Condensate Drain Kit

FIELD-INSTALLED ACCESSORIES (52P AND 52C) (cont)

Condensate Drain Kit

Part No.: DRAIN-KIT-4PK

This universal drain kit may be used internally or externally to route condensate to a drainage system. It can be field-installed on any Carrier wall sleeve.

Although Carrier’s units are designed to dissipate all the condensate generated during normal cooling, there may be times when abnormal conditions cause more condensate than the unit can dissipate. If condensate that drips from the wall sleeve is objectionable, this internal/external drain kit should be installed.

The drain kit may be attached to the exterior right or left side of the wall sleeve for external draining or may be mounted to the room side of the wall sleeve for internal draining.

IMPORTANT: For internal drains installed in the plastic wall sleeve, the drain must be installed on the flat area of the sleeve. It cannot be installed in the wafer area.

Lateral Duct Kit

Part No.: LATERAL-DUCT (Adapter Plenum and Extension)

The accessory lateral duct kit allows one unit to heat or cool two rooms. The kit provides substantial sav- ings for apartments, hotel suites, and office suites by eliminating the need for separate units for every room. The amount of air that can be diverted to an adjoining room is adjustable from 20 to 30 percent.

The lateral duct kit consists of two main components, the plenum and the extension duct. The kit mounts to the wall sleeve and allows either right or left side duct- ing. Consider the following when designing a ducted application.

The maximum extension of the duct length is 4 feet.

The duct run must be straight and horizontal; no bends or turns.

The minimum recommended clearance between the unit and the adjoining room wall is 6 inches.

You must provide for return air from the adjoining room.

Carrier 52P and 52C units are not qualified for use with any other ducting scheme.

See page 31 for more information.

NOTES:

1.Lateral Duct Kit includes wall register for duct extension and a molding kit to trim the wall open- ing.

2.The sleeve should extend a minimum of 3-in. into the room to install mounting brackets.

3.The Lateral Duct Kit is not compatible with previ- ous PTAC models.

Drain Kit

Lateral Duct Kit

24

Page 24
Image 24