

44

 

3.6/1.5

44

 

3.7/1.5

 

 

 

750

45

 

3.7/1.5

44

 

3.2/1.3

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.4

 

 

 

775

46

 

3.6/1.5

46

 

3.8/1.6

45

 

3.7/1.5

44

 

3.2/1.3

44

 

3.3/1.4

Only

 

5001

800

46

 

3.4/1.4

46

 

3.5/1.5

46

 

3.7/1.5

46

 

3.8/1.6

45

 

3.7/1.5

 

 

825

47

 

3.7/1.5

47

 

3.8/1.6

46

 

3.4/1.4

46

 

3.6/1.5

46

 

3.7/1.5

 

to

850

47

 

3.4/1.4

47

 

3.6/1.5

47

 

3.7/1.5

47

 

3.8/1.6

46

 

3.5/1.4

U.S.A.

 

 

 

 

 

 

 

 

875

48

 

3.7/1.5

48

 

3.8/1.6

47

 

3.5/1.4

47

 

3.6/1.5

47

 

3.7/1.5

 

6000

900

48

 

3.5/1.4

48

 

3.6/1.5

48

 

3.7/1.5

47

 

3.4/1.4

47

 

3.5/1.4

 

 

 

 

 

 

 

 

 

 

925

48

 

3.3/1.4

48

 

3.4/1.4

48

 

3.5/1.5

48

 

3.6/1.5

48

 

3.8/1.6

 

 

 

950

49

 

3.7/1.5

49

 

3.8/1.6

48

 

3.3/1.4

48

 

3.5/1.4

48

 

3.6/1.5

 

 

 

975

49

 

3.5/1.4

49

 

3.6/1.5

49

 

3.7/1.5

48

 

3.3/1.4

48

 

3.4/1.4

 

 

 

1000

49

 

3.3/1.4

49

 

3.4/1.4

49

 

3.6/1.5

49

 

3.7/1.5

49

 

3.8/1.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

ALTITUDE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

HEAT VALUE

 

 

 

 

 

 

 

RANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(FT)

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTU/CU FT)

No.

 

No.

 

No.

 

No.

 

No.

 

 

 

 

 

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

 

650

44

 

3.5/1.5

44

 

3.7/1.5

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.4

 

 

 

675

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.4

44

 

3.6/1.5

44

 

3.7/1.5

Only

 

 

700

45

 

3.7/1.5

44

 

3.2/1.3

44

 

3.3/1.3

44

 

3.4/1.4

44

 

3.5/1.4

 

6001

725

46

 

3.6/1.5

46

 

3.7/1.5

45

 

3.7/1.5

45

 

3.8/1.6

44

 

3.2/1.3

 

 

750

47

 

3.8/1.6

46

 

3.5/1.4

46

 

3.6/1.5

46

 

3.7/1.5

46

 

3.8/1.6

U.S.A.

 

 

 

 

 

 

 

 

to

775

47

 

3.6/1.5

47

 

3.7/1.5

47

 

3.8/1.6

46

 

3.5/1.4

46

 

3.6/1.5

 

 

800

48

 

3.8/1.6

47

 

3.5/1.4

47

 

3.6/1.5

47

 

3.7/1.5

47

 

3.8/1.6

 

 

7000

825

48

 

3.6/1.5

48

 

3.7/1.5

48

 

3.8/1.6

47

 

3.5/1.4

47

 

3.6/1.5

 

 

 

850

48

 

3.4/1.4

48

 

3.5/1.4

48

 

3.6/1.5

48

 

3.7/1.5

47

 

3.4/1.4

 

 

 

875

49

 

3.8/1.6

48

 

3.3/1.4

48

 

3.4/1.4

48

 

3.5/1.5

48

 

3.6/1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*For 125-20 size only, input is 20,500 Btuh for high fire. Deduct 0.1-in. from manifold pressure shown in table. Change orifice size if manifold pressure falls below 3.2-in. wc.