Carrier 592-085 warranty LEGEND AWG — American Wire Gage B— Black

Models: 592-085

1 56
Download 56 pages 23.58 Kb
Page 49
Image 49
LEGEND

 

FRONT DESK SWITCH PANEL

 

ROOM 100

ROOM 101

ROOM N

FIELD-SUPPLIED

24-V

TRANSFORMER

(SEE NOTE 1)

BWBW

PTAC #1

PTAC #2

LEGEND

AWG — American Wire Gage

BBlack

PTAC — Packaged Terminal Air Conditioner

WWhite

NOTES:

1.To size transformer, use the following equation:

Quantity of PTAC units x 12 va = Transformer Size (va) Example: 110 PTAC Units x 12 va = 1320 va Transformer

2.Following are recommended wire sizes:

AWG WIRE SIZE NO.

MAXIMUM LENGTH (ft)

24

400

22

600

20

900

18

1500

16

2000

BW

PTAC #N

Typical Wiring Schematic for Energy Management Kit

49

Page 49
Image 49
Carrier 592-085 warranty LEGEND AWG — American Wire Gage B— Black