Carrier 58TMA operating instructions Derated 4% for Each 1000 Ft Above Sea Level

Models: 58TMA

1 24
Download 24 pages 11.84 Kb
Page 18
Image 18

Table 10—Model 58TMA Orifice Size and Manifold Pressure for Correct Input

(Tabulated Data Based on 21,000 Btuh High Heat/13,500 Btuh Low Heat per Burner,

Derated 4% for Each 1000 Ft Above Sea Level)*

 

 

 

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

ALTITUDE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

HEAT VALUE

 

 

 

 

 

 

 

RANGE

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(FT)

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTU/CU FT)

No.

 

No.

 

No.

 

No.

 

No.

 

 

 

 

 

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

 

850

42

 

3.3/1.4

42

 

3.4/1.4

42

 

3.5/1.5

42

 

3.7/1.5

42

 

3.8/1.6

 

 

 

875

43

 

3.8/1.6

42

 

3.2/1.3

42

 

3.3/1.4

42

 

3.5/1.4

42

 

3.6/1.5

Canada

 

 

900

43

 

3.6/1.5

43

 

3.7/1.5

42

 

3.2/1.3

42

 

3.3/1.3

42

 

3.4/1.4

 

0

925

43

 

3.4/1.4

43

 

3.5/1.5

43

 

3.6/1.5

43

 

3.8/1.6

42

 

3.2/1.3

 

 

950

44

 

3.7/1.5

44

 

3.8/1.6

43

 

3.5/1.4

43

 

3.6/1.5

43

 

3.7/1.5

and

 

to

975

44

 

3.5/1.5

44

 

3.6/1.5

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.4

 

 

1000

44

 

3.3/1.4

44

 

3.5/1.4

44

 

3.6/1.5

44

 

3.7/1.5

44

 

3.8/1.6

U.S.A.

 

 

 

 

 

 

 

 

2000

1025

44

 

3.2/1.3

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.5

44

 

3.6/1.5

 

 

1050

45

 

3.7/1.5

45

 

3.8/1.6

44

 

3.2/1.3

44

 

3.4/1.4

44

 

3.5/1.4

 

 

 

 

 

 

 

 

 

 

 

1075

46

 

3.7/1.5

46

 

3.8/1.6

45

 

3.7/1.5

44

 

3.2/1.3

44

 

3.3/1.4

 

 

 

1100

46

 

3.5/1.5

46

 

3.6/1.5

46

 

3.8/1.6

45

 

3.7/1.5

45

 

3.8/1.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

ALTITUDE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

HEAT VALUE

 

 

 

 

 

 

 

RANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(FT)

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTU/CU FT)

No.

 

No.

 

No.

 

No.

 

No.

 

 

 

 

 

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

U.S.A.

775

43

 

3.7/1.5

42

 

3.2/1.3

42

 

3.3/1.4

42

 

3.4/1.4

42

 

3.5/1.4

 

 

Altitudes

800

43

 

3.5/1.4

43

 

3.6/1.5

43

 

3.7/1.5

42

 

3.2/1.3

42

 

3.3/1.3

Canada

 

2001

825

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.5

43

 

3.6/1.5

43

 

3.7/1.5

 

to

850

44

 

3.6/1.5

44

 

3.7/1.5

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.5

 

3000

875

44

 

3.4/1.4

44

 

3.5/1.4

44

 

3.6/1.5

44

 

3.7/1.5

44

 

3.8/1.6

and

 

or

900

44

 

3.2/1.3

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.4

44

 

3.6/1.5

 

Canada

925

46

 

3.8/1.6

45

 

3.8/1.6

44

 

3.2/1.3

44

 

3.3/1.4

44

 

3.4/1.4

U.S.A.

 

 

 

 

 

 

 

Altitudes

950

46

 

3.6/1.5

46

 

3.7/1.5

45

 

3.7/1.5

45

 

3.8/1.6

44

 

3.2/1.3

 

2000

975

46

 

3.4/1.4

46

 

3.5/1.5

46

 

3.7/1.5

46

 

3.8/1.6

45

 

3.7/1.5

 

 

 

 

 

 

 

 

 

to

1000

47

 

3.7/1.5

47

 

3.8/1.6

46

 

3.5/1.4

46

 

3.6/1.5

46

 

3.7/1.5

 

 

4500

1025

47

 

3.5/1.5

47

 

3.6/1.5

47

 

3.8/1.6

46

 

3.4/1.4

46

 

3.5/1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

ALTITUDE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

HEAT VALUE

 

 

 

 

 

 

 

RANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(FT)

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

Pressure

 

 

 

(BTU/CU FT)

No.

 

No.

 

No.

 

No.

 

No.

 

 

 

 

 

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

High/Low

 

 

 

750

43

 

3.5/1.4

43

 

3.6/1.5

43

 

3.7/1.5

42

 

3.2/1.3

42

 

3.3/1.4

 

 

 

775

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.4

43

 

3.6/1.5

43

 

3.7/1.5

 

 

 

800

44

 

3.5/1.5

44

 

3.7/1.5

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.4

Only

 

3001

825

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.5

44

 

3.7/1.5

44

 

3.8/1.6

 

 

850

45

 

3.8/1.6

44

 

3.2/1.3

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.6/1.5

U.S.A.

 

to

875

46

 

3.7/1.5

45

 

3.7/1.5

44

 

3.2/1.3

44

 

3.3/1.3

44

 

3.4/1.4

 

 

900

46

 

3.5/1.5

46

 

3.7/1.5

46

 

3.8/1.6

45

 

3.7/1.5

44

 

3.2/1.3

 

4000

925

47

 

3.8/1.6

46

 

3.5/1.4

46

 

3.6/1.5

46

 

3.7/1.5

46

 

3.8/1.6

 

 

 

 

 

 

 

 

 

 

950

47

 

3.6/1.5

47

 

3.7/1.5

46

 

3.4/1.4

46

 

3.5/1.5

46

 

3.6/1.5

 

 

 

975

47

 

3.4/1.4

47

 

3.5/1.5

47

 

3.7/1.5

47

 

3.8/1.6

46

 

3.4/1.4

 

 

 

1000

48

 

3.7/1.5

48

 

3.8/1.6

47

 

3.5/1.4

47

 

3.6/1.5

47

 

3.7/1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*For 125-20 size only, input is 20,500 Btuh for high fire. Deduct 0.1-in. from manifold pressure shown in table. Change orifice size if manifold pressure falls below 3.2-in. wc.