Table 12—Speed Selection
COLOR | SPEED | AS SHIPPED |
White | Common | COM |
Black | High | Cool |
Yellow | SPARE | |
Orange† | Med | SPARE or Capped |
Blue | ||
Red | Low* |
* Continuous fan speed.
† Available on
Recheck temperature rise. It must be within limits specified on unit rating plate. Recommended operation is at midpoint of rise range or above.
THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
R Y W G
10 TURNS
FROM UNIT
CONTROL TERMINALS
EXAMPLE: | 5.0 AMPS ON AMMETER | = | 0.5 AMPS FOR THERMOSTAT | |
10 TURNS AROUND JAWS | ANTICIPATOR SETTING | |||
|
|
A96316
Fig. 21—Amp Draw Check With Ammeter
components in
b.When using an electronic thermostat, set cycle rate for 3 cycles per hr.
CHECK SAFETY CONTROLS
The flame sensor, gas valve, and pressure switches were all checked in the
1.Check primary limit control.
This control shuts off combustion control system and ener- gizes
The preferred method of checking limit control is to gradually block off return air after furnace has been operating for a period of at least 5 minutes. As soon as limit has shut off burners,
2.Check draft safeguard switch.
The purpose of this control is to permit safe shutdown of he furnace during certain blocked vent conditions.
a.Disconnect power to furnace and remove vent connector from furnace flue collar. Be sure to allow time for vent connector pipe to cool down before removing.
b.Restore power to furnace and set room thermostat above room temperature.
c.After normal
d.Remove blockage and reconnect vent connector to furnace flue collar.
e.Wait 5 minutes and then reset draft safeguard switch.
3.Check
This control proves operation of draft inducer blower.
a.Turn off
b.Remove gas control door and disconnect inducer motor lead wires from wire harness.
c.Turn on
d.Close thermostat switch as if making normal furnace start. If hot surface ignitor does not glow within several minutes and control flashes code 32, pressure switches are func- tioning properly.
e.Turn off
f.Reconnect inducer motor wires, replace gas control door, and turn on
4.Check auxiliary limits.
a.Turn off
b.Remove blower access door.
c.Disconnect red motor lead at blower speed selector. Mark terminal for proper reconnection.
d.Replace blower access door.
e.Turn on
f.Allow furnace to operate until auxiliary limit activates, but DO NOT operate furnace longer than 4 minutes.
g.If furnace operates for 4 minutes, check/replace limit switch(es).
h.Turn off
i.Remove blower access door.
j.Reconnect red motor lead, reset switch, and replace door.
k.Turn on
22