Carrier 58TMA → -HorizontalInstallation on Blocks, HorizontalFilter Arrangement

Models: 58TMA

1 24
Download 24 pages 11.84 Kb
Page 9
Image 9
→ Fig. 10—Horizontal Installation on Blocks

A95235

Fig. 10—Horizontal Installation on Blocks

AIRFLOW

Fig. 11—Horizontal Filter Arrangement 12

Table 4—Filter Retainer (In.) 4Fig. 12—Downflow Filter Arrangement A88486D

FIELD-SUPPLIED￿

FILTER RETAINERS

Fig. 11—Horizontal Filter Arrangement

Table 4—Filter Retainer (In.)

FURNACE CASING WIDTH

FILTERS

D

14-3/16

(2) 14 X 20 X 1

14-3/8

17-1/2

(2) 14 X 20 X 1

13-3/8

21

(2) 16 X 20 X 1

11-5/8

24-1/2

(2) 16 X 20 X 1

10-1/4

 

 

 

If flexible connector is required or allowed by authority having jurisdiction, black iron pipe shall be installed at gas valve and extend a minimum of 2 in. outside furnace casing.

Use the proper length of pipes to avoid stress on gas control manifold. A failure to follow this warning could result in a gas leak causing fire, explosion, personal injury, or death.

Use a backup wrench at furnace gas control when connecting gas pipe to furnace to avoid damaging gas controls or manifold.

Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution to check for gas leaks. A failure to follow this warning could result in fire, explosion, personal injury, or death.

Joint compounds (pipe dope) should be applied sparingly and only to male threads of joints. This pipe dope must be resistant to action of propane gas.

AIRFLOW Table 5—Maximum Capacity of Pipe*

INSTALLATION￿

POSITION￿

OF FILTERS

RETURN-AIR￿

PLENUM

ACCESS DOOR

Fig. 12—Downflow Filter Arrangement A88486

Table 5—Maximum Capacity of Pipe*

NOMINAL

INTERNAL

 

LENGTH OF PIPE (FT)

 

IRON PIPE

DIAMETER

 

 

 

 

 

 

10

 

20

30

40

50

SIZE (IN.)

(IN.)

 

1/2

0.622

175

 

120

97

82

73

3/4

0.824

360

 

250

200

170

151

1

1.049

680

 

465

375

320

285

1-1/4

1.380

1400

 

950

770

660

580

1-1/2

1.610

2100

 

1460

1180

990

900

 

 

 

 

 

 

 

 

*Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a supply line pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table 10-2, NFPA 54-1996.

Install accessible manual shutoff valve upstream of furnace gas controls and within 72 in. of furnace. A 1/8-in. NPT plugged tapping is provided on gas value for test gage connection. Installation of additional 1/8-in. NPT plugged tapping, accessible for test gage connection, installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff valve is not required. Place ground joint union between gas control manifold and manual shutoff.

Install sediment trap in riser leading to furnace. The trap can be installed by connecting a tee to riser leading from furnace. Connect capped nipple into lower end of tee. The capped nipple should extend below level of gas controls. (See Fig. 13.)

Piping should be pressure tested in accordance with local and national plumbing and gas codes before furnace has been attached. If test pressure exceeds 0.5 psig (14-in. wc), the gas supply pipe must be disconnected from furnace and capped before pressure test. If test pressure is equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff switch located on the gas valve before test. (See Fig. 13.) It is recommended that ground joint union be loosened before pressure testing.

After all connections have been made, purge lines and check for gas leakage with regulated gas supply pressure.

9

Page 9
Image 9
Carrier 58TMA operating instructions → -HorizontalInstallation on Blocks, HorizontalFilter Arrangement, FilterRetainer In