GAS
SUPPLY
MANUAL SHUTOFF VALVE (REQUIRED)
SEDIMENT
TRAP
UNION
Fig. 13—Typical Gas Pipe Arrangement A89414
EAC - ELECTRONIC AIR CLEANER
NOTE: Proper polarity must be maintained for
→The cabinet must have an uninterrupted or unbroken ground according to NEC ANSI/NFPA
Refer to ESD Precautions Procedure before proceeding with
Make field
When furnace is installed in horizontal position with RH discharge air,
The
7 8 9
4 5 6
1 2 3
PR2 | L2 | COM | PARK |
|
| ||
PR1 | L1 |
|
| FU1 3 | |||
|
|
|
|
|
| ||
|
|
|
|
| 10 | 11 | 12 |
|
|
|
|
| 7 | 8 | 9 |
|
|
|
|
| 4 | 5 | 6 |
|
|
|
|
| 1 | 2 | 3 |
MASTER
1
FUSE
LED
DIAGNOSTIC LIGHT
TWIN / TEST
TERMINAL
on main control. Any
ACCESSORIES
1. Electronic air cleaner (EAC) |
A terminal block |
|
|
| TWIN TEST | LED |
|
|
|
| 1 |
|
|
|
| HUM |
|
|
|
| G |
|
|
|
| W/W1Y/Y2 R |
|
|
| OFF | COM 24V |
4 | 3 | 2 | 1 |
|
|
|
| ON | W2 |
|
|
|
|
HUM
HUMIDIFIER
AMP MAX)
THERMOSTAT TERMINALS
provided for EAC connection. (See Fig. 14.) The terminals are |
energized with 115v, |
operation. |
2. Humidifier (HUM) |
Screw terminals
FURNACE AND
BLOWER OFF DELAY
SETUP SWITCHES
Fig. | A93348 |
|
Step 8—Electrical Connections
Refer to unit rating plate or Table 6 for equipment electrical requirements. The control system requires an earth ground for proper operation.
Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.
→Make all electrical connections in accordance with the current edition of the National Electrical Code (NEC) ANSI/NFPA
Step 9—VENTING
→Refer to National or Local Installation Code such as; National Fuel Gas Code NFPA No.
Step 10—Start-Up, Adjustment, and Safety Check
GENERAL
The furnace must have a
The gas service pressure must not exceed 0.5 psig
Thermostat wire connections at R and W/W1 are the minimum required for gas heating operation. W2 must be connected for
10