WIRING DIAGRAMS (52P AND 52C) (cont)
TYPICAL THERMOSTAT INTERFACE
T’STAT OUTPUT: | RC CONTROLER OUTPUT: | UNIT OPERATION: | |
‘G’ — 24 VAC | ‘FR’ — LINE VAC | FAN | |
‘G’ — 0 VAC | ‘FR’ — 0 VAC | ||
| |||
‘Y’ — 24 VAC | ‘HR1 & HR2’ — LINE VAC | HEATING | |
‘O’ — 0 VAC | ‘RVR’ — LINE VAC | ||
| |||
‘W’ — 24 VAC | ‘HR1 & HR2’ — LINE VAC | HEATING | |
‘Y’ — 24 VAC | ‘CR’ — LINE VAC | COOLING | |
‘O’ — 24 VAC | ‘RVR’ — 0 VAC | ||
| |||
‘R’ — 24 VAC | ‘R’ — 24 VAC OUTPUT | POWER TO WALL | |
‘C’ — COMMON | ‘C’ — COMMON | THERMOSTAT |
1.If ‘W’ is ON, then ‘FR’ is forced ON (regardless of ‘G’) & ‘CR’ is forced OFF.
2.If ‘Y’ is ON, then ‘FR’ is forced ON (regardless of ‘G’).
3.If IFT (indoor coil) is < 20° F, then ‘CR’ is forced OFF until IFT is > 50° F.
|
| COMPONENT LEGEND |
|
|
|
| |||
| Component Connection (Marked) | FM | — | Fan Motor | ST | — | Start Thermistor | ||
| Component Connection (Unmarked) | HTR | — | Heater | TRANS | — | Transformer | ||
| Terminal Board Connection | IFT | — | Indoor Frost Thermostat | PCBD | — | Printed Circuit Board | ||
| Field Splice | OFT | — | Outdoor Frost Thermostat | — HR1 | — | Heater Relay | ||
| Field Control Wiring | OL | — | Overload | — HR2 | — | Heater Relay | ||
| Accessory or Optional Wiring | PLS | — | Primary Limit Switch | — CR | — | Compressor Relay | ||
| To Indicate Common Potential Only Not To Represent Wire | RVS | — | Reversing Valve Solenoid | — FR | — | Fan Relay | ||
CAP | — Capacitor | SLS | — | Secondary Limit Switch | — RVR | — | Reversing Valve Relay | ||
COMP | — Compressor | SSS | — | Speed Selector Switch |
|
|
|
NOTES:
1.Recommended for use on grounded power supply only.
2.Compressor and fan motor thermally protected.
3.Use copper conductors only.
4.All wiring must conform with N.E.C. and local codes.
5.Dashed lines indicate compo- nents when used.
6.Field control wire suitable for N.E.C. class 2 control circuit, at 24 volts.
7.OFT determines whether to bring on compressor heat or electric heat.
52PQ and 52CQ — Typical Wiring Schematic for Wall Thermostat Control Heat Pump Units
46