Table 10—Model 58TMA Orifice Size and Manifold Pressure for Correct Input—Continued

(TABULATED DATA BASED ON 21,000 BTUH HIGH HEAT/13,500 BTUH LOW HEAT PER BURNER,

DERATED 4% FOR EACH 1000 FT ABOVE SEA LEVEL)*

 

 

 

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

ALTITUDE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

HEAT VALUE

 

 

 

 

 

 

 

RANGE

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(FT)

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTU/CU FT)

No.

 

No.

 

No.

 

No.

 

No.

 

 

 

 

 

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

 

625

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.5

44

 

3.6/1.5

44

 

3.7/1.5

 

 

 

650

45

 

3.7/1.5

45

 

3.8/1.6

44

 

3.3/1.3

44

 

3.4/1.4

44

 

3.5/1.4

Only

 

 

675

46

 

3.6/1.5

46

 

3.7/1.5

46

 

3.8/1.6

45

 

3.8/1.6

44

 

3.2/1.3

 

7001

700

47

 

3.8/1.6

46

 

3.4/1.4

46

 

3.6/1.5

46

 

3.7/1.5

46

 

3.8/1.6

 

 

725

47

 

3.5/1.5

47

 

3.6/1.5

47

 

3.8/1.6

46

 

3.4/1.4

46

 

3.5/1.5

U.S.A.

 

 

 

 

 

 

 

 

to

750

48

 

3.7/1.5

47

 

3.4/1.4

47

 

3.5/1.5

47

 

3.6/1.5

47

 

3.7/1.5

 

 

775

48

 

3.5/1.5

48

 

3.6/1.5

48

 

3.8/1.6

47

 

3.4/1.4

47

 

3.5/1.4

 

 

8000

800

48

 

3.3/1.4

48

 

3.4/1.4

48

 

3.5/1.5

48

 

3.6/1.5

48

 

3.7/1.5

 

 

 

825

49

 

3.6/1.5

49

 

3.8/1.6

48

 

3.3/1.4

48

 

3.4/1.4

48

 

3.5/1.5

 

 

 

850

49

 

3.4/1.4

49

 

3.5/1.5

49

 

3.7/1.5

49

 

3.8/1.6

48

 

3.3/1.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

ALTITUDE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

HEAT VALUE

 

 

 

 

 

 

 

RANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(FT)

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTU/CU FT)

No.

 

No.

 

No.

 

No.

 

No.

 

 

 

 

 

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

 

600

45

 

3.7/1.5

44

 

3.2/1.3

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.4

 

 

 

625

46

 

3.6/1.5

46

 

3.7/1.5

46

 

3.8/1.6

45

 

3.8/1.6

44

 

3.2/1.3

Only

 

8001

650

47

 

3.8/1.6

46

 

3.4/1.4

46

 

3.5/1.5

46

 

3.7/1.5

46

 

3.8/1.6

 

 

675

47

 

3.5/1.4

47

 

3.6/1.5

47

 

3.7/1.5

47

 

3.8/1.6

46

 

3.5/1.4

 

to

700

48

 

3.7/1.5

48

 

3.8/1.6

47

 

3.5/1.4

47

 

3.6/1.5

47

 

3.7/1.5

U.S.A.

 

 

 

 

 

 

 

 

725

48

 

3.4/1.4

48

 

3.6/1.5

48

 

3.7/1.5

48

 

3.8/1.6

47

 

3.4/1.4

 

9000

750

49

 

3.8/1.6

48

 

3.3/1.4

48

 

3.4/1.4

48

 

3.5/1.5

48

 

3.7/1.5

 

 

 

 

 

 

 

 

 

 

775

49

 

3.5/1.5

49

 

3.7/1.5

49

 

3.8/1.6

48

 

3.3/1.4

48

 

3.4/1.4

 

 

 

800

49

 

3.3/1.4

49

 

3.4/1.4

49

 

3.5/1.5

49

 

3.7/1.5

49

 

3.8/1.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

ALTITUDE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

HEAT VALUE

 

 

 

 

 

 

 

RANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(FT)

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTU/CU FT)

No.

 

No.

 

No.

 

No.

 

No.

 

 

 

 

 

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

 

575

46

 

3.6/1.5

46

 

3.7/1.5

46

 

3.8/1.6

45

 

3.8/1.6

44

 

3.2/1.3

 

 

 

600

47

 

3.7/1.5

46

 

3.4/1.4

46

 

3.5/1.5

46

 

3.6/1.5

46

 

3.8/1.6

Only

 

9001

625

47

 

3.4/1.4

47

 

3.6/1.5

47

 

3.7/1.5

47

 

3.8/1.6

46

 

3.5/1.4

 

 

650

48

 

3.6/1.5

48

 

3.8/1.6

47

 

3.4/1.4

47

 

3.5/1.5

47

 

3.6/1.5

 

to

675

48

 

3.4/1.4

48

 

3.5/1.4

48

 

3.6/1.5

48

 

3.7/1.5

48

 

3.8/1.6

U.S.A.

 

 

 

 

 

 

 

 

700

49

 

3.7/1.5

49

 

3.8/1.6

48

 

3.3/1.4

48

 

3.5/1.4

48

 

3.6/1.5

 

10,000

725

49

 

3.4/1.4

49

 

3.5/1.5

49

 

3.7/1.5

49

 

3.8/1.6

48

 

3.3/1.4

 

 

 

 

 

 

 

 

 

 

750

50

 

3.8/1.6

49

 

3.3/1.4

49

 

3.4/1.4

49

 

3.5/1.5

49

 

3.6/1.5

 

 

 

775

50

 

3.5/1.5

50

 

3.7/1.5

50

 

3.8/1.6

49

 

3.3/1.4

49

 

3.4/1.4

*For 125-20 size only, input is 20,500 Btuh for high fire. Deduct 0.1-in. from manifold pressure shown in table. Change orifice size if manifold pressure falls below 3.2-in. wc.